SP28-F2 Modular Series Fireplace

Installing The Gas Line

The gas line must be installed before finishing the fireplace. 

Natural Gas

requires a minimum inlet gas supply  pressure of 5.5" W.C. & a manifold
pressure of 3.5" W.C. 

Propane Gas

 requires a minimum inlet gas

supply pressure of 11" W.C. & a manifold pressure of 10" W.C.
Provision must also be made for a 1/8" N.P.T. plugged tapping and be
accessible for test gauge connection immediately upstream of the gas
supply controls to the appliance.  The fireplace gas connection and the
main operating gas valve is located behind the removable trim at the
bottom of the unit and need only be attached to the gas line  with an
approved fitting, as required by the 

applicable installation codes

.

Installation

B-Vent  Installation

The 

EP-28 Modular Series 

is certified for use with standard 5" B-Vent

and requires no B-Vent appliance connector. Simply attach the B-Vent to
the fireplace flue collar, and secure it to the L-shaped brackets on each
side of the opening using 1/4" sheet metal screws. Do not penetrate the
inner sleave of the B-Vent when tightening the screws.

Refer to the current 

CAN/CGA B-149.1

 and

 .2

 or 

ANSI Z223.1-1988

Gas Installation Code

 for specific vent sizing.

2

7

37 1/2

Gasline

Installing  The  Remote  Switch

The 

EP28 Series'

 gas valve, located behind the lower trim, may be

connected to a wall switch. The valve generates its own power.

 

This is a

millivolt circuit. Use only low voltage wire, and 

DO NOT

 connect any

external power to it.

Refer to Figure 24a, 24b, and 24c for wiring requirements.

Note:

  The switch location must not exceed 30' from the fireplace.

The appliance and its individual shutoff valve must be disconnected from
the gas supply piping system during any pressure testing of that system
at test pressures in excess of 1/2 psig (3.5 kPa).

The appliance must be isolated from the gas supply piping system by
closing its individual manual shutoff valve during any pressure testing of
the gas supply piping system at test pressures equal to or less than 1/2
psig (3.5 kPa).

Figure 4.  

Gas line access.

Test your B-Vent installation after completion to ensure that no
combustible by-products are spilling from the fireplace opening.
This draft test should be performed after a fifteen (15) minute warm
up period. The manufacturer will not be responsible for any
installations with inadequate draw.

CAUTION:

Notes:

n

After gas line is connected each appliance connection, valve
and valve train
 must be checked while under normal operating
pressure with either a liquid solution, or leak detection device, to
locate any source of leak. Tighten any areas where bubbling
appears or leak is detected  until bubbling stops completely or
leak is no longer detected. 

Do NOT 

use a flame of any kind to

test for leaks.

Summary of Contents for SP28-F2

Page 1: ...ne Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Warning Improper installation adjustment alteration serviceormaintenancecancause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier For Your Safety Do not store or use gasoline or other flammab...

Page 2: ...nsibilityfor thefollowingactions n Modificationofthefireplaceand orcomponentsincluding combustionairassemblyorglassdoors n Useofanycomponentpartnotmanufacturedorapprovedbythe manufacturerincombinationwithanEC Plusfireplacesystem n Installationotherthanasinstructedinthismanual ConsultyourlocalGasInspectionBranchoninstallationrequirementsfor factory builtgasfireplaces Installation repairsshouldbedon...

Page 3: ...Floor 0 Mantle 6 RecessDepth 15 Flue 1 Clearancefromthetopofthefireplacetoa combustibleceiling withinthefireplace enclosure Refer to page 5 See Figure 2 Framing Forprotectionagainstfreezingtemperatures itisrecommendedthat outer walls of the chase be insulated with a vapour barrier This will reducethepossibilityofacold airconvectioncurrentonthefireplace 37 1 2 15 1 2 36 When sheetrock is not used b...

Page 4: ...witch The EP28 Series gas valve located behind the lower trim may be connected to a wall switch The valve generates its own power This is a millivoltcircuit Useonlylowvoltagewire and DONOTconnectany externalpowertoit Refer to Figure 24a 24b and 24c for wiring requirements Note Theswitchlocationmustnotexceed30 fromthefireplace Theapplianceanditsindividualshutoffvalvemustbedisconnectedfrom thegassup...

Page 5: ...Mantels Surrounds NOTE Mantelclearancesshownareforfirehazardprevention Newtechnology tomeetconsumerandgovernmentdemandsforthe wiseuseofenergy haspromptedustomanufacturemanymodelsof fireplaceswhicharehot fuelandenergyefficient Pleasebeaware temperaturesoverthemantelwillriseabovenormal roomtemperatureandwallsabovefireplacemaybehottotouch Werecommendcarefulconsiderationbegiventotheeffectsofelevated m...

Page 6: ...an Liftcompleteburnerassembly upand outofunittoclearsupportledge 6 Install the new burner by reversing step 5 Be sure to re install the twoscrewsatthebottomrearofburnerpantosecurepanintoplace 7 Re installthefrontbar Makesurethefrontbarissecuredwithfour screws 8 Reconnectgaslinebyfollowingtheinformationonpage4 9 Turnongassupplyandleaktesttheconnection Notes n ASpillSwitchissuppledwitheachunit Thism...

Page 7: ...mation Installations in Canada which employ the fan kit must be in accordance with CSA C22 1 Canadian Electrical Code Part 1 and or LocalCodes Installations in the USA employ the fan kit must be in accordance withlocalcodesor intheabsenceoflocalcodes withtheNational ElectricalCode ANSI NFPA70 1987 EP28 F2Logset Thismodelaresuppliedwithfiveceramicfibrelogsandapackageof silicasand Unpackthelogsandha...

Page 8: ...doorssothattheyarestraightand tightenthescrewto holdthedoorinposition Adjustbothdoorsuntiltheopeningbetweenthe doors whenclosed isevenfromtoptobottom Figure 12 Adjusting the glass doors Spring Clip Top Door Rail Bottom Door Rail Inset Pivot Point Upgrading to the S2 Heating Insert 1 Remove the upper and lower trims Warning You must turn off gas supply to the fireplace 2 Removethedoorsandmeshfiresc...

Page 9: ...ouchesthebackwallofthe shell anddrivetwoscrewsthroughthepilotholesinthebracket Refertofigure17 Plugthefanintothefanspeedcontrolbox Figure 16 Cutting the front bar Figure 17 Installing the blower assembly 8 Installtheefficiencycollarasshowninfigure18 Usealong screwdriver to hold the collar out of the way while you install the HeatingInsert Figure 18 Installing the efficiency collar Installation Ins...

Page 10: ...e new front bar as shown in figure 21 Figure 21 Installing the new front bar 13 InstallthefillerplatesfirstandthenthehoodasshowninFigure22 Loosenthetwoadjustmentscrewsonthemountingbrackets Hook thebottomofthehoodofthetopedgeoftheInsertandslidethe mountingbracketsintotheholesoneachsideoftheshell Re tighten theadjustmentscrews 14 Remove the glass door as shown in Figure 23 Remove the plastic shippin...

Page 11: ...lier s instructions To Turn Off Gas To Appliance Operation Model EP28 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Replace trim 1 Turn off remote switch 2 Removelowertrim 1 STOP Read the safety information above on this label 2 Removelowertrim 3 Push in gas control knob and turn clockwise to OFF 4 Wait five 5 minutes to clear out any gas Smell for gas including near...

Page 12: ...edwhencleaningappliancewitha vacuum n Glass and logs can get very hot Handle only when cool Cleaning Whenthefireplaceisfirstactivated theremaybesomesmokinganda visiblefilmmaybeleftontheglassdoors Thisisanormalcondition and istheresultofburningtheprotectivecoatingsonnewmetal n Glassmustbecleanedperiodicallytoremoveanyfilm anormalbi productofcombustion whichmaybevisible Handlethedoor carefully andcl...

Page 13: ...e figure 24a b c notlight 2 Check wall switch for proper connection EP28 4 Pilot Burner Adjustment 1 Determinewhichpilotisinstalledinthefireplacebasedonfigures 25a and 25b 2 LocatePilotAdjustmentScrew Seefigures24a 24b and24c 3 Adjust pilot key to provide properly sized flame See figure 25a or 25b 4 Replacepilotadjustmentcap 5 Afterinstallingorservicing leaktestwithasoapsolutionwithmain burneron C...

Page 14: ...resandwillresultinafirehazard Limitations On Liability Limitations On Liability Limitations On Liability Limitations On Liability Limitations On Liability ItisexpresslyagreedandunderstoodthatTheCompaniessoleobligation andpurchaser sexclusiveremedyunderthisWarranty underanyotherwarranty expressed orimplied orincontract tortorotherwise shallbelimitedtoreplacement repair orrefund asspecifiedabove Inn...

Page 15: ...Page 15 SP28 F2 Modular Series Fireplace XG0318 Notes ...

Page 16: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0318 Rev 00 03 2003 ...

Reviews: