VMX-synergy™ - Profibus DP Interface Quick Start Guide
1 |
P a g e
Caution
This option module is specifically designed to be used with
the VMX-synergy
TM
range of soft-start products and is
intended for professional incorporation into complete
equipment or systems. If installed incorrectly it may present a
safety hazard. Before commencing installation and
commissioning, the user should ensure they are fully familiar
with the VMX-synergy
TM
unit, and in particular have read the
important safety information and warnings contained in the
VMX-synergy
TM
User Guide.
Overview
The Profibus DP Interface is intended to be installed in the
VMX-synergy
TM
option slot, and allows the VMX-synergy
TM
to
be connected to a Profibus DP network. The interface offers
the following functionality:-
Installation
Ensure all power is removed from the VMX-
synergy
TM
unit prior to installing the option module
Remove the blanking plate from the option module
slot
Carefully slide the option module into the slot,
ensuring that the location tabs are correctly aligned.
DO NOT USE EXCESSIVE FORCE
Tighten the two screws on the option module to
secure
VMX-synergy configuration
VMX-synergy
TM
will automatically configure when the option
module is installed. Correct installation can be confirmed
from the touch screen interface:
Device >> Networks >> Profibus
Front panel
Item
1
Operation mode
2
Status
3
Profibus network
connector
Operation mode
State
Indication
Off
No power or not inserted
Green
Online data exchange
Green, flashing
Network OK, no data exchange
Single Red flash
Parameter error
Double Red flash
Network error
Status
State
Indication
Off
No power
Green
Initialised
Green, flashing
Initialised, Self testing
Red
Error
Profibus DP Connector Pinout
Pin
Function
1
N/C
2
N/C
3
B line Positive RxD/TxD,
RS485
4
RTS
5
Bus Ground (GND)
6
+5V Bus output termination power
7
N/C
8
A Line negative RxD/TxD, RS485
9
N/C