SAFET Y
General Safety:
CAUTION!
It is essential that all instructions in this man-
ual be followed to ensure proper operation of the equip-
ment and safety of operating personnel. Use of equipment
in a manner not specified by the manufacturer may impair
protection provided by the equipment. The use of this
symbol is used within this manual to highlight important
safety issues. Please pay particular attention to these
items.
Electrical Shock Caution:
The
Vibra
Rod
™ level sensor can be powered with HIGH
VOLTAGE. No operator serviceable parts are inside. All
servicing is to be performed by qualified personnel.
Extreme care shall be taken if the unit’s cover is removed
and live electrical terminations are exposed. To avoid
electrical shock, do not contact any exposed electrical
connections. Each unit is provided with a “protective
ground” connection, which shall be terminated to earth
ground potential. This terminal shall be used to reduce
shock hazard in the unlikely event of internal insulation
breakdown.
EMC Emissions:
Meets: EN 61326-1: Electrical Equipment for Control
Use, EMC.
EN 55011: Radiated and conducted emissions
(Class A - industrial).
EMC Immunity:
EN 61000-4-2: Electrostatic discharge (industrial).
EN 61000-4-3: RF radiated EM fields (industrial).
EN 61000-4-4: Electrical fast transients (industrial).
EN 61000-4-5: Electrical surges (industrial).
EN 61000-4-6: RF conducted EM energy (industrial).
EN 61000-4-11: Voltage dips, short interruption and
voltage variation immunity (industrial).
Monitor Technologies LLC warrants each
Vibra
Rod
™ to be free
from defects in material and workmanship under normal use and
service for two (2) years from the date of purchase. The pur-
chaser must notify Monitor of any defects within the warranty
period, return the product intact, and prepay transportation
charges. The obligation of Monitor Technologies LLC under this
warranty is limited to repair or replacement at its factory. This
warranty does not apply to any product which is repaired or
altered outside of Monitor Technologies’ factory, or which has
been subject to misuse, negligence, accident, incorrect wiring by
others, or improper installation. Monitor Technologies LLC
reserves the right to change the design and/or specifications
without prior notice.
WARRANT Y
SPECIFICATIONS
Power Requirements: 22-27VDC (+10%);
22-232VAC (+10%), 50/60 Hz
Power Consumption: ≤ 4VA (AC); ≤ 3W (DC)
Altitude: 6562 ft (2000m) max
Installation Category:
II
Pollution Degree:
2
Process Temperature:
Standard Probe: -4˚ to 176˚ F (-20˚ to 80˚ C)
Pipe Extension Probe: -4˚ to 176˚ F (-20˚ to 80˚ C)
Ambient Temp (all units): -22˚ to 149˚ F (-30˚ to 65˚ C)
Output Relay:
VAC: SPDT isolated; 3A @ 250VAC max
VDC: SPDT isolated; 3A @ 30VDC max
Sensitivity:
A:
10.0~12.5lbs/ft
3
(160~200kg/m
3
)
B:
12.5~15.6lbs/ft
3
(200~250kg/m
3
)
C:
18.7~21.8lbs/ft
3
(300~350kg/m
3
)
Fail-Safe:
Switch Selectable: High or Low
Housing: Powder coated die-cast aluminum;
NEMA 4X, ENCLOSURE TYPE 4X,
IP66
Process Connection: 1-1/4" NPT (VibraRod),
1-1/4” NPSC (Vessel)
Pressure Rating:
Standard Probe: 145psi (10bar)
Pipe Extension Probe: 145psi (10bar)
Conduit Connections: 1/2" NPT
Local Indicator: Bi-color LED:
Green = No material,
Red = Material present,
No light = No power
Probe Material:
Standard Probe: 304SS
Pipe Extension Probe: 304SS with 304SS 3/4” pipe,
Max 6ft / 1.83m (Top Mount),
Max 2ft / 0.61m (Side Mount)
Weight:
Standard Probe Version: Approx. 3.25 lbs (1.5 kg)
Approvals:
CSA
US/C
: Ordinary Locations;
Class
II,
Div. 1 & 2, Groups E, F, G;
Class
III
Hazardous Locations
with Intrinsically Safe Probe
ATEX: II 2D Ex tb [ia Da] lllC T75
˚
C Db
IECEx: Ex tb [ia Da] lllC T75
˚
C Db
(See Bulletin #554K regarding specific
conditions of use.)
CE Mark
CHINA RoHS 2