MSD Multi-Axis System Operation Manual DC-AC Servo Drive
5.4.2
Display
The following table defines various indications and items of status information p ovided
via the display.
Display
Meaning
Menu entries
("PA" in this case serves as an example, for further possible entries see
chapter 5.4.4 and chapter 5.4.5)
[Flashing decimal points]
Selected function in progress
[Two dashes]
Entry/function not available
[OK]
Action executed successfully, no errors
[Error]
• Action via control unit
not
executed successfully,
"Er" flashes alternately with the error number
(see chap. chapter 5.4.3)
• Device error indication,
"Er" flashes alternately with error number and error location (see "MSD Servo
Drive Device Help")
Numerical values
("10" in this case serves as an example)
• Data set and error numbers are shown in
decimal
on the Parameter menu
(PA).
• All other values are displayed in
hexadecimal
. In these cases the 10
displayed would represent the decimal value 16.
Table 5.6 Meaning of display
NOTE:
If no input is made via the keyboar
d for a period of 60 s, the display r
eturns to
the indication of the device status.
5.4.1
Function of buttons T1 and T2
These buttons are used to activate the different menus and to control the corresponding
functions.
Button
Function
Comment
T1 (left)
• Activate the menu (exit the device
status display)
• Scroll through the menus/sub-menus
• Set values - left segment display (D1)
The button T1 can be held pressed for any
length of time because the display will only
scroll through the menu commands available
at the corresponding level. No settings will
be changed.
T2 (right)
• Selection of chosen menu
• Set values - right segment display (D2)
The button T2 must
not
be held pressed
for any length of time because the display
will change from one menu level to the next
within the menu structure and then change
the parameter that is reached at the end. You
should therefore always release the button
T2 after each change in display.
T1 and T2
together
• Menu level up
• Accept selection
• Acknowledge
After pressing T1 and T2 at the same time,
the value applied flashes for five seconds.
During this time the save procedure can still
be aborted by pressing any button, without
applying the value set. Otherwise the new
value will be saved after five seconds.
General
• The time the button needs to be held
depressed until an action is executed, is
approx. 1 second.
• If there is no action by the user for a
period of 60 seconds, the display returns
to the indication of the device status.
Table 5.5 Function of buttons T1 and T2
moog
Id. no.: CA97554-001 0
5
/2017
5 Commissioning