MORLEY-IAS MI-LZR Installation And Maintenance Instructions Download Page 2

M200-01-00 

I56-2155-003R

CAUTION

Dust covers provide limited protection against airborne dust 
particles  during  shipping.  Dust  covers  must  be  removed 
before the sensors can sense smoke. Remove sensors prior 
to heavy remodeling or construction.

Testing

Before testing, notify the proper authorities that the system 
is undergoing maintenance, and will temporarily be out of 
service. Disable the system to prevent unwanted alarms.

All  sensors  must  be  tested  after  installation  and  periodi-
cally thereafter. Testing methods must satisfy the Authority 
Having Jurisdiction (AHJ). Sensors offer maximum perfor-
mance  when  tested  and  maintained  in  compliance  with 
EN54 and applicable local codes. 

The sensor can be tested in the following ways:
A. Functional: Magnet Test (P/N M02-04-01 or M02-09-00) 
  This sensor can be functionally tested with a test mag-

net.  The  test  magnet  electronically  simulates  smoke  in 
the sensing chamber, testing the sensor electronics and 
connections to the control panel.

  1. Hold the test magnet in the magnet test area as shown 

in Figure 3.

  2. The sensor should alarm the panel.
    Two LEDs on the sensor are controlled by the panel 

to indicate sensor status. Coded signals, transmitted 
from  the  panel,  can  cause  the  LEDs  to  blink,  latch 
on, or latch off. Refer to the control panel technical 
documentation  for  sensor  LED  status  operation  and 
expected delay to alarm.

C0100-00

3

2

1

3

2

1

+

+

OPTIONAL RETURN LOOP

REMOTE ANNUNCIATOR

+

B. Smoke  Entry:  Aerosol  Generator  (Gemini  501)                    

The  GEMINI  model  501  aerosol  generator  can  be  used 
for  smoke  entry  testing.  Set  the  generator  to  represent 
4%/ft. to 5%/ft. obstruction as described in the GEMINI 
501  manual.  Using  the  bowl  shaped  applicator,  apply 
aerosol until the panel alarms.

 
A  sensor  that  fails  any  of  these  tests  should  be  cleaned 
as  described  under 

CLEANING

,  and  retested.  If  the  

sensor fails after cleaning, it must be replaced and returned 
for repair.

When  testing  is  complete,  restore  the  system  to  nor-
mal  operation  and  notify  the  proper  authorities  that  the  
system is back in operation.

Figure 1. Wiring diagram:

M200-01-00 

I56-2155-003R

C0169-00

C0170-00

Cleaning

It  is  recommended  that  the  detector  be  removed  from 
its  mounting  base  to  facilitate  cleaning.  The  detector  is 
cleaned as follows:

NOTE:

  Before  removing  the  detector,  notify  the  proper 

authorities  that  the  smoke  detector  system  is 
undergoing  maintenance  and  will  be  temporarily 
out of service. Disable the zone or system undergo-
ing maintenance to prevent unwanted alarms.

1.  Remove  the  detector  cover  by  prying  away  the  four 

side  tabs  with  a  small-bladed  screwdriver,  and  then 
pulling the cover from the base.

2.  Vacuum  the  screen  carefully  without  removing  it.  If 

further cleaning is required continue with Step 3, oth-
erwise skip to Step 7.

3.  Remove the screen/chamber cover assembly by pull-

ing it straight out (see Figure 4).

4.  Clean the chamber by vacuuming or blowing out dust 

and particles.

5.  Replace the sensing chamber cover, aligning the arrow 

on the top with arrow on the printed circuit board.

6.  To  replace  the  screen,  place  it  over  the  chamber 

assembly, turning it until it snaps into place.

7.  Replace  the  cover  using  the  LEDs  to  align  the  cover 

and then gently pushing it until it locks into place. 

8.  Reinstall the detector.
9.  Test the detector as described in TESTING.
10.  Reconnect disabled circuits.
11.  Notify the proper authorities that the system is back 

on line.

C0146-00

Figure 2. Rotary decade address switches:

Figure 3. Test magnet position:

tenS

oneS

9

8

7

6

5

4

3

2

1 0

9

8

7

6

5

4

3

2

1 0

D

N

T

N

I

A P

T

O

O

LED STATUS

INDICATORS

TES

T

MAGNET

PAINTED

SURFACE

PAINTED

SURFACE

TEST

MAGNET

MAGNET TEST

MARKER

Figure 4. Sensor assembly:

CAUTION

Do not loop wire under terminal 1 or 2. Break 
wire run to provide supervision of connection.

SenSInG

cHaMBer

Screen

aSSeMBlY

SenSor

coVer

coVer reMoVal

taBS

control

 p

anel

www.acornfiresecurity.com

www.acornfiresecurity.com