M38BV-ST B-Vented Fireplace

Installing The Gas Line

The gas line must be installed before finishing the M38BV-ST fire-
place. 

Natural Gas

 requires a minimum inlet gas supply  pressure of 

5.5" W.C. & a manifold pressure of 3.5" W.C. 

Propane Gas

 requires a 

minimum inlet gas supply pressure of 11" W.C. & a manifold pressure 
of 10" W.C. Provision must also be made for a 1/8" N.P.T. plugged 
tapping and be accessible for test gauge connection immediately 
upstream of the gas supply controls to the appliance.  The fireplace 
gas connection and the main operating gas valve is located behind 
the removable brass trim at the bottom of the unit and need only be 
attached to the gas line  with an approved fitting, as required by the 

applicable installation codes

.

• Only use gas shut-off valves approved for use by the state, province, 
region, or governing body, in which the appliance is being installed, or 
as required by the applicable installation codes.
• Flexible gas connectors must not exceed 3 feet in length, unless it is 
allowable  within applicable installation codes.

 * After gas line is connected 

each appliance connection, 

valve and valve train

 must be checked while under normal 

operating pressure with either a liquid solution, or leak detec-

tion device, to locate any source of leak. Tighten any areas 

where bubbling appears or leak is detected  until bubbling 

stops completely or leak is no longer detected. 

Do NOT 

use 

a flame of any kind to test for leaks.

Installing The Remote Switch

The 

M38BV-ST 

is equipped with a remote-operated valve, located 

behind the removable brass grille, to the right of the gas control 
valve (refer to Figure 10.) The valve is pre-wired and completely self 
contained to generate its own power.

 DO NOT

 connect any external 

power to it.

Note:

  The switch location must not exceed 30' from the fireplace.

Figure 3.  

Gas line access.

The appliance and its individual shutoff valve must be disconnected 
from the gas supply piping system during any pressure testing of that 
system at test pressures in excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply piping system by 
closing its individual manual shutoff valve during any pressure testing 
of the gas supply piping system at test pressures equal to or less than 
1/2 psig (3.5 kPa).

Installation

B-Vent  Installation

The 

M38BV-ST  

is certified for use with standard 

4" B-Vent 

and 

requires no B-Vent appliance connector. Simply attach the B-Vent to 
the fireplace flue collar, and secure it using 1/4" sheet metal screws. 
Do not penetrate the inner sleave of the B-Vent when tightening the 
screws.
Refer to the current 

CAN/CGA B-149.1

 and

 .2

 or 

ANSI Z223.1-1988 

Gas Installation Code

 for specific vent sizing.

1 3/4

2 3/8

1 3/4

7

7

 

Test your B-Vent installation after completion to ensure that 
no combustible by-products are spilling from the fireplace 
opening. This draft test should be performed after a three(3) 
minute warm up period. The manufacturer will not be respon-
sible for any installations with inadequate draw.

CAUTION:

Installation In 

Bedrooms and Bedsitting Rooms:

This fireplace is supplied with a secondary limit switch -- an added 
safety feature that prevents overheating. This switch will also shut the 
fireplace down if the flue becomes blocked. Once the reason for the 
shutdown has been cured, the pilot burner must be relit.

Summary of Contents for M38BV-ST

Page 1: ...ighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department For Your Safety Do not store or use gasolineorotherflammable vapors and liquids in the vicinity of this or any other appliance Safety Notice Glass doors on gas fireplaces are extremely hot while the fireplaces is on and remain hot even after the fireplace has been turned off Safety ...

Page 2: ...Gas Inspection Branch on installation require ments for factory built gas fireplaces Installation repairs should be done by a qualified contractor Installations in Canada must conform to the current CAN CGA B 149 1 and 2 Gas Installation Code and local regulations This unit employs fans and must be electrically grounded in accordance with CSA C22 1 Canadian Electrical Code Part 1 and or Local Code...

Page 3: ... 1 2 Floor 0 Mantle 6 Recess Depth 17 1 8 Clearance from the top of the fireplace to a combustible ceiling within the fireplace enclosure Refer to page 5 Top View Front View WARNING When this appliance is installed directly on carpeting tile or any combustible material other than wood flooring it must be installed on a metal or wood panel extending the full width and depth of the appliance 41 Figu...

Page 4: ...ble brass grille to the right of the gas control valve refer to Figure 10 The valve is pre wired and completely self contained to generate its own power DO NOT connect any external power to it Note The switch location must not exceed 30 from the fireplace Figure 3 Gas line access The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressu...

Page 5: ...sumer and government demands for the wise use of energy has prompted us to manufacture many models of fireplaces which are hot fuel and energy efficient Please be aware temperatures over the mantel will rise above nor mal room temperature and walls above fireplace may be hot to touch We recommend careful consideration be given to the effects of elevated mantel temperatures which may be in excess o...

Page 6: ...he M38BV ST is supplied with five 5 fibre logs To install simply place log A s rectangular shaped extension into the log mounting slot located on rear wall of the burner assembly Place log B onto front log slots of the burner assembly Place log C and log D onto the mating positions as shown in Figure 7a below When log set is installed it should look like Figure 7b Figure 7b Log Installation Step 2...

Page 7: ...figure 8b Ensure that a good seal is maintained Figure 8b Installing Glass Door Glass door and frame Door surround Tab B Slot A Magnet Pull bottom of door surround outwards and upwards Machine Screws Door Rail Tabs Operation Lighting Instructions See Pages 8 9 Gas Control Knob Shown in Pilot postion Burner Adjustment The M38BV ST is equipped with an adjustable burner allowing you to raise or lower...

Page 8: ... you cannot reach your gas supplier call the Fire To Turn Off Gas To Appliance Operation Model M38BV ST 3 Push in gas control knob slightly and turn clock wise to Off Do not force 4 Replace trim 1 Turn off remote switch 2 Remove lower trim 1 STOP Read the safety information above on this label 2 Remove lower trims 3 Push in gas control knob and turn clockwise to OFF 4 Wait five 5 minutes to clear ...

Page 9: ... gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor What To Do If You Smell Gas Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions 1 Turn off remote switch 2 Remove lower trim Gas Inlet Gas C...

Page 10: ...n Off Gas To Appliance 1 STOP Read the safety information above on this label 2 Flip down the lower trims 3 If the switch on the control module is set to Continuous Pilot Off then the pilot will light when the appliance is turned on by the remote switch When switched to Continuous Pilot On then the control module will attempt to light the pilot until it detects that the pilot has been successfully...

Page 11: ...tings on new metal Glass must be cleaned periodically to remove any film a normal bi product of combustion which may be visible Film can easily be removed by removing the door as shown on page 7 Handle the door carefully and clean it with glass cleaners One of the most effective products is Kel Kem Silicone seals on inner door during initial firing will off gas leaving a visual deposit of a white ...

Page 12: ...lable from the manufacturer or your local dealer M38BV ST I Troubleshooting The following is a troubleshooting chart of possible problems PROBLEM CORRECTIVE ACTION Noisy Pilot Flame Locate Pilot Adjustment Screw Flame is decreased by turning adjust ment screw clockwise Pilot won t ignite Disconnect remote wires and try to light pilot If pilot now works remote connections are faulty Check wiring di...

Page 13: ... by The Companies 2 The Montigo Gas Appliance must be subjected to normal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance will produce excessive temperatures and will result in a fire hazard Limitations On Liability It is expressly agreed and understood that The Companies sole...

Page 14: ...Set RLGS22 RLGS22 13 Fan Kit RFK1009 RFK1009 Note Use only original replacement parts This will protect your warranty cover age for parts replaced under warranty Contact authorized dealers of this product If they can not supply original replacement part s Call toll free at 1 800 378 3115 Canadian Heating Products Montigo Delray Corp 27342 Gloucester Way Langley BC V4W 4A1 When contacting dealer or...

Page 15: ...Page 15 M38BV ST B Vented Fireplace Notes ...

Page 16: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0400 011707 ...

Reviews: