[9]
4.
Genset Info.: Display generator inforamtion
A.
Event Record:
Display operation history
B.
Parameter Modify:
1.
Crank Settings
1.
Detect Frequency
Setting
:
Disable/ Enable
Default
:
Enable
Description
:
Check frequency value before cranking the engine.
2.
Detect oil press
Setting
:
Disable/ Enable
Default
:
Enable
Description
:
Check oil pressure before cranking the engine.
3.
Crank interval
Setting
:
5~40(seconds)
Default
:
10
Description
:
Set the duration of each crank.
4.
Crank attempts
Setting
:
1~10
Default
:
3
Description
:
Set total number of crank attempts.
5.
Escape up limit
Setting
:
15~30(Hz)
Default
:
20
Description
:
When frequency reaches setting, starter motor disconnects from engine.
6.
Engage low limit
Setting
:
15~30(Hz)
Default
:
20
Description
:
If frequency is below setting allows crank procedure
7.
OP build up time
Setting
:
0.2~2.0(Seconds)
Default
:
0.6
Description
:
Time delay before disconnecting starter motor after oil pressure switch
activates. (“Detect oil press” must be enabled.)
8.
Idle interval
Setting
:
0~600(Seconds)
Summary of Contents for GTR-660