Installation 

1.

 

To prevent the unit from overheating, always allow sufficient 
clearance around the unit for proper ventilation: 5 mm left and right, 
40 mm above, and 20 mm below. You should also keep a 10 to 15 cm 
clearance from adjacent devices that act as a heat source. 

2.

 

The appropriate mounting orientation is vertical, with input terminals 
on the bottom and output on the top of the DRP-240. Other mounting 
orientations, such as upside down, horizontal, or table-top, are not 
allowed. 

 

3.

 

Use copper wire only; the recommended wiring is shown below. 
AWG 

18 

16 

14 

12 

10 

Rated Current 
(Amps) 

6-10 

13-16 

16-25 

25-32 

Lead cross-section 
(mm

2

0.75 

1.00 

1.5 

2.5 

Note:   
When 5 or more wires are connected to the unit, the current carried 
by each wire could be 20% less than the current listed above. 
Make sure that all strands of each wire are properly inserted into the 
terminal connection, and that the screw terminals are securely fixed 
to prevent poor contact. If the power supply has multiple output 
terminals, make sure each contact is connected to wires to prevent 
stress on a single contact from too much current. 

4.

 

Use wire that can withstand temperatures of at least 80°C, such as 
UL1007. 

5.

 

Suggested fuses and the maximum number of the PSUs that can be 
connected to a circuit breaker at 230 V are shown as below: 

Model 

Fuse 

Circuit breakers 

C16 

D16 

DRP-240 

F5A/L250W 

6.

 

The recommended wire strapping length is 5 mm (0.197 inch). 