4.

 

  Genset Info.: Display generator inforamtion 

 

A.

 

Event Record: 

Display operation history

 

 

B.

 

Parameter Modify: 

1.

 

Crank Settings 

1.

 

Detect Frequency   

Setting

Disable/ Enable 

Default

Enable 

Description

Check frequency value before cranking the engine. 

2.

 

Detect oil press 

Setting

Disable/ Enable 

Default

Enable 

Description

Check oil pressure before cranking the engine. 

3.

 

Crank interval 

Setting

5~40(seconds) 

Default

10 

Description

Set the duration of each crank. 

4.

 

Crank attempts 

Setting

1~10 

Default

Description

Set total number of crank attempts. 

5.

 

Escape up limit 

Setting

15~30(Hz) 

Default

20 

Description

When frequency reaches setting, starter motor disconnects from engine.   

6.

 

Engage low limit 

Setting

15~30(Hz)

 

Default

20 

Description

If frequency is below setting allows crank procedure

 

7.

 

OP build up time 

Setting

0.2~2.0(Seconds) 

Default

0.6 

Description

Time  delay  before  disconnecting  starter  motor  after  oil  pressure  switch 

activates. (“Detect oil press” must be enabled.)

 

8.

 

Idle interval 

Setting

0~600(Seconds) 

Summary of Contents for GTR-660

Page 1: ...1 GTR 660 User manual T E L 0 4 2 2 3 8 0 6 9 8 F A X 0 4 2 2 3 8 0 8 9 1 Web Site http www monicon com t w E m a i l s a l e s m o n i c o n c o m t w...

Page 2: ...In password entry mode this keypad switches to next digit 2 Under PARAMETER setting this keypad switches to the next parameter 1 In password entry mode this keypad switches to previous digit 2 Under P...

Page 3: ...METER setting mode this keypad decreases the setting Enter or exit the parameter setting mode Code 0000 Confirm and save the settings These keypads alternately change the display of Genset information...

Page 4: ...gine again For example if the conditions and parameter settings are given as follows 1 stop duration is 10 seconds crank attempt is 3 times The engine cranks for 10 seconds and then rest for 10 second...

Page 5: ...CT 2 input I2 51 CT 3 input I3 52 CT Common input Com 53 Sensor V output Sensor V 54 Sensor Common GND input Common 55 Oil pressure sensor input Oil Press 56 Oil temperature sensor input Oil Temp 57...

Page 6: ...6 2 Dimension...

Page 7: ...VAR 3 phase 6 P F 7 RPM 8 Engine parameter settings 9 Battery voltage 10 Exerciser 11 Water temperature 12 Oil pressure 13 1024 Event log 14 64 Error record B Remote access 1 Start stop and reset 2 Pa...

Page 8: ...ion DC input 8 36 VDC Power consumption Max 24 W Voltage measurement 0 500VAC 0 2 Current measurement 0 5 A CT ratio 0 2 Frequency measurement 0 80 Hz 0 02 Charger or pickup voltage 5 V 70 V peak to p...

Page 9: ...fault 10 Description Set the duration of each crank 4 Crank attempts Setting 1 10 Default 3 Description Set total number of crank attempts 5 Escape up limit Setting 15 30 Hz Default 20 Description Whe...

Page 10: ...iggering engine shutdown failed alarm 5 Trip then shut Setting Disable Enable Default Enable Description When error occurred timer starts before shutdown the engine 6 Trip duration Setting 30 900 Seco...

Page 11: ...Description Set the hour meter in hours 4 Acc Hour 100 Setting 0 99 100 Default 0 Description Set the hour meter in 100 hours scale 4 Sensors Switches 1 H W T Detection Setting Disable Enable Default...

Page 12: ...tion Activates Input 0 function 3 Input 0 Name Setting 1 Emergency Stop 2 User Define 3 Low battery Voltage 4 System fault 5 High fuel level 6 System trip 7 Insulation Fail 8 Cooling failure 9 Malfunc...

Page 13: ...ally close or normally open 11 In1 delay Setting 0 2 5 0 Seconds Default 2 0 Description When input1 activates timer starts before activating protection 12 Input 2 Detect Setting Disable Enable Defaul...

Page 14: ...ng 1 Warning 2 Alarm 3 Trip 4 Stop Default 4 Description Setup the action when input 3 activates 20 In3 Switch Type Setting NC NO Default Normal Open Description Setup Input 3 to normally close or nor...

Page 15: ...water temperature switch 16 High AC voltage 17 Low AC voltage 18 Overload 19 Short circuit 20 Low battery voltage 21 High battery voltage 22 Input 0 activate 23 Input1activate 24 Input 2 activate 25...

Page 16: ...ting 50 60 60 72 Hz Default 55 66Hz Description When AC frequency is higher than setting controller shuts down the engine and display high frequency error if high frequency protection is enable 4 Hi F...

Page 17: ...sables and engine operates at idle speed 8 Battery 1 System DC volt Setting 12 24 V Default 12 Description Setup DC voltage in 12V or 24V 2 Batt Fault Alarm Setting Disable Enable Default Enable Descr...

Page 18: ...V Description Setup controller AC input voltage 3 Hi ACV Detect Setting Disable Enable Default Enable Description Activates high voltage protection 4 Hi ACV Protect Setting 1 Warning 2 Alarm 3 Trip 4...

Page 19: ...setpoint Setting 34 88 36 96 58 152 62 166 66 176 114 304 V Default 56 60 96 110 110 198 Description When sudden drop of AC voltage blows setting low voltage protection is disabled 13 ACV Escape Motor...

Page 20: ...000 0 A 64 0 3200 0 A 80 0 4000 0 A 100 0 5000 0 A 120 6000 A Description When current is above setting the controller outputs trip signal setup range is related to the CT ratio 5 Overload Delay Setti...

Page 21: ...e LCD A If the engine revolution is 1800 and alternator revolution is 460 input pulse the R P M numerator could be set to 90 1800 20 and R P M denominator could be set to 23 460 20 Solution 1800 460 3...

Page 22: ...nt Setting 1350 2100 RPM Default 1980 Description If engine speed is higher than setting controller shuts down the engine only if over speed is enabled 8 Over speed delay Setting 1 10 Second Default 1...

Page 23: ...e motor Setting Disable Enable Default Disable Description Disconnect starter motor when oil pressure reaches setting 9 Esc OP Set point Setting 25 65 PSI Default 45 Description Disconnect starter mot...

Page 24: ...ing Disable Enable Default Enable Description Activates exerciser function 2 Date week Depend Setting Date Week Default Date Description Setup monthly exercise by date or week 3 Date set point Setting...

Page 25: ...password 4 Maintain Code 1 Setting 0 99 Default 15 Description Setup remaining digits of service password 5 Maintain DnCount Setting 0 1275 hour Default 250 Description Setup the duration between eac...

Page 26: ...for displaying warning or error messages after engine starts 2 Language Setting English Chinese Default English Description Choose between English or Chinese language 3 Comm Address Setting 0 255 00H...

Page 27: ...iption Setup real time clock 2 User Code Description Reset user password 3 Maintain Code Description Reset engineer password 4 Crank information Description a Total count Display total number of crank...

Reviews: