22
Manual # 42-02-U001, Rev C1
UPS Output Adjust for TAPS 6kVA Units Only
• TAPS 6kVA-480 VAC: UPS is correct at factory default setting (220VAC). No UPS output
voltage adjustment is required.
• TAPS 6kVA-240 VAC: The UPS output is set to 220VAC at the factory. If the line voltage
for your elevator controller is 208 or 240 VAC, you must set the UPS output voltage to
match the controller line voltage.
Check Setting
First, with TAPS and the UPS powered on:
1. Press the Function button. The LCD
will display:
Note
If no button is pressed within 4 to 8 seconds,
the LCD will return to the original display.
2. Press the Down Arrow repeatedly until
the Output Voltage screen appears.
3. If output is set correctly (208 or 240VAC according to line voltage), skip to Set Param-
eters on
. If not, proceed with 6kVA UPS Output Setting.
Note
Press the Function button to exit the display screens or, if no button is pressed within 4 to 8 sec-
onds, the LCD will return to the original display automatically.
6kVA UPS Output Setting
1. Press and hold the OFF button until you hear a click and the LCD displays:
2. Press the ON and Down Arrow buttons simultaneously for about 3 seconds. The UPS
buzzer will sound twice and the unit will start in settings mode, displaying buzzer status:
3. Press the Down Arrow button repeatedly until the UPS output voltage is displayed.
4. Press the Up Arrow button repeatedly until the correct voltage is displayed.
Summary of Contents for TAPS
Page 6: ...2 Manual 42 02 D001 Rev A 1 September 2003...
Page 15: ...Installation 9 Manual 42 02 U001 Rev C1 Figure 5 6kVA UPS Enclosure Base Assembly...
Page 16: ...10 Manual 42 02 U001 Rev C1 Figure 6 6kVA UPS Enclosure Assembly...
Page 40: ...34 Manual 42 02 U001 Rev C1 6kVA Units The 6kVA unit uses an LCD as well as LEDs...
Page 42: ...36 Manual 42 02 U001 Rev C1 6 12 12...
Page 43: ...TAPS Drawings 37 Manual 42 02 U001 Rev C1...
Page 44: ...38 Manual 42 02 U001 Rev C1...