background image

9 P-

I

 selection

For position closed loops, initially select only P (SW6:2). For 
pressure or velocity loops select 

I

 (SW6:4) initially and then P. 

See paragraph 12 below for more detail. For a complete 
discussion of P and 

I

 control, see the G122-202 servoamplifier 

Application Notes (part no C31015).

10  Integrator input

The servoamplifier has a unity gain input error amplifier 
followed by two parallel stages, one a proportional amplifier 
and the other an integrator. The outputs of these two stages 
can be switched to the output power amplifier (see paragraph 
7 above) which then drives the valve.

The input to the integrator stage can be switch selected 
(SW4:1) from either the output of the error amplifier, 

I

 in = E, 

or the output of the proportional stage, 

I

 in = P. The latter 

arrangement is used in the G122-202. It is beyond the scope 
of these Application Notes to detail the benefits of each 
arrangement. If you have experience with the G122-202, 

I

 in = P would seem to be an easy choice.

11  P only gain

For position loops select only P control (SW6:2). Input a step 
disturbance of 50% valve current with the step push button 
(SW3). Adjust the P gain for the required stability, while 
monitoring the front panel valve test point, or the feedback 
signal. The gain range of the proportional amplifier can be 
moved by changing the plug-in resistor R17. The value loaded 
when shipped is 100k Ohms, which gives a 1 to 20 range. 
Selecting 200k Ohms will give 2 to 40. The circuit will function 
correctly with the value of R17 between 100k Ohms and 
10M Ohms.

Note that as P gain is increased, the movement due to the step 
push button decreases.

12  P and 

I

 gains together

If you are inexperienced with integral control the following 
set-up method is a good starting point.

 

I

 in = E: Initially select only 

(SW6:4). Press the step push 

button (SW3). Increase 

I

 gain until one overshoot in the 

feedback signal is observed.

Next select P (SW6:2) and 

I

 (SW6:4) together and increase the 

P gain to reduce the overshoot.

For the 

I

 in = E arrangement the P and 

I

 sequence could be 

reversed. i.e.: adjust P first, followed by 

I

.

  

I

 in = P: For an 

I

 in = P arrangement, only the “P followed 

by 

I

” sequence of adjustment can be used.

For a more thorough discussion see G122-202 Application 
Notes (part no C31015).

13 

I

 limit

The contribution from the integrator to the output amplifier 
can be reduced by selecting 

I

 limit on (SW6:3). When this 

switch is on the integrator contribution is reduced to 
approximately 15% of the level when it is off. This feature is 
useful in a position loop that may require integral control to 
achieve the required steady state accuracy. The limited integral 
control removes valve null error when the final position is 
reached. It is also useful in a pressure loop to limit overshoot, 
if the valve drive saturates.

14 Dither

The dither frequency is fixed at 200Hz and the level is 
adjustable with the front panel pot to ±10% of valve drive, 
regardless of the type and level of valve drive selected. It can 
be turned on or off with ([SW1:3]). Dither is seldom needed in 
a position loop but can be beneficial in pressure or velocity 
loops. Increase dither until it can just be detected in the 
controlled variable, such as pressure or velocity. Dither can 
compromise valve life, so it should be kept to a minimum.

15 Enable

A relay on the circuit card needs to be energised to connect 
the output stage to its screw terminal and to un-clamp the 
integrator. The clamp prevents integrator wind-up when the 
loop is not operating. Supply 24V to the appropriate terminal 
to energise the relay. The enable switch ([SW1:2]) on the circuit 
card can be set to permanently energise the relay and provide 
a permanent enable.

16  In position

When the valve drive signal falls below ±10% of the selected 
full scale signal, the “in position” signal goes true and provides 
an opto-isolated current path between the + and – terminals. 
This can be connected to a PLC to initiate the next step in a 
control sequence. Do not apply more than 40V to the + 
terminal and ensure the load on the – terminal is less than 
20mA.

The “in position” signal is not relevant for a velocity loop.

17   Withdrawing the circuit card 

from its case

The circuit card needs to be withdrawn from its case to set the 
selector switches, change the plug-in resistors and operate the 
step push button.

To do this, push one cover release tab with a pen or 
screwdriver, while gently pulling on the top cover on that side. 
The cover will release approximately one mm. Repeat on the 
second tab on that side. Repeat on the other side and then 
withdraw the cover and circuit card until the required switches 
are exposed. The rigidity of the connecting wires will hold the 
circuit card in position while changes are made.

Page 4 of 6: C70861 Rev E – 07.14

Reviews: