- 4 -
Dimensions
Unit = mm (inch)
Reset Button
Restore the MGate to factory default settings by using a pointed object
(such as a straightened paper clip) to hold the reset button down until the
Ready LED stops blinking (approximately five seconds).
Pull-Up, Pull-Down, and Terminator for RS-485 (Modbus)
On the MGate 5111’s left side panel, you will find DIP
switches to adjust each serial port’s pull-up resistor,
pull-down resistor, and terminator.
SW
MODBUS
1
2
3
Pull-up
resistor
Pull-down
resistor
Terminator
ON
1
kΩ
1
kΩ
120
Ω
OFF
150
kΩ
(default)
150
kΩ
(default)
– (default)
Rotary Switch
Before communicating, you must assign a slave ID to the
PROFIBUS slave, If you would like to assign an address
between 0 to 99, you need to change the rotary switch to
the desired address. If you would like to assign an
address which is over 99, you must set it via web
console.