ioThinx 4500 (45ML) Module Series
Hardware Installation
3-2
Module Specifications
Terminal Blocks
Wire range:
18 to 24 AWG
Wire strip length:
9 to 10 mm
Unit: mm (in.)
45ML-5401
Pin Assignment
The following tables shows the 45ML-5401 pin assignments.
Pin
RS-232
RS-422
RS-485
Pin
RS-232
RS-422
RS-485
1
GND
GND
GND
11
GND
GND
GND
Port
1
2
TxD1
TxD1+
Data1+
Port
3
12
TxD3
TxD3+
Data3+
3
RxD1
TxD1-
Data1-
13
RxD3
TxD3-
Data3-
4
RTS1
RxD1+
–
14
RTS3
RxD3+
–
5
CTS1
RxD1-
–
15
CTS3
RxD3-
–
Port
2
6
TxD2
TxD2+
Data2+
Port
4
16
TxD4
TxD4+
Data4+
7
RxD2
TxD2-
Data2-
17
RxD4
TxD4-
Data4-
8
RTS2
RxD2+
–
18
RTS4
RxD4+
–
9
CTS2
RxD2-
–
19
CTS4
RxD4-
–
10
GND
GND
GND
20
GND
GND
GND
Setting Up Termination Resistors
When setting up your RS-485 and RS-422 networks for long-distance communication, you should use
termination resistors to prevent signal reflections. The following figures illustrate how to properly configure
termination for a 2-wire RS-485 network, and an RS-422 network.
The 45ML-5401 Series comes with 10 kilo-ohm pull-high/low resistors built in. You will usually only need to
install termination resistors (typically 120 Ω) on the first and last devices on your network.