Moxa Technologies ICF-1280I Series Hardware Installation Manual Download Page 10

 

- 10 - 

Troubleshooting LED Indicators and Fiber Diagnosis 

LED 

Status 

Description   

Status/Troubleshooting   

Ready    Flashing 

green 

Fiber diagnosis 
finished 

Check Fault LED;   
At least one converter is in Fiber 
Diagnosis mode; 
Check PROFIBUS master settings; 
Tx and Rx cables crossed 

Flashing 
red 

Detecting 
baudrate 

No PROFIBUS node; 
No PROFIBUS signal received; 
Tx and RX crossed over; 
Baudrate setting is incorrect. 

Flashing 
green/red 

Slot time setting 
error 

Recalculate the slot time; Set 
TSDR 

≥ 11;

 

Set HAS = greatest PROFIBUS 
node a 1; 
Check consistency of operation 
mode for DIP switch 6/7; 
Check consistency of Fiber Link 
Monitor Mode for DIP switch 5 

Fault 

Flashing 
red 

Fiber 
abnormality 
occurred in 
another segment 

Use Fiber Diagnosis on another 
converter that is not adjacent to 
this converter 

Solid red  Fiber 

abnormality 
occurred on this 
converter   

Check P1 and P2 LEDs 

P1/P2 

Flashing 
red 

Rx fiber cable 
abnormality 

Check the Rx fiber cable 
connecting to this port*; 
Tx and Rx cables crossed over; 
Partner module is powered OFF or 
defective 

Solid red  Tx fiber cable 

abnormality 

Check the fiber cable linking to Tx 
of this port* 

P3 

OFF 

PROFIBUS is idle  Check the PROFIBUS device 

connection 

Flashing 
red 

PROFIBUS side 
error 

RS-485 cable is not terminated or 
only terminated at one end; 
Open bus cable; 
PROFIBUS D+ and D- crossed 
over; 
Short circuit on PROFIBUS cable; 
RS-485 driver is defective; 
Check slot time setting, baudrate, 
and operation mode 

If the abnormality indicated by the LED disappears in Fiber Diagnosis 
mode, check the consistency of the DIP switch settings on all the 
converters. 
 
If the Tx and Rx cables are both abnormal, the P1/P2 LED will shine red. 
Check the Rx cable first for troubleshooting. 
 
*If the Fault LED, P1 LED, and P2 LED are all lit/flashing red 
simultaneously, the Tx and Rx cables of P1 and P2 may be crossed over. 

Summary of Contents for ICF-1280I Series

Page 1: ...2013 Moxa Inc All rights reserved P N 1802012800011 Moxa ICF 1280I Series Industrial PROFIBUS to Fiber Converter Hardware Installation Guide First Edition August 2013...

Page 2: ...ence and radio frequency interference It provides a clean communication path and is immune to cross talk Insulation Optical fiber is an insulator interface the glass fiber eliminates the need for usin...

Page 3: ...Protection feature protects against accidentally connecting the power cables to the wrong terminal The converter is designed to detect automatically which power wire is positive and which is negative...

Page 4: ...o this converter are working properly the Fault LED will flash red As a result you should run Remote Fiber Diagnosis on every other second converter in the topology to recursively troubleshoot the pro...

Page 5: ...F 1280I S models Up to 4 km with multi mode ICF 1280I M models Point to point linear bus star and redundant ring topologies Dual power input for redundancy Wide operating temperature from 40 to 75 C f...

Page 6: ...ack panel of the ICF 1280I converter when you take it out of the box If you need to reattach the DIN rail attachment plate to the ICF 1280I converter make sure the stiff metal spring is situated towar...

Page 7: ...nterference that may cause undesired operation Slot Time Settings Although ICF 1280I series converters can be connected in different topologies with a large number of units the total cable length and...

Page 8: ...40 28 6000 951 120 24 3000 551 60 24 1500 351 30 24 500 251 10 24 187 5 171 3 75 24 93 75 171 1 875 24 45 45 851 0 909 24 19 2 171 0 384 24 9 6 171 0 192 24 Transmission Speed kbps SW1 SW2 SW3 SW4 Aut...

Page 9: ...nner transceiver IC defective PROFIBUS port Data communication error Insufficient shielding of the bus cable Echo package timeout Open Solid red Echo package timeout PROFIBUS UART character error Open...

Page 10: ...ity occurred on this converter Check P1 and P2 LEDs P1 P2 Flashing red Rx fiber cable abnormality Check the Rx fiber cable connecting to this port Tx and Rx cables crossed over Partner module is power...

Page 11: ...Cable Single mode Multi mode 8 3 125 8 7 125 9 125 or 10 125 m 50 125 62 5 125 or 100 140 m Wavelength ICF 1280I S 1310 nm ICF 1280I M 820 nm Tx Output ICF 1280I S 7 dBm ICF 1280I M 14 dBm Rx Sensitiv...

Page 12: ...latory Approvals Safety UL 508 EN 60950 1 EMC CE FCC Part 15 sub part B Class A EMI EN 55022 Class A EN 55024 EMS EN 61000 4 2 ESD Level 2 EN 61000 4 3 RS Level 3 EN 61000 4 4 EFT Level 4 EN 61000 4 5...

Reviews: