Motrona GV210 Operating Instructions Manual Download Page 11

GV21002d_e.doc / Sep-13

Page 11 / 11

6. Technical Specifications

Power supply Vin

:

12 - 30 Vdc

Power consumption

:

50 mA (no-load operation)

Aux. encoder supply output

:

5.2 volts and Vin – 2 volts, 2x 125 mA
(short-circuit-proof)

Max. frequency

:

1 MHz (RS422 or TTL differential)

250 kHz (HTL and TTL single-ended)

Inputs

:

Single-ended A, B, Z (2x) or

differential A, /A, B, /B, Z, /Z (2x), 2 – 30 volts

Outputs

:

Push-pull A, /A, B, /B, Z, /Z (2x)

Level 5 volts (50 mA) – 30 volts (30 mA)

short-circuit-proof

Signal propagation delay

:

approx. 600 nsec.

Temperature range *)

:

Operation:

-20° - +60°C (-04° - +140°F)

Storage:

-30° - +75°C (-22° - +167°F)

Weight

:

ca. 100 g

Conformity and standards

:

EMC 2004/108/EC: EN 61000-6-2

EN 61000-6-3

*) Humidity non-condensing

Summary of Contents for GV210

Page 1: ...Z A A B B Z Z Universal encoder interface applicable as level converter encoder splitter and encoder cross switch Two encoder inputs A B Z and A B Z adjustable to either TTL RS422 level or to HTL 10...

Page 2: ...he operating staff it is indispensable to meet effective precautions in order to avoid such consequences Regarding installation wiring environmental conditions screening of cables and earthing you mus...

Page 3: ...verter 4 1 2 Encoder splitter dual output 4 1 3 Encoder signal switcher 5 2 Connection Diagram 6 2 1 Power supply 6 2 2 Control inputs 6 2 3 Encoder inputs 6 2 4 Asymmetric TTL Inputs 7 2 5 Outputs 7...

Page 4: ...ontrol input 1 LOW or unconnected and Control input 2 HIGH the signal ways are as shown in the drawing above featuring two independent level converters 1 2 Encoder splitter dual output In1 Control 1 L...

Page 5: ...ntial format using A A B B Z Z channels or to asymmetric single ended format using A B Z channels only Acceptable input levels are RS422 TTL and HTL 10 30 volts The output standard can again be select...

Page 6: ...terminal on the front side terminal 1 terminal 2 GND The current consumption is about 50 mA aux voltages and outputs unloaded 2 2 Control inputs The control inputs are accessible via the 3 position te...

Page 7: ...d behind the front plate must be set This hidden switch becomes accessible by slightly lifting up the front foil at the lower end e g by means of a small screw driver Switch position 1 is responsible...

Page 8: ...the basic function of the unit Yellow LED off Control1 and Control2 are either both LOW or both HIGH at the same time In this case the unit operates as a splitter both outputs are connected to the sa...

Page 9: ...A B B Z Z Both input and inverted input must be used Levels from 2 to 30 volts are acceptable 1 Z 1 B 1 A Input 2 single ended A B Z with HTL level Inverted inputs remain open level must be HTL 10 30...

Page 10: ...GV21002d_e doc Sep 13 Page 10 11 5 Dimensions 102 4 016 91 3 583 82 5 3 248 102 4 016 22 5 0 886 ON Side view Top view Front view...

Page 11: ...422 or TTL differential 250 kHz HTL and TTL single ended Inputs Single ended A B Z 2x or differential A A B B Z Z 2x 2 30 volts Outputs Push pull A A B B Z Z 2x Level 5 volts 50 mA 30 volts 30 mA shor...

Reviews: