15

FDY

PC-Programmable Frequency

Transmitter and Display

Figure 11.

  Custom Curve Parameters Tab

Programming the Custom Curve 
Parameters

The 

Custom Curve 

section of the confi guration 

software allows you to setup your own custom curve 
table with up to 128 points. In effect, this allows you 
to tell the transmitter what it should output when it 
receives a certain input.  Use the 

Custom Curve 

tab for 

customizing the display’s engineering units, reversing 
the output, signal limiting and creating custom curves.

Follow these directions to setup your custom curve 
table:

1. Check the 

Enabled

 box in the 

Custom Curve

 

section. Click the 

Set

 button and wait for the 

transmitter to fi nish downloading the information.

2. Input the 

Lower Range

 and the 

Upper Range

 

into the appropriate boxes. The point you enter in 
the 

Lower Range

 will become the zero point of the 

transmitter, and the transmitter will send out a 4mA 
signal (or the selected output signal, if the zero output 
is set at a value other than 4mA) when this point is 
reached. Likewise, the point you enter into the 

Upper 

Range

 will cause the transmitter to output 20mA (or full 

output signal, if different) when that point is reached.

3. Enter the desired engineering unit into the 

Display EGU label

 box. This will control what type of 

engineering unit (up to 5 alphanumeric characters, 
excluding symbols) is displayed by the Confi guration 
Software and on the FDY’s display.

4. Click 

Set

 to download all of the information to the 

transmitter.

NOTE:

“Read” will upload the information from the transmitter 

to the confi guration program. This can be used to 

take the last table that you have downloaded to the 

transmitter and enter it into the PC Confi guration 

Software.

5. Click 

Edit Table

 to begin creating your own custom 

curve table (see next page for instructions).

IMPORTANT:

Once you enable the custom curve, you must edit the 

table in order for your transmitter to work properly.

Summary of Contents for FDY

Page 1: ...FDY FDYNovember 2013 165 730 00E1 PC Programmable Frequency Transmitter and Display PC Programmable Frequency Transmitter and Display...

Page 2: ...ters 9 Programming the Input Parameters 9 Programming the Range Parameters 10 Programming the Output Parameters 11 Programming the Trimming Parameters 12 Sensor Trimming 12 Output Trimming 13 Loop Tes...

Page 3: ...eatures a large integral display that shows real time process status About this Manual Wherever you see a Note Caution or WARNING pay particular attention A Note provides information to help you in av...

Page 4: ...kohms typical 1kHz for input 6V for 0 02 30AC model 125kohms for 10 250AC model Load Capability 508 ohms 24V Output Current Limiting 3 8mA and 21 4mA for input under range and over range 3 6mA and 23...

Page 5: ...Hz Table 6 Period Input Parameters Resolution 1mV 1mV 1mV Range 0 01 1 5V 0 002 0 15V 0 002 0 15V Hysteresis Measured Period 40 sec to 50sec 40 sec to 2sec 40 sec to 2sec Input Range 100mV 30V DC Reso...

Page 6: ...3 25 in 62mm 2 45 in 64mm 2 50 in 66mm 2 58 in 76mm 3 00 in 43mm 1 70 in 18mm 0 70 in FDY COM PS 0 PS 0 6027 8 HZ Figure 2 FDY Dimensions 65mm 2 55 in GND GND 1 2 NPT 1 2 NPT 102mm 4 00 in 129mm 5 06...

Page 7: ...rrent configuration of the attached FDY 4 Measurement Mode The drop down menu selects which type of measurement the FDY will monitor 5 Variables Device Status Communications These sections display the...

Page 8: ...ion Program 1 2 3 4 5 6 7 Default Factory Configurations The following are the default factory settings for your unit Input Measurement Mode Frequency 0 100Hz Input Hysteresis 10mV Timeout Period 10s...

Page 9: ...ions Cable Communications Software Programming the FDY All operating parameters of the FDY are set using a PC a serial communication cable and Moore Industries Intelligent PC Configuration software Wh...

Page 10: ...ed to set this to the default setting of 2V maximum is 2 5V For input voltages below 3V it is recommended to set this to 2 3 of the peak to peak p p input signal voltage plus the low state signal volt...

Page 11: ...ed reading This can be used to compensate for bent blades in a monitored turbine by setting the value to equal the number of blades on the turbine i e if the turbine has four blades set the Averaging...

Page 12: ...ox This reduces the effect of sudden spikes and helps stop unnecessary alarms by smoothing the reading Failure Mode Failure Mode lets you set the output of the transmitter when it is malfunctioning It...

Page 13: ...attempt to trim the FDY ensure that the correct sensor is attached to the transmitter then go to the Trimming tab as shown at the left and 1 Select the User radio button under Trim Mode then answer Y...

Page 14: ...e output will no longer be fixed at 4mA 4 Continue by clicking the Fix Current High button This should cause the FDY to output 20mA If the output is a different value enter it into the Output Current...

Page 15: ...int of the transmitter and the transmitter will send out a 4mA signal or the selected output signal if the zero output is set at a value other than 4mA when this point is reached Likewise the point yo...

Page 16: ...onfiguration program you are ready to download the configuration file Downloading the Configuration File After the configuration has been set to your satisfaction it can be downloaded to the unit by s...

Page 17: ...signal wiring should be 2 inches Note Some of Moore Industries instruments can be classified as receivers IPT2 IPX2 etc and some can be classified as transmitters TRX TRY etc while some are both a rec...

Page 18: ...eas requiring intrinsically safe instrumentation Refer to the Special Conditions outlined below before proceeding with installation Special Conditions of Use The following instructions must be adhered...

Page 19: ...The Interface Solution Experts 19 FDY PC Programmable Frequency Transmitter and Display...

Page 20: ...isions of the Directive Fulfilled by the Equipment Group II Category 1G EEx ia IIC T4 Notified Body for EC Type Examination LCIE Notified Body Number 0081 33 av du G n ral Leclerc 92260 Fontenay aux R...

Page 21: ...EC Type Examination Certificate ISSeP 08 ATEX 033 X Technical Standards Used EN 60079 0 2006 Explosive atmospheres Part 0 Equipment General requirements EN 60079 1 2007 Explosive atmospheres Part 1 Eq...

Page 22: ...IES FOR BREACH OF ANYWARRANTY CONCERNINGTHE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE THE COMPANY SHALL IN NO EVE...

Reviews: