78D0011
11
WDV Series Gas Fireplace
Vent InstallatIOn
InstallatIOn plannInG
There are two basic types of direct-vent installation:
•
Horizontal Termination
•
Vertical Termination
It is important to select the proper length of vent pipe for
the type of termination you choose. It is also important to note the wall thickness.
FOr hOrIZOntal terMInatIOn
Select the amount of vertical rise desired. All horizontal run of venting must have 1/4" rise for
every 1" of run towards the termination below 7
Z\x
feet of vertical rise from the floor of the fire-
place. With 7
Z\x
feet or more vertical rise from the floor of the fireplace, the horizontal run may
run level. NEVER run vent piping down.
You may use up to three 90° elbows in this vent configuration. Refer to Vertical/Horizontal Ter-
mination Configurations on
Page 15
.
FOr VertIcal terMInatIOn
Measure the distance from the fireplace floor to the ceiling. Add the ceiling thickness, the vertical
rise in an attic or second story, and allow for sufficient vent height above the roof line.
nOte:
You may use two 45° elbows in place of a 90° elbow. You must follow rise to run ratios
when using 45° elbows. The appliance is approved for use with three 90° elbows maximum or
a combination of 90° and 45° elbows up to a maximum of 70°.
For two-story applications, firestops are required at each floor level. If an offset is needed in the
attic, additional pipe and elbows will be required.
You may use a chase with a vent termination with exposed pipe on the exterior of the house.
Refer to
Installing A Vent System in an Outside Chase
below. If pipe is enclosed in chase, it is
not exposed.
It is very important that the venting system maintain its balance between the combustion air
intake and the flue gas exhaust. Certain limitations apply to vent configurations and must be
strictly followed.
InstallInG a Vent systeM In an OutsIDe chase
A chase is a vertical boxlike structure built to enclose venting that runs along the outside of a
building. A chase is required for such venting.
n
O
t
Ice
When installing in a chase, you should insulate the chase as you would the
outside walls of your home. this is especially important in cold climates.
Insulation should be considered a combustible material. Maintain proper
clearances to all combustible materials.
treatment of firestops and construction of the chase may vary from
building type to building type. these instructions are not substitutes for
the requirements of local building codes. you must follow all local building
codes.
n
O
t
Ice
never run the vent pipe level down. this may
cause excessive temperatures which could
cause a fire.
W
arn
In
G
always maintain minimum clearances around vent systems. the minimum
clearances to combustibles for horizontal and vertical vent pipe are 1" at the
top, sides and bottom of the vent system. Do not pack the open air spaces with
insulation or other materials. this could cause high temperatures and may present
a fire hazard.
W
arn
In
G