background image

Page 17

MD38-DV-2  Homefire

Part No. XG0111

Maintenance

WARNING:

Do not attempt to clean glass when hot.

Do not clean glass with abrasive materials as any glass
etching may cause premature glass failure.

CAUTIONS

n

Fireplace gas control must be in the “OFF” position and pilot
and main burners extinguished when cleaning appliance with
a vacuum.

n

Doors and logs can get very hot. Handle only when cool.

General

n

Have the fireplace installation inspected yearly, including a visual
check of the vent system, the burner and the pilot flame. For your
convenience a 1/8" manifold pressure tap is supplied on the gas
valve for a test gauge connection. See Figure 26.

n

For Natural Gas this appliance requires a minimum inlet pressure
of 5.5" W.C. and a manifold pressure of 3.5" W.C.

n

For Propane Gas this appliance requires a minimum inlet
pressure of  11" W.C. and a manifold pressure of 10" W.C.

n

Always keep the fireplace area clear and free of combustible
materials, as well as gasoline and other flammable vapours and
liquids.

n

Do not use this appliance if 

any part has been under water

.

Immediately call a qualified service technician to inspect the
appliance and to replace any part of the control system and any
gas control which has been under water.

Cleaning

When the fireplace is first activated, there may be some smoking and a
visible film may be left on the glass. This is a normal condition, and is
the result of burning of protective coatings on new metal.

n

Glass must be cleaned periodically to remove any film (which is a
normal biproduct of combustion) which may be visible. Film can
easily be removed by removing the door, as shown on page 13.
Handle the door carefully, and clean it with non-abrasive glass
cleaners. One of the most effective products is Kel Kem.

n

Silicone seals on inner door during initial firing will "off gas",
leaving a visual deposit of a white substance on combustion
chamber walls. This can easily be removed using normal
household products.

n

Use a vacuum cleaner or whisk broom to keep the control
compartment, burner, and firebox free from dust and lint.

n

Logs may be cleaned periodically with a vacuum to remove soot
or other contaminates.

Gas Control Valve

Figure 27. 

Sit Nova 820 

gas valve

.

Pilot  Burner Adjustment

1. Locate Pilot Adjustment Screw. 

(See figure 27.)

2. Adjust pilot screw to provide properly sized flame as shown in

figure 28).

3. After installing or servicing, leak test with a soap solution with main

burner on. Coat pipe and tubing joints, gasket etc. with soap
solution. Bubbles indicate leaks. Tighten any areas where the
bubbles appear until the bubbling stops completely.

Figure 28. 

Pilot Burner

Manifold Pressure
Test Connection

Pilot Adjustment Screw

Inlet
Pressure

Power
Generator

Wall Switch

Troubleshooting

The following is a troubleshooting chart of possible problems:

PROBLEM

CORRECTIVE ACTION

Noisy Pilot Flame

Locate pilot adjustement screw on gas
control valve. Flame is decreased by
turning adjustment screw clockwise.

Pilot won’t ignite

Disconnect remote wires and try to
light pilot. If pilot now works, remote
connections are faulty. Check wiring
diagram 

figure 

27

.

Main burner will

1. Check wiring (

see figure 27

).

not light

2. Check wall switch for proper
connection.

MD38-DV-2

Summary of Contents for Homefire plus MD38-DV-2

Page 1: ...hbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Warning Improper installation adjustment altera tion service or maintenance can cause injury or property damage Refer to this manual Forassistanceoradditionalinfor mationconsultaqualifiedinstaller service agency or the gas supplier For Your Safety Do not store or use gasoline or other...

Page 2: ...d be done by a qualified contractor Installations in Canada must conform to the current CAN CGA B 149 1 and 2 Gas Installation Code and local regulations If the optional air circulating fan kit is installed it must be electrically grounded in accordance with CSA C22 1 Canadian Electrical Code Part 1 and or Local Codes Installations in the USA must conform to local codes or in the absense of local ...

Page 3: ...learances Theseclearancesapplytoalldimensions except the framed opening where the clearance to combustibles is 0 The MD38 DV 2 clearances to combustible materials are Top Rear Vent 7 Top Top Vent 32 Back 0 Side 1 Floor 0 Mantle 12 Clearancefromthetopofthefireplacetoacombustible ceilingwithinthefireplaceenclosure Refertopage10 If the standard elbow MEL90 is used with the Low ClearanceSleeve CRS30 t...

Page 4: ...ssure of 10 W C Provision must also be made for a 1 8 N P T plugged tapping and be accessible for test gauge connection immediately upstream of the gas supply controls to the appliance The fireplace gas connection and the main operating gas valve is located behind the removable brass trim at the bottom of the unit and need only be attached to the gas line with an approved fitting as required by th...

Page 5: ...1 Frame the termination opening to 12 x 12 2 Fasten the MOSR frame to the interior side of the studs using a minimum of 4 screws 3 Insert the termination into the MOSR frame as shown here and attach by screwing through the four pilot holes in the termination MSR MTO 3 MTO 3F MTO 3 MTKOG 1 Ensure that the two long mounting brackets are facing the bottom of the termination See inset This will provid...

Page 6: ...e vent termination is 84 this would NOT be an acceptable installation Figure 7 Venting Graph Figure 8 Heat Shield Install by sliding over the vent pipe where it passes through combustible construction Heat Shields Due to high flue temperatures heat shields are required on all 38 Series Modular Direct Vent installations except those with vertical terminations at the point where the venting connects...

Page 7: ...o outside wall and a minimum of 7 6 when retracted in opposite direction see Figure 10 and 11 D flex sections and E solid sections may be used in conjunction with one another to obtain different possible horizontal length installations NOTE Flexsectionwithnoverticalrisemustnotexceed maximum horizontal length of 3 feet see Figure 12 Flex runs over 3 feet must fall within the limits set by the venti...

Page 8: ...measured center to center of piping Example Typicalventinstallation 20 verticalvent 2 2 offsets required 25 of 20 5 max offset allowed Thisventingconfigurationmeetsrequirements A Termination MVTK 1 B Flex sections MFL 1 12 section MFL 2 24 section MFL 3 36 section MFL 4 48 section C Solid sections MEXT 1 12 section MEXT 2 24 section MEXT 3 36 section MEXT 4 48 section D Support Ring Plate MSPXT 8 ...

Page 9: ...ion The height from the hearth to the center of the termination is 28 MD38 DV 2 Rear Vent versions are supplied with an 18 extension pipe EXT 18 with female female connections For shorter installations cut the EXT 18 to the desired length For extended installations use the EXT 18 section as supplied for an 18 vent run Note For Rear Vent models maximum horizontal run with no vertical lift must neve...

Page 10: ...imension from the hearth is 90 and the horizontal run to the wall flange of the vent termination is 126 this would be an acceptable installation Example C Unacceptable Installation If the vertical dimension from the floor of the fireplace is 78 and the horizontal run to the wall flange of the vent termination is 108 this would NOT be an acceptable installation Figure 18a MD38 DV 2 Rear Vent Ventin...

Page 11: ...ire hazard prevention to combustible materials New technology to meet consumer and government demands for the wise use of energy has prompted us to manufacture many models of fireplaces which are hot fuel and energy efficient Please be aware temperatures over the mantel will rise above normal room temperature and walls above fireplace may be hot to touch We recommend careful consideration be given...

Page 12: ...rt INSET 1 Tab INSET 2 Mounting Bracket Fresh Air Flex 4 dia High temp silicone seal Venting Plate Front Slot Installation Figure 21a Wiring for optional air circulating fan kit G L2 WH L1 BLK Quick Connect plug to motor Wiring for the optional Fan Kit All 38 Series Modular fireplaces may be equipped with optional fan or blower kits for circulating heat into the living space Installations in Canad...

Page 13: ...surface of the logs will crack due to the heat from the flames This is a normal occurance Log D Log E Log A Log C Log B Installing the Log Set Installing the Logs The MD38 DV 2 is supplied with six ceramic fibre logs Unpack the logs and handle them very carefully 1 Remove the door cover and the glass door 2 Place the Back log onto the back log rest as shown below in figure 24a The log has lip on t...

Page 14: ...p on See figure 25 Figure 24b Proper log placement Installation Operation Lighting Instructions See pages 15 and 16 Burner Adjustment The MD38 DV 2 Homefire Plus is equipped with adjustable burners allowing you to raise or lower the flames Operating the control knob as described below will adjust both the main burner and the ember burner n To raise the flame height turn the black knob located behi...

Page 15: ...ion Model MD38 DV 2 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Flip up lower trim 1 Turn off remote switch 2 Flip down lower trim 1 STOP Read the safety information above on this label 2 Flip down lower trims 3 Push in gas control knob and turn clockwise to OFF 4 Wait five 5 minutes to clear out any gas Smell for gas including near the floor If you then smell gas ...

Page 16: ...o light any appliance n Do not touch any electrical switch do not use any phone in your building n Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions 1 Turn off remote switch 2 Flip down lower trim 3 Turn the switch on the gas control to Off 4 Flip up lower trim 1 STOP Read the safety information above on this label 2 Flip down lower trims 3 Turn swi...

Page 17: ...ny film which is a normal biproduct of combustion which may be visible Film can easily be removed by removing the door as shown on page 13 Handle the door carefully and clean it with non abrasive glass cleaners One of the most effective products is Kel Kem n Silicone seals on inner door during initial firing will off gas leaving a visual deposit of a white substance on combustion chamber walls Thi...

Page 18: ...rms up and glows red Pilot Valve opens Turn gas on Pilot Burner lights Main Valve opens SYSTEM OK Unplug Pilot Burner Cable Measure Voltage at SV9500 SV9600 HSI Terminals 24 VAC Nominal See INSET Replace Igniter Flame Rod Assembly Replace Igniter Flame Rod Assembly Replace SV9500 SV9600 Measure Voltage to SV9500 SV9600 Voltage must be at least 19 5 VAC Discard old Igniter Flame Rod Assembly Replac...

Page 19: ...afirehazard Limitations On Liability Limitations On Liability Limitations On Liability Limitations On Liability Limitations On Liability ItisexpresslyagreedandunderstoodthatTheCompaniessoleobligation andpurchaser sexclusiveremedyunderthisWarranty underanyotherwarranty expressed orimplied orincontract tortorotherwise shallbelimitedtoreplacement repair orrefund asspecifiedabove InnoeventshallTheComp...

Page 20: ...ilable Options and Accessories 1 Add on Bay Window 2 Hand Held Remote Control 3 VariableSpeedBlowerKit 4 4 Fan Kit 5 4 PiecePictureFrameSurround PFS 6 3 PiecePictureFrameSurround PFO 7 DoorCover Square DF0 8 DoorCover Arched DFA 9 Horizontal Trim Kits Black Brass Nickel 10 ReplacementLogset ...

Page 21: ...ted States 6 feet 1 8 m minimum in Canada L clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance 16 inches 41 cm minimum for appliances 100 000 BTU H 30kW M clearance to mechanical air supply inlet 6 feet 1 8 m minimum N clearance above paved sidewalk or a paved driveway located on public property 7 feet 2 1 m minimum P clearanceunderveranda po...

Page 22: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0111 Rev 8 07 02 ...

Reviews: