5.5.2 I²t monitoring synchronous motor
A synchronous motor by design has lower loss than an asynchronous motor,
because permanent magnets replace the magnetizing current. It is normally not
internally cooled, but discharges its heat loss by internal convection. For that reason
a synchronous motor has a different characteristic to an asynchronous motor. It is
necessary to adapt the I
2
t characteristic because the factory setting mostly does not
exactly map the present motor.
Image 5.9: “I²T monitoring” screen for a synchronous motor
MOOG
ID No.: CB40859-001 Date: 11/2020
MSD Servo Drive - Device Help
43
5 Motor
If the I
2
t type is set to "THERM(1) = Thermal time constant dependent", all settings
apart from the thermal time constant are disabled.
If the integrator exceeds its limit value, the error E-09-01 is triggered. The current
value of the integrator is indicated in P 701[0] - Mon_ActValues.
NOTE
l
The limits are specified in Servo Drive as percentages of the rated
quantities (e.g. current, torque, speed,...) of the motor. The defaults
relate to 100 % of the rated quantities.
Calculation of capacity utilization via exponential function with thermal
time constant of motor:
Setting of I
2
t type:
l
P 735[0]
= “FREQ(0)=Output frequency-dependent": Moog-specific i(f)
evaluation
l
P 735[0]
= “THERM(1)=Thermal time constant-dependent”: Evaluation based
on thermal time constant i(Tth)
l
Thermal time constant
P 733[7] - Ttherm
in [s]
l
The shut-off threshold is 110% (reduction in current noise)