background image

CDL6325 Rev C  500-218  698

Industrial Controls Division

Moog Inc., East Aurora, NY 14052-0018
Telephone: 716/655-3000
Fax: 716/655-1803 
Toll Free: 1-800-272-MOOG

SNAP TRAC  EXAMPLE

Suggested Setup Procedure:

(Reference Moog Documents N121-132A and N123-134)

1.

Turn off hydraulic power and

relieve pressure.

2.

Set the GAIN pots (R4 and

R43) on the N121-132A card

approximately five turns from

full counter-clockwise.

3.

Set the SCALE pot (R9) on 

the N121-132A card full

clockwise.

4.

Apply electrical power.

5.

On the N121-132A card,

temporarily remove the

feedback connection from

terminals [2] and [6]. Adjust the

BIAS pot (R16) for zero coil

current at midstroke of the

command pot. Re-connect

terminal [2].

6.

Apply hydraulic pressure.

7.

Adjust the N123-134

Exciter/Demodulator card for

proper GAIN (R34) and PHASE

(R11) by monitoring the voltage

at terminal [12].

8.

Re-connect terminal [6] of the

N121-132A card.Turn the

SCALE pot (R9) full counter-

clockwise.

9.

Increase the GAIN pots (R4,

R43) clockwise until the system

exhibits the desired sensitivity.

Check the stability of the system

throughout the full load range.

10. Adjust the BIAS pot (R16) for

mid actuator position at zero

command signal, or as desired.

Modifications to the 

N121-132A card:

(Reference Moog Document N121-132A)

•  Set the jumpers for 

proportional control only.

• Insert R45=20K

.

MODEL

N

123-134

EXCITER-DEMODULA

T

OR

MODEL

N

121-132A

SER

VOCONTROLLER

Reviews: