7.15.2 Pressure control deviation monitoring
Figure 142: Pressure control deviation monitoring
Chapter "7.5.2 Object 0x63D0: Control deviation", page 169
7.15.2.1 Object 0x63D1: Type
The parameter <Type> (0x63D1) is used to activate or deactivate the standard pressure control deviation
monitoring function.
Value description
t
<PrsControlDeviation>
(0x63D0)
<Upper
Threshold
>
(0x63D4)
<Lower
Threshold
>
(0x63D5)
<DelayTime>
(0x63D2)
<StatusWord>
(0x6041)
Bit 11 = 1
<StatusWord>
(0x6041)
Bit 11 = 0
<UpperThreshold>
(0x63D4)
<StatusWord> (0x6041) Bit 11 (
Control deviation
)
<LowerThreshold>
(0x63D5)
<DelayTime>
(0x63D2)
Pressure
deviation
monitoring
<Type>
(0x63D1)
<PrsControlDeviation>
(0x63D0)
ValvePressureControl_ControlMonitoring
Index
Sub-index
Parameter name
Data type
Access
Persistence
Value range
Default
0x63D1
0
Type
INT8
rw
Y
0…1
0
<Type>
Description
0
Pressure control deviation monitoring off.
1
Pressure control deviation monitoring on.
Table 92: Possible values of parameter <Type> (0x63D1)