- 3 -
LED
Color Function
Off
Gateway is waiting for the PROFIBUS token
Ethernet
Amber
Steady: 10Mbps, no data is transmitting
Blinking: 10Mbps, data is transmitting
Green
Steady: 100Mbps, no data is transmitting
Blinking: 100Mbps, data is transmitting
Off
Ethernet cable is disconnected
Reset Button
The reset button is used to load factory defaults. Use a pointed object
such as a straightened paper clip to hold the reset button down for five
seconds. Release the reset button when the Ready LED stops blinking.
Hardware Installation Procedure
STEP 1
:
Connect the power adapter. Connect the 12-48 VDC power line
or DIN-rail power supply with the MGate 5101-PBM-MN
device’s terminal block.
STEP 2
:
Use a PROFIBUS cable to connect the unit to a PROFIBUS slave
device.
STEP 3
:
Connect the unit to the Modbus TCP device.
STEP 4
:
The MGate 5101-PBM-MN series is designed to be attached to
a DIN rail or mounted on a wall. For DIN-rail mounting, push
down the spring and properly attach it to the DIN-rail until it
“snaps” into place. For wall mounting, install the wall-mount
kit (optional) first and then screw the device onto the wall.