For technical assistance call 866-357-8832
MA50777-MNL_revP1
Section A: Installation Instructions
!
DANGER:
This controller must be adjusted to ANSI/BHMA A156.10 and
A156.19 standards by a qualified person. Unsafe operation
may result if standards are not met.
!
DANGER:
Never attempt uses which are not covered in this manual.
Serious injury or death may result.
!
WARNING:
Controller may already be set to High Energy if requested at
time of order, or if the cover seal is broken. See item 8 for
details.
1.
Ensure dedicated power (120VAC, 50/60HZ, 10A).
2.
Ensure power is not shared with other equipment.
3.
Main power into the header must be de-energized before making connections.
4.
Incoming power wires should be connected per local codes and then connected to the power
harness inside the header (see
“Wiring Diagram”
on last page).
a. Black – Line (Hot)
b. White – Neutral
c. Green – Ground (earth ground)
!
WARNING:
Supply earth ground should be connected to the green
ground screw inside the operator header. Severe injury or
death may result if ground wire is not properly connected.
5.
Install required equipment into the door opening (safety sensors, activation sensors,
beams, switches, electric lock etc.).
!
DANGER:
Connections are safety critical. Ensure wires are fastened
securely in terminal blocks.
6.
Strip 3/8” off of wire ends and make connections to controller ensuring proper wire
engagement. Do not connect the power harness at this time. Make all terminal block
connections. Reference the attached table
“
Wiring Inputs at Terminal Block
”
for
description of terminal usage and the attached
“
Wiring Diagram”
for wire routing.
Depress tab completely
before inserting wire
Terminal block
Insert wire here &
pull lightly to check
engagement