Fs340_02b_oi_e.docx / Nov-21
Page 28 / 49
Definitions of the Master Encoder
F03
Range
Default
F03.026 Encoder properties
0 … 3
1
0= Differential Impulses A, /A, B, /B (2 x 90°) incl. inv.
1= Single-ended Impulses A, B (2 x 90°) without inv.
F03.027 Edge counting
0 … 2
0
0= Simple edge evaluation (x1)
1= Double edge evaluation (x2)
2= Full quadrature edge evaluation (x4)
F03.028 Counting direction
0 … 1
0
0= Up when A leads B
1= Down when A leads B
F03.029 Speed Display Factor
Multiplication factor to calculate the speed display value
from the master frequency (see chapter
1 … 999999
1
F03.030 Speed Display Divider
Divider to calculate the speed display value from the master
frequency (see chapter
1 … 999999
1
F03.031 Speed Display Dec.Point
Position of decimal point for the speed display value (see
chapter
0 … 5
0