background image

HIM

18 

The Interface Solution Experts

Smart HART

 Loop 

Interface and Monitor

Alarms Tab

The Alarms tab controls the programmable alarm 
trip(s) option. This screen will be grayed out if the 
attached HIM is not equipped with at least one alarm 
trip.  To program the Alarm parameters, change the 
settings in the 

Alarm1 

and/or

 Alarm2 

 box, then press 

Quick Set

. The sections of the screen are described 

below.

 
 

Trip/Fault Alarms

Trip Alarm

 monitors a selected variable and trips 

either when the variable exceeds a set value (Trip 
High) or when the variable falls below a selected 
value (Trip Low).  The 

Source

 specifies which variable 

will be monitored, while the 

Trip Point

 sets the point 

at which the alarm will trip.  After the alarm trips, the 

Dead Band

 determines how far past the trip point the 

variable will have to go before the alarm condition 
returns to normal.  
 
There are two types of Fault Alarms. A 

HIM Fault 

Alarm

 monitors the health of the HART monitor. It will 

trip whenever the internal error status word is set. 
For example, if the HIM’s configuration file becomes 
corrupt, this alarm will trip and the monitor will display 
BAD_CONFIG.

  

Field Device Fault Alarm

 monitors 

the health of the HART transmitter. This fault alarm will 
trip for any of these eight malfunctions:

Device Malfunction (Bit 7)

Figure 11.

  Alarms Tab

Relay trips whenever it detects that a hardware error or 
failure has occurred in the connected HART device. 

Configuration Changed (Bit 6)

Relay trips whenever it detects that the connected 
HART device has had its configuration changed.

Cold Start (Bit 5)

Relay trips whenever the power to the HART device 
is interrupted.  It will also trip during a HART Master 
Reset or Self Test Command.

Additional Status (Bit 4)

Relay trips whenever the connected HART device 
reports a condition requiring HART Command #48, 
which is Read Additional Information.  This indicates 
that the instrument needs attention from a device with 
full HART command capability.

Output Current Fixed

 

(Bit 3)

Relay trips whenever the HIM detects that the 
connected HART device’s output is no longer 
responding to changes in its input, and is being held at 
a predefined level.

PV Analog Output Saturated (Bit 2)

 

Relay trips whenever it detects that both its analog 
and digital representations of the Primary Variable are 
outside rated operating limits, and no longer reflect the 
true sensor input.

Non-PV Out of Limits (Bit 1)

Relay trips whenever one of the HART ancillary 
variables (Secondary, Tertiary, or Quaternary), are 
operating outside the limits that can be effectively 
measured. 

PV Out of Limits (Bit 0)

Relay trips whenever the HART Primary Variable is 
operating outside the limits that can be effectively 
measured.

Delay & Fail Safe

By entering a value in the 

Delay

 box, you can specify 

how long (in seconds) the alarm condition needs 
to exist before the alarm trips.  

Failsafe

 alarms (box 

checked) de-energize when in alarm condition;  

Non-Failsafe

 alarms energize when tripped.

Summary of Contents for HIM

Page 1: ...D e m a n d M o o r e R e l i a b i l i t y All product names are registered trademarks of their respective companies User s Manual HIM No 224 778 00G November 2018 Smart HART Loop Interface and Moni...

Page 2: ...s Europe Australia 16650 Schoenborn Street North Hills California 91343 6196 U S A Tel 818 894 7111 Fax 818 891 2816 E mail info miinet com TOLL FREE 1 800 999 2900 www miinet com 1 Lloyds Court Manor...

Page 3: ...Inputs 5 Outputs 5 Options 5 TX Power Supply 5 HIM Dimensions 6 Specifications 7 Configuring the HIM 8 Terminal Designations 9 Installing the HIM 10 Installing the HIM into the Loop 10 Bench Checking...

Page 4: ...nting 30 Making the Electrical Connections 30 Recommended Ground Wiring Practices 30 CE Conformity 30 Power Sourcing Parameters for General Locations Intrinsically Safe and Non Incendive Type N Applic...

Page 5: ...es uses the model and serial numbers of our instruments to track information on each unit that we sell and service If a problem occurs with your HIM check for a tag affixed to the unit listing these n...

Page 6: ...Quaternary Variable Process Data and Instrument Diagnostic Information HIM HART Interface Module Breaks Out Data from Smart HART Instruments HART Primary Master Smart HART Multivariable Mass Flow Tra...

Page 7: ...nge Configurable from 1 to 247 Unit will assume a MODBUS address of 01 by default Baud Rate Interface supports the following 300 600 1200 4800 9600 19 2k MODBUS interface will support even odd and no...

Page 8: ...folder 2 Double click the installation program located in the folder Follow the prompts to correctly install the program Once the Configuration Program is installed on the PC the unit can be connecte...

Page 9: ...6 10 11 12 HART Input 2 MODBUS Outputs and 1 Analog Output MB1AO Dual Alarm 2PRG HIM 1 2 3 7 8 9 10 11 12 TX HIM 10 11 12 IN IN A MODBUS 2 1 2 3 4 5 6 10 11 12 HART Input 2 MODBUS Outputs MB No Alarm...

Page 10: ...Computer Moore Industries PC Configuration Software Communication Cable 250 ohms 0 01 Accurate to 0 009 of span e g HP Model 3487A 24Vdc 10 Microsoft Windows based PC 16Mb free RAM 20MB free disk spa...

Page 11: ...OM 0 ADDR COMMON NC normally closed NO normally open 4 20mA DCS Sensor Input NO NC 24Vdc Power Source R HART Multivariable Field Instrument Temperature Pressure Level and Flow Analog Output tied to An...

Page 12: ...ADY INPUT TRIP 2 TRIP 1 COM 0 ADDR COMMON NC normally closed NO normally open 4 20mA DCS Sensor Input NO NC DC GND 24Vdc Power Source DCC R must be 250 and 1100 Ohms R HART Multivariable Field Instrum...

Page 13: ...The Interface Solution Experts 13 HIM Smart HART Loop Interface and Monitor Figure 7 HIM Output Wiring with Active Output and Passive Output...

Page 14: ...device was configured HIM Tag A phrase used to identify a HIM Figure 8 HIM PC Configuration Software Screen HIM Device Status Displays how the HIM is functioning giving a brief summary of any errors...

Page 15: ...ing the HIM to function as the Primary HART Master in the application means that any other HART device in the loop must be configured either as a HART Secondary Master 1 per loop or as a HART Slave up...

Page 16: ...9 HART Slave Device Long Format Address Settings Screen To convert HEX to Decimal code perform the following steps Access the Calculator feature in Microsoft Windows by opening the Start menu Next sel...

Page 17: ...econd increments Directly below the Toggle checkbox are two list boxes to select the variables that you would like to be displayed Notice that if you select a scaled variable it is important to check...

Page 18: ...r failure has occurred in the connected HART device Configuration Changed Bit 6 Relay trips whenever it detects that the connected HART device has had its configuration changed Cold Start Bit 5 Relay...

Page 19: ...s information returned by certain HART instruments This provides flexibility to the requirement of alarming on additional status information Choosing this feature you are given the ability to spec ify...

Page 20: ...n Custom Curve The middle section of the screen displays the custom curve table After enabling custom curve mode and setting the variable to be monitored continue by selecting the number of points for...

Page 21: ...set the Source as SV Set the Input Range to 0 and 400 F and the Output Range to 4mA to 20mA Click Quick Set to download the new configuration file to the HIM Output Current Box The Output Current Box...

Page 22: ...til the analog output matches the minimum point 4mA for a 4 20mA output when you click the Fix Output at Low Point button After the low point is trimmed press the Fix Output at High Point button Read...

Page 23: ...to measure the level of a tank in either centimeters inches or PSI Since the tank is only 300 centimeters 10 feet high the full range of the primary variable PV output from the DP transmitter is 0 4 3...

Page 24: ...ast significant bits in the first register Selecting Swapped MSW most significant word will reverse the order storing the most signifi cant bits in the first register and the least significant bits in...

Page 25: ...erature Pressure Level Flow Multivariable HART Communicator can be connected anywhere on the loop COM IN TX IN MODBUS output with MODBUS option A B S RS485 RS232 Converter TO serial COM port of PC MOD...

Page 26: ...it 1 EEPROM fail Bit 2 EEPROM configuration checksum error Bit 3 EEPROM calibration checksum error Bit 4 EEPROM blank Bit 5 Out of range error Bit 6 Division by zero error Bit 7 Configuration data bad...

Page 27: ...te 1 Additional Status Byte 2 Additional Status Byte 3 Additional Status Byte 4 HART Primary variable float format HART Secondary variable float format HART Tertiary variable float format HART Quatern...

Page 28: ...aming error Overrun error Parity error No error Undefined Invalid selection Passed parameter too large Passed parameter too small Too few bytes received Device specific command error In write protect...

Page 29: ...nformation can be considered as valid Another example using Tables 4 and 5 the following value in MODBUS Register 13 0000 0000 0001 1001 binary or 19 hexadecimal or 25 decimal implies Primary variable...

Page 30: ...eceiver and a transmitter SPA 2 HIM etc Hence your shield ground connections should be appropriate for the type of signal line being shielded The shield should be grounded at the receiver and not at t...

Page 31: ...and not to Buyer s customers or the users of Buyer s products unless Buyer is an engineering contractor in which case the policy shall extend to Buyer s immediate customer only This policy shall not...

Reviews: