Page 10
MD44-DV Direct Vent Vented Fireplace
Finishing Around the Fireplace
Combustible mantels and mouldings may be safely installed over the
top and on the front of the fireplace provided that they do not project
beyond shaded area shown in
Figure 19a
. Side wall clearances are
3". Combustible surrounds may be installed with 3" clearance to the
side of the fireplace as shown in
Figure 19b
.
Fireplace Facing
When selecting the finish material for your fireplace, it is important to
remember the following:
HORIZONTAL TRIMS MUST NOT BE
OBSTRUCTED IN ANY WAY - to do so restricts the air supply for
the control compartments and heat exchanger it also prevents
access for servicing controls.
The face of the fireplace may be painted to match the room decor,
provided you use a heat-resistant paint. Decorative facing must not
extend past the fireplace opening at all, because it will interfere with the
access to retainers for removal of glass door.
Installation
Figure 19a. Combustible mantles and facings.
Mantels & Surrounds
NOTE:
National Canadian Gas Association mantel test requirements
are for fire hazard prevention to combustible materials.
New technology, to meet consumer and government demands for the
wise use of energy, has prompted us to manufacture many models of
fireplaces which are hot, fuel and energy efficient.
Please be aware; temperatures over the mantel will rise above
normal room temperature and walls above fireplace may be hot to
touch.
We recommend careful consideration be given to the effects of
elevated mantel temperatures which may be in excess of product
design, for example: candles, plastic or pictures. This can cause
melting, deformation, discoloration or premature failure of T.V. and
radio components.
Painting:
Figure 19b. Combustible surrounds.
Sheetrock/
Drywall
Header
4
3
45°
Special care is recommended by the Master Painters and Decorators
Association, when painting the fireplace surrounds, to select and
apply a quality
Alkyd sealer
prior to the applying of latex paints. This
is to prevent leaching of water from evaporation and causing a
brownish staining effect to paint over coats.
Installing the Log Set
The
MD44-DV
is supplied with five (5) fibre logs. The two large bottom
logs are factory mounted and cannot be moved. Mount the three top
logs by placing them as indicated in Figure 20a (below). Ember
material, supplied in 6 oz bag, should be placed in the tray along the
front of the burner.
Drywall
Top of
Fireplace
Combustible construction
allowed on or above
shaded area.
12 11 10 9 8 7 6 5 4
3 2 1
12
16
11
15
10
14
9
13
8
7
6
5
4
3
2
1
Figure 20a. Log Installation.
WARNING:
If logs are not placed properly, excessive
sooting will result.