TECHNICAL SPECIFICATIONS
ITEM/FEATURES
OFFICE PRO 60
Rating Conditions
dry bulb
95º F (35º C)
wet bulb
83º F (28.2º C)
humidity
60%
Specifications
power frequency
60Hz
line voltage
single phase 208/230V
power consumption
7.1 Kw
current consumption
33 Amps
power factor
99%
starting current
140A
power wiring
6 (3-core) AWG
Cooling Unit
cooling capability
15,100 Kcal/hr
60,000 BTU/hr
cooling system
direct expansion
Blower
type of fan
centrifugal fan
air volume:
evaporator (high speed)
1940 ft
3
/min (3296 m
3
/h)
evaporator (low speed)
1770 ft
3
/min (3007 m
3
/h)
condenser (high speed)
2830 ft
3
/min (4808 m
3
/h)
evaporator (low speed)
2650 ft
3
/min (4502 m
3
/h)
motor output:
evaporator (high)
0.60 Kw
condenser (high)
1.12 Kw
Compressor
type
hermetic scroll
output
4.7 Kw
refrigerant type
R-22
refrigerant capacity
6.83 lbs (3.1 kg)
Safety Devices
compressor overload protector
included
fan motor protector
included
anti-freezing thermistor
included
full drain tank switch
included
automatic restart (power interruption)
included
compressor time delay program
included
Dimensions & Weight
W x D x H (in)
30" x 55" x 64.4"
W x D x H (mm)
760 x 1398 x 1635
weight (lbs/kg)
625/283
Operating Conditions
inlet air (relative humidity)
106º F (41º C), 60%
65º F (18.3º C), 50%
Control Device
temperature control
included
programmable timer
included
two speed fan
included
20
Summary of Contents for Office Pro 60
Page 3: ...OPERATION MANUAL OFFICE PRO 60 ...
Page 4: ...ii ...
Page 6: ...iv ...
Page 27: ...MANUAL DE UTILIZACIÓN OFFICE PRO 60 ...
Page 28: ...xxii ...
Page 30: ...xxiv ...
Page 51: ...MODE D EMPLOI OFFICE PRO 60 Des Solutions Innovantes avec l Air Conditionné Portable ...
Page 52: ...xlvi ...
Page 54: ...xlviii ...