22
Installation
xg0227 - 112718
Installing a Wall Mounted RHS8 heat shield
the Rhs8 heat shield cAnnot be used wIthIn 36" horizontal or 60"
vertically of the fireplace, (see figure 18a). For applications within these
dimensions the Rhs101 heat shield Must be used.
to install the Rhs8, frame an opening in combustible construction,
Figure 18 below. slide the heat shield in place over the vent pipe which
attaches to the fireplace. After the fireplace and vent pipe has been
installed, clearances should match the dimensions in Figure 18.
Installing a Wall Mounted RHS101 Heat shield
the Rhs101 heat shield Must be used where the Rhs8 termination
(Figure 18 and 18a) cAnnot be used. use the Rhs100 within 36"
horizontal or 60" vertical.
to install the Rhs101, slide the Inner section over the vent pipe that
will connect to the fireplace. Fasten the vent pipe to the back of the
fireplace with a Min. of three sheet metal screws.
next, slide the Rhs101 outer section from the outside of the structure.
To complete the installation fasten the Heat Shield Outer Section &
termination frame to the structure.
figure 15.e
RHS101 Installation
figure 15.c
RHS101 Installation. (Install by sliding Outer Section over vent pipe where it passes
through the combustible construction.
figure 15.a
RHS8 Installation. (Install by sliding over vent pipe where it passes through the
combustible construction).
figure 15.b
RHS8 Installation. (Minimum requirements).
figure 15.d
Heat Shield. After sliding the outer section in place.
RHS8 Heat Shield
1” Min. Both sides Typical
1” Min.
1” Min.
Combustible Framing
Section 3-3-3: Heat Shields 5''/8''
3/8'' min. Both sides Typical
Drywall / sheetrock
Drywall / sheetrock
Rhs101 heat shield, inner section
Rhs101 heat shield, inner section
Vent pipe, from fireplace
Vent pipe, from fireplace
combustible framing
Rhs101 heat shield outer section
Rhs101 heat shield outer section
termination
termination
3/8'' min.
1'' min.
1'' min.
3/8'' min.
Inner shield
outer shield
combustible Framing
1'' min. Both sides Typical
Rhs8 heat shield
combustible framing
exterior
wall
hearth
termination
heat shield
60''
Min.
36''
Min.