Page 18

H52-DF Gas Fireplace

Part No. XG0650

Appendix A - Termination Locations

A

 =  clearance to the termination frame above grade, veranda, porch, deck, 

or balcony [16 inches (41 cm) minimum] 

B

 =  clearance to door, or sides and top of window, that may be opened [16 

inches (41 cm) minimum for appliances 

100 000 BTU/H (30kW)] 

C

 =  clearance to bottom of  window that may be opened horizontally [36 inches 

(92 cm) minimum for appliances 

100 000 BTU/H (30kW)] 

D

 =  no clearance to permanently closed window when installed with approved 

glass penetration termination

E

 =  clearance to permanently closed  window [16 inches 41 cm recommended 

to prevent condensation on window]

F

 =  vertical clearance to ventilated soffit located above the termination within a 

horizontal distance of 2 feet (61 cm) from the centreline of the termination 

[22 inches (56 cm) minimum]

G

 =  c l e a r a n c e   t o   u n v e n t i l a t e d   s o f f i t   [ 1 6   i n c h e s 

( 4 1   c m )   m i n i m u m   t o   n o n - c o m b u s t i b l e s ]   

[22 inches (56 cm) minimum to combustibles]

H

 =  clearance to outside corner [9 inches (23 cm) minimum]

I

 =  clearance to inside corner [12 inches (31 cm) minimum]

J

 =  *  not  to  be  installed  above  a  meter/regulator  assembly  within  

40" (103 cm) horizontally from the centreline of the regulator

K

 =  clearance to service regulator vent outlet [3 feet  minimum in the United 

States] [*6 feet  (1.8 m) minimum in Canada]

=  clearance to non-mechanical air supply inlet to building or the combustion 

air inlet to any other appliance [16 inches (41 cm) minimum for appliances 

100 000 BTU/H (30kW)]

M

 =  clearance to mechanical air supply inlet [*6 feet  (1.8 m) minimum]

N

 = 

 clearance above paved sidewalk or a paved driveway located on public 

property [*7 feet (2.1 m) minimum]

P

 =  clearance  under  veranda,  porch,  deck,  or  balcony  

[16  inches  (41  cm)  minimum

  to  non-combustibles] 

[22 inches (56 cm) minimum

 to combustibles]

Q

 =  clearance above a roof [24 inches (61 cm) minimum]

R

 =  clearance  to  adjacent  walls  and  neighboring  buildings  

[18 inches (46 cm) minimum]

S

 =  c l e a r a n c e   f r o m   c o r n e r   i n   r e c e s s e d   l o c a t i o n  

[12 inches (31 cm) minimum]

T

 =  m a x i m u m   d e p t h   i n   r e c e s s e d   l o c a t i o n 

 [48 inches (122 cm) minimum]

U

 =  minimum  width  for  back  wall  of  recessed  location 

 [24 inches (61 cm) minimum]

V

 =  no horizontal clearance between the frames of two terminations that 

are level.

W

 =  horizontal clearance between the frames of two terminations that are 

not level.  [36 inches (92 cm) minimum]

 

a vent shall not terminate directly above a sidewalk or paved driveway 

which is located between two single family dwellings and serves both 

dwellings

   only permitted if veranda, porch, deck, or balcony has an open side that 

is equal to or greater than the depth of the enclosed area

*

   as specified in CGA B149 Installation Codes. Note: local Codes or 

Regulations may require different clearance.

Summary of Contents for H52-DFN

Page 1: ...e Safety Notice Glass doors on gas fireplaces are extremely hot while the fireplace is on and remain hot even after the fireplace has been turned off Safety screens are available and can reduce the risks of severe burns Please keep children away from the fireplace at all times C US Installer Leave this manual with the appliance Consumer Leave this man ual for future reference Check local codes and...

Page 2: ... this owner s manual unless noted other wise applies to all models and gas control systems Your new Montigo gas fireplace will give you years of durable reliable use Welcome to the FireFeature family of gas fireplace products Safety Alert Key DANGER Indicates a hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a hazardous situation which if not avoid...

Page 3: ... as instructed in this manual Consult your local Gas Inspection Branch on installation requirements for factory built gas fireplaces Installation repairs should be done by a qualified contractor Installations in Canada must conform to the current CAN CGA B 149 1 and 2 Gas Installation Code and local regulations If the optional air circulating fan kit is installed it must be electrically grounded i...

Page 4: ...ir convection current on the fireplace G H J K C L I C L K J H52 Fireplace Dimensions A 52 B 56 C 47 21 2 D 373 4 E F G H 287 8 38 5 1 I 8 J N A K R H52DF 19 N A L O N M M O H52DF 29 3 4 N Framing Dimensions 52 1 4 56 1 4 B A C D D D F 12 6 1 2 G B Installing The Gas Line The gas line must be installed before finishing the H52 DFN Fireplace Natural Gas requires a minimum inlet gas supply pressure ...

Page 5: ...g the standoff s Installing The Remote Switch The H52 DFN s gas valve located behind the lower trim may be connected to a wall switch The valve generates its own power on a millivolt circuit Use only low voltage wire and DO NOT connect any external power to it Refer to Figure 15 for wiring requirements Note The switch location must not exceed 30 from the fireplace Termination Installation Thissect...

Page 6: ... LPVH60 60 foot power cord and harness LPVH70 70 foot power cord and harness LPVH80 80 foot power cord and harness Before You Begin Minimum clearances of 1 from vent to all combustible materials must be maintained The LDVPV58 must only be installed with Montigo venting components as specified in these instructions In order to maintain the power vent system integrity all 5 and 8 venting connections...

Page 7: ... Factory Installed Pipe Adapter Restrictor are not Covered when installing New Pipe Connection Venting Installation The LDVPV58 s Power Vent must be installed with the H52 DFN gas fireplaceequippedwithanelectronicignitionsystem Wheninstallingthe venting the installation must adhere to the Venting Installation Section in this Installation Operation and Maintenance Instructions as well as these few ...

Page 8: ...d by Ten feet 10 0 for every 90 elbow added Deduct ten feet 10 0 of vent length for every one foot 1 0 of vent run traveling in a downward direction Figure 7a HorizontaI Linear Power Vent with Horizontal Vent Run Linear Power Vent Vertical Vent Multi elbow installations are possible up to a maximum seventy feet 70 0 with three 3 90 elbows Minimum vent run from Fireplace to Power Vent must be two f...

Page 9: ...ure 9 LDVPV58 Power Vent overall dimensions Access Cover 18 1 2 33 1 8 11 34 7 8 Top View Side View Figure 10 LDVPV58 Power Vent framing dimensions 2 MIN 5 MIN 5 MIN 1 2 MIN Louvres Vent Framing Dimensions Figure 11 Conduit and Wiring Clearances Wiring Installation Connect the wiring to the linear power vent as outlined in the previ ous section and connect the wiring to the fireplace as outlined i...

Page 10: ...11a Vertical Exterior Stainless Steel Roof top Power Vent Horizontal Exteriot Stainless Steel Wall mounted Power Vent see instruction guide for EDVWSPV47 58 Figure 11b Horizontal Exterior Stainless Steel Roof top Power Vent Installation Restrictor Ring Part No EPVR55 Figure 14 EPVR55 for H52DF Only Restrictor Ring Installation From inside firebox ONLY Restrictor Ring Installation H52DFN ONLY ...

Page 11: ... has prompted us to manufacture many models of fireplaces which are hot fuel and energy efficient Please be aware temperatures over the mantel will rise above normal room temperature and walls above fireplace may be hot to touch Warning When covering the upper metal portion of the fireplace up to 6 as shown Fig 13 Fig 14 withanon combustiblematerialPleaseNote The decorative facing materials may be...

Page 12: ...t Installing the Logs TheH52 DFNissuppliedwithsevenceramicfibrelogs Unpackthelogs and handle them very carefully install as described below Figure 16 Installation of four 4 Base Logs Step 1 Place the Base Logs A B C D as shown Move them left or right to ensure they fit between the grate stiles as shown Figure 16a Installation of Log E Step 2 Place flat portion underside of Log E on the formed stee...

Page 13: ...e the Horizontal Access Panel Figure 28a Loccate the door buckles Both Sides Typical Step 1 Remove the Horizontal cover by placing fingers in both finger holes then pushng away from you and lifting out Place it aside during maintenance or cleaning Install in reverse order Installed Gas Valve Cover Door Latch Hook Door Latch Slot Hand hold 1 Step 3 Firmly grasp hand hold end of tool and place the m...

Page 14: ... 5 Pull hard if necessary to release the spring tension Caution The latch springs back with force hold the tool securely 4 Step 6 Remove the tool from the latch slot Ensure the latches are hanging freely the hook end is released from the bottom of the door Repeat all 4 steps for the remaining latches Removing the Door Figure 28d Figure 28e Figure 28f To install the door hook the top edge of the do...

Page 15: ... to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions 1 Turn off remote switch 2 Flip down the lower trim 3 Turn the switch on the gas control to Off 4 Flip up the trim 1 STOP Read the safety information above on this label 2 Flip down the lower trims 3 Turn...

Page 16: ...oor as shown on page 15 Handle the door carefully and clean it with non abrasive glass cleaners One of the most effective products is Kel Kem Silicone seals on inner door during initial firing will off gas leaving a visual deposit of a white substance on combustion chamber walls This can easily be removed using normal household products Use a vacuum cleaner or whisk broom to keep the control compa...

Page 17: ...mal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance will produce excessive temperatures and will result in a fire hazard Limitations On Liability It is expressly agreed and understood that The Companies sole obligation and purchaser s exclusive remedy under this Warranty under...

Page 18: ...the United States 6 feet 1 8 m minimum in Canada L clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 16 inches 41 cm minimum for appliances 100 000 BTU H 30kW M clearance to mechanical air supply inlet 6 feet 1 8 m minimum N clearance above paved sidewalk or a paved driveway located on public property 7 feet 2 1 m minimum P clearance under ...

Page 19: ... line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection the...

Page 20: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0650 120108 ...

Reviews: