background image

 

 

 7 

STEP 3

: Once the screws are fixed on the 

wall, insert the four screw heads through 
the large parts of the keyhole-shaped 
apertures, and then slide the EDS-408A 
downwards, as indicated. Tighten the four 
screws for added stability.

 

 

II 3G

 ATEX 

Information 

1.

 

Certificate number DEMKO 08 ATEX 0712961X 

2.

 

Ambient range (-40

°

 Tamb 

 75

°

C)  

3.

 

Certification string (Ex nC nL IIC T4)   

4.

 

Standards covered ( EN60079-0:2006, EN60079-15:2005)   

5.

 

The conditions of safe usage:   

y

 

These products must be mounted in an IP54 enclosure.   

y

 

Install in an area of pollution degree 2 or less. 

y

 

Use a conductor wire of size 0.2 mm² or greater. 

y

 

PROVISIONS SHALL BE MADE, EXTERNAL TO THE 
APPARATUS, TO PREVENT THE RATED VOLTAGE BEING 
EXCEEDED BY THE TRANSIENTS DISTURBANCES OF MORE 
THAN 40 % 

Wiring Requirements 

 

WARNING 

Safety First!

 

Be sure to disconnect the power cord before installing and/or 
wiring your Moxa EtherDevice Switch. 

Calculate the maximum possible current in each power wire and 
common wire. Observe all electrical codes dictating the 
maximum current allowable for each wire size. 

If the current goes above the maximum ratings, the wiring could 
overheat, causing serious damage to your equipment.

 

 

Be sure to read and follow these important guidelines: 

y

 

Use separate paths to route wiring for power and devices. If power wiring 
and device wiring paths must cross, make sure the wires are perpendicular 
at the intersection point. 
NOTE: Do not run signal or communications wiring and power wiring 
through the same wire conduit. To avoid interference, wires with different 
signal characteristics should be routed separately. 

y

 

Use the type of signal transmitted through a wire to determine which wires 
should be kept separate. The rule of thumb is that wiring that shares similar 
electrical characteristics can be bundled together. 

y

 

Keep input wiring and output wiring separate. 

y

 

It is strongly advised that you label wiring to all devices in the system, 
when necessary. 

Summary of Contents for EDS-408A

Page 1: ...ware Installation Guide First Edition November 2008 2008 Moxa Inc All rights reserved Reproduction without permission is prohibited Fl 4 No 135 Lane 235 Pao Chiao Rd Shing Tien City Taipei Taiwan R O C TEL 886 2 8919 1230 P N 1802004000020 ...

Page 2: ...al Networking Capability y Redundant Self Healing Ethernet Ring Capability y Port Based VLAN to ease network planning y QoS IEEE802 1p and TOS DiffServ to increase determinism y SNMP V1 V2c V3 and RMON for high security network management Designed for Industrial Applications y Bandwidth management to prevent unpredictable network status y Port mirroring for online debugging y Automatic warning by ...

Page 3: ... 1 Rear Panel View 2 17 16 16 4 3 2 1 1 Grounding screw 2 Terminal block for power input PWR1 PWR2 and relay output 3 Heat dissipation orifices 4 Console port 5 DIP switches 6 Power input PWR1 LED 7 Power input PWR2 LED 8 Fault LED 9 Master LED 10 Coupler LED 11 Turbo Ring logo 12 TP port s 100 Mbps LED 13 TP port s 10 Mbps LED 14 Model Name 15 10 100BaseT X ports 16 Screw hole for wall mounting k...

Page 4: ...iew 2 19 18 18 4 3 2 1 NOTE The appearance of EDS 408A SS SC is identical to that of EDS 408A MM SC 1 Grounding screw 2 Terminal block for power input PWR1 PWR2 and relay output 3 Heat dissipation orifices 4 Console port 5 DIP switches 6 Power input PWR1 LED 7 Power input PWR2 LED 8 Fault LED 9 Master LED 10 Coupler LED 11 Turbo Ring logo 12 TP port s 100 Mbps LED 13 TP port s 10 Mbps LED 14 Model...

Page 5: ...2S SC and EDS 408A 2M1S SC are identical to that of EDS 408A 3M SC 1 Grounding screw 2 Terminal block for power input PWR1 PWR2 and relay output 3 Console port 4 DIP switches 5 Heat dissipation orifices 6 Power input PWR1 LED 7 Power input PWR2 LED 8 Fault LED 9 Master LED 10 Coupler LED 11 10 100BaseT X ports 12 TP port s 100 Mbps LED 13 TP port s 10 Mbps LED 14 100BaseFX ports 15 1 FX port s 100...

Page 6: ...nt View Wall Mounting Kit DlN Rail Kit DlN Rail Kit DlN Rail 105 00 113 8 10 10 5 7 75 30 50 7 75 9 00 32 30 35 00 134 9 30 00 135 00 25 29 13 18 13 27 20 48 30 23 56 46 61 39 54 135 00 13 10 15 10 25 40 3 5 6 6 66 80 57 05 13 9 18 2 13 9 45 8 52 9 105 28 ...

Page 7: ...ll as shown in the following figures STEP 1 Remove the aluminum DIN Rail attachment plate from the EDS 408A s rear panel and then attach the wall mount plates with M3 screws as shown in the diagram at the right top plate bottom plate STEP 2 Mounting the EDS 408A on the wall requires 4 screws Use the switch with wall mount plates attached as a guide to mark the correct locations of the 4 screws The...

Page 8: ... Moxa EtherDevice Switch Calculate the maximum possible current in each power wire and common wire Observe all electrical codes dictating the maximum current allowable for each wire size If the current goes above the maximum ratings the wiring could overheat causing serious damage to your equipment Be sure to read and follow these important guidelines y Use separate paths to route wiring for power...

Page 9: ... detect both power faults and port faults The two wires attached to the fault contacts form an open circuit when 1 A relay warning event is triggered OR 2 The EDS 408A is the Master of this Turbo Ring and the Turbo Ring is broken OR 3 Start up failure If none of these three conditions is satisfied the fault circuit will remain closed Wiring the Redundant Power Inputs The top two contacts and the b...

Page 10: ... MDI X HUB Switch type ports and also show cable wiring diagrams for straight through and cross over Ethernet cables MDI Port Pinouts MDI X Port Pinouts 8 pin RJ45 Pin Signal Pin Signal 1 Tx 1 Rx 2 Tx 2 Rx 3 Rx 3 Tx 6 Rx 6 Tx RJ45 8 pin to RJ45 8 pin Straight Through Cable Wiring Straight Through Cable RJ45 Plug Pin 1 Switch Port RJ45 Connector RJ45 Connector Tx Tx Rx Rx NIC Port Cable Wiring 3 3 ...

Page 11: ... to B2 SC Port Pinouts SC Port to SC Port Cable Wiring Tx Rx A A B B Cable Wiring A A B B ST Port Pinouts ST Port to ST Port Cable Wiring Tx Rx A A B Cable Wiring A A B B B ATTENTION This is a Class 1 Laser LED product To avoid causing serious damage to your eyes do not stare directly into the Laser Beam Redundant Power Inputs Both power inputs can be connected simultaneously to live DC power sour...

Page 12: ...tting There are 4 Hardware DIP Switches for Turbo Ring on the top panel of EDS 408A that can help setup the Turbo Ring easily within seconds If you do not want to use a hardware DIP switch to setup the Turbo Ring you can use a web browser telnet or console to disable this function NOTE Please refer to the Turbo Ring DIP Switch section and Using Communication Redundancy section in User s Manual for...

Page 13: ...witches will auto negotiate to determine which one will be the Ring Master NOTE To switch on the Master or Coupler functions of the DIP switch you have to enable the Turbo Ring Pole first LED Indicators There are several LEDs on the EDS s front panel The function of each LED is described in the following table LED Color State Description On Power is being supplied to power input PWR1 PWR1 AMBER Of...

Page 14: ...net cable being used for the connection This means that you can use either a straight through cable or cross over cable to connect the EDS 408A to Ethernet devices Fiber Ports The EDS 408A s fiber switched ports operate at a fixed 100 Mbps speed and full duplex mode to provide excellent performance The fiber ports are factory built as either multi mode or single mode SC ST connectors Therefore you...

Page 15: ...STER and COUPLER Relay Contact One relay output with current carrying capacity of 1A 24 VDC DIP Switches Master Coupler Turbo Ring Reserve Optical Fiber Multi mode Single mode Single mode 80 km Wavelength 1300 nm 1310 nm 1550 nm Max Tx 10 dBm 0 dBm 0 dBm Min Tx 20 dBm 5 dBm 5 dBm Rx Sensitivity 32 dBm 34 dBm 34 dBm Link Budget 12 dB 29 dB 29 dB Typical Distance 5 km a 4 km b 40 km c 80 km d Satura...

Page 16: ...nd D ATEX Class I Zone 2 Ex nC nL IIC T4 EDS 408A 3M 3S 2M1S 1M2S pending Maritime DNV EDS 408A 3M 3S 2M1S 1M2S pending GL EDS 408A 3M 3S 2M1S 1M2S pending EMI FCC Part 15 CISPR EN55022 class A EMS EN61000 4 2 ESD Level 3 EN61000 4 3 RS Level 3 EN61000 4 4 EFT Level 3 EN61000 4 5 Surge Level 3 EN61000 4 6 CS Level 3 Shock IEC60068 2 27 Freefall IEC60068 2 32 Vibration IEC60068 2 6 WARRANTY 5 years...