M400BFC Balanced Flue Heat-Circulating Fireplace

87D1505

Planning Information

Preplanning an installation is very important to ensure 
safety and to save time and money.  An installer must 
predetermine where a fireplace will be set and how the 
chimney system will be run.

Mounting the Fireplace

A fireplace may only be mounted on the following sur-
faces:
1.  A flat combustible surface.
2.  A raised wooden platform.
3.  A concrete block or other solid object placed be-

neath each of the four (4) corners of the fireplace.

The fireplace 

must

 be spaced 1” (25 mm) from a com-

bustible back wall and 1/2” (13 mm) from a combustible 
side wall or support. (Page 13, Fig. 17)

Planning the Chimney Run

Determine how the chimney will be run, length of run 
and chimney components required to complete the 
job. (Fig. 4)  

Never

 install a chimney below minimum 

heights.

In planning a chimney system, it is important to know:
1.  The height of a chimney is measured from the 

hearth to the exit point on the termination.

2.  A chimney cannot be offset more than 30° from a 

vertical plane.

3.  A chimney may run straight up or it may be neces-

sary to offset it to avoid obstructions.

4.  The maximum length of an angled run (total chimney 

system) is 20’ (6 m).  

5.  No more than 2 offsets (4 total 30° elbows in U.S./or 

2 total 45° elbows in Canada) per fireplace may be 
used.

6.  A guy wire stabilizer is required for chimneys extend-

ing more than 6’ (1.8 m) above a roof line.

The Ten Foot Rule

Major U.S. building codes specify a minimum chimney 
height above the roof top. The “Ten Foot Rule” is a fire 
safety rule and not a draft rule.  To ensure proper draft, 
it is recommended that you always meet or exceed the 
“Ten Foot Rule,” especially when installing a termination 
on a high pitch roof.  (Fig. 5)
The key points of the “Ten Foot Rule” are:
1. If the horizontal distance from the chimney to the 

peak of the roof is 10’ (3 m) or less, the top of the 
chimney must be at least 2’ (610 mm) above the 
peak of the roof, but never less than 3’ (914 mm) 
in height above the highest point where it passes 
through the roof.

2. If a horizontal distance from the chimney to the peak 

of the roof is more than 10’ (3 m), a chimney height 
reference point is established on the surface of the 
roof a distance of 10’ (3 m) from the chimney in a 
horizontal plane. The top of the chimney must be 
at least 2’ (610 mm) above the reference point, but 
never less than 3’ (914 mm) in height above the high-
est point where it passes through the roof.

L1

L1

LT

TOTAL

LENGTH 

(LT)

INSTALLED

LENGTH 

(L1)

56O

"

56O

"

56O

"

56O

"

56O

"

56O

"

56O

"

56O

"

FP288A

MBUF-INSTALLED LENGTH

Triple wall

1/28/99   djt

TRIPLE

WALL

81

818

83

84

FP288a

Fig. 4

  Installed lengths of chimney sections.

2’ Min.

2’ Min.

3’

Min.

0 To 10’

3’

Min.

0 To 10’

AC246

4/1/96

Reference

Point

AC246

Fig. 5

  Ten Foot Rule illustration.

Summary of Contents for M400BFC

Page 1: ...nced Flue Closed Combustion Heat Circulating Fireplace For use in the U S Canada Underwriter s Laboratories Report No MH7603 DO NOT DISCARD THIS MANUAL Retain for future use 87D1505 12 09 Rev 3 Homeowner s Installation and Operating Manual ...

Page 2: ...BFC Listed UL127 ULC S610 Standard for Factory Built Fireplaces Safety Information 3 Specifications and Framing 4 Parts Identification 6 Chimney Requirements 7 Planning Information 8 Installation 9 Replacement Parts 19 Accessories 21 Warranty 23 Table of Contents ...

Page 3: ...himney assembly or any component parts thereof except for chase flashings as detailed in MHSC Chimney Top installation instructions Installation other than as instructed by MHSC or Installation and or use of any component part not manufactured or approved by MHSC in combination or assembly with a MHSC fire place system notwithstanding any indepen dent testing laboratory or other third party approv...

Page 4: ... BFC36 specs 8 18 00 djt 1356O Dia 343mm Rough Opening Width 43 Rough Opening Height Rough Opening Depth Gas Line Access 5156QE 1297mm 5156QE 1297mm 6 Q E 1 8 3 4 m m 6M 197mm 23 584mm 610mm 6QE 624mm 3956M 997mm 556QE 246mm 35 889mm 279mm Gas Line Access 56O 902mm 36 914mm 1092mm 11 Dia 179mm 8 Dia 203mm 5 6 9 1 8 m m A B C FP1531 hearth dimensions 9 04 djt Front Width Back Width Depth A B C M400...

Page 5: ...ftstop Standoff Surround Trim Ledge Standoff Glass Door Romex Pigtail Gas Line Access Knock out Each Side Air Inlet Basket Grate Bottom Grille Metal Safety Strip s Shown not inplace 1 2 or 3 pieces Nailing Flange Top Grille and Air Outlet Gas Line Ac cess Hole Each Side Ceiling Level Firestop Batt Insulation Cut out around firestop FP554c Fig 2 Fireplace and chase parts identification ...

Page 6: ...feet of angled run of chimney Chimney supports are required for every 30 feet and 60 feet of vertical chimney height above the hearth Determine the offset distance of your chimney arrangement from the centerline of the fireplace to the centerline of the chimney where it is to pass through the first ceiling Note This offset distance may not be your full offset distance See Examples 2 and 3 Fig 3 Ch...

Page 7: ...lbows in Canada per fireplace may be used 6 A guy wire stabilizer is required for chimneys extend ing more than 6 1 8 m above a roof line The Ten Foot Rule Major U S building codes specify a minimum chimney height above the roof top The Ten Foot Rule is a fire safety rule and not a draft rule To ensure proper draft it is recommended that you always meet or exceed the Ten Foot Rule especially when ...

Page 8: ...cation or how the chimney system should be run contact your Monessen dealer for assistance Installation Insulating Fireplace Enclosure for Cold Climates If you live in a cold climate it is not required but highly recommended that you insulate fireplace enclosure to eliminate cold air penetration as much as possible Insulate base of fireplace with a noncombustible insulation rated for a minimum of ...

Page 9: ... wire nuts must be tight NOTE Check local building codes to determine if junction box is required at the romex pigtail house wire connection Also check junction box and speed control SCVS installation instructions The Model FKSX A blower assembly is preinstalled in the M400BFC FP1062 romex pigtail 8 21 00 djt Romex Pigtail Provided Fireplace Electrical Coverplate Wire Nuts Not pro vided Ground Bla...

Page 10: ...t Check to see where existing ceiling joists and other possible obstructions are located i e wiring plumbing etc If necessary re position chimney and or fireplace to avoid obstructions Cutting the Hole Cover fireplace collar opening and cut proper sized chimney hole in chimney Framing the Ceiling Hole Frame the ceiling chimney hole as shown in Figure 10 It is good practice to use framing lumber th...

Page 11: ...n front of the fireplace This Z shaped safety strip is not provided but must be fabricated of metal with each horizontal leg at least 1 38 mm wide and equal in length to the metals strips provided with the fireplace Note Safety strips are not required over non com bustible floors where all supports at the base of the fireplace are noncombustible Four 4 nailing flanges are supplied with the firepla...

Page 12: ...ickness up to 8 203 mm When combined thickness of ceiling material ceiling joists and flooring material exceeds 8 203 mm adjustments must be made in framing to assure that minimum air spaces to chimney are maintained Proper Firestop Spacer Installation Figure 16 shows different installation procedures for both an area that is an attic and an area that is not an attic If the area above the ceil ing...

Page 13: ...jacent combustible surfaces Combustible surfaces include burnable materials such as ceiling members joists flooring combustible insulation and roof structures WARNING Do not pack required air spaces with insulation or other materials Mark an outline of the roof hole around the center of the point nail Note Hole dimensions given in the chim ney top installation instructions are horizontal dimen sio...

Page 14: ... a substitute for local building codes You must check your local building codes to determine specific requirements for your city or state Note Other building materials may be required in addition to firestop spacers Finishing CAUTION All joints between the finished wall and the fireplace surround top sides must be sealed with non combustible material to prevent cold air leakage into the room Only ...

Page 15: ...mantel clearances 12 from top of grille opening 6 from top of grille opening Face Plate FP531b mantel clearances 9 03 djt Z x 12 305mm Max 12 305mm Min 1Z x 38mm 6 159mm Min Fig 19 Mantel clearance Combustible Mantel Shelf and Trim Finished Wall Stud Standoff Circulating Front Noncombustible Material Fireplace Opening 2 x 4 Stud Finished Wall Must be sealed with noncom bustible material Fireplace ...

Page 16: ...rotect hearth extension material Fig 21 Secure the hearth extension to the floor to prevent shifting using trim molding or other similar means at three 3 outer edges Seal crack between the fireplace hearth and hearth extension with a non combustible material Figs 21 and 23 Minimum Wall Clearances WITH Noncombustible Surround Facing WITHOUT Noncombustible Surround Facing Minimum Hearth Extension Di...

Page 17: ...nits of K BTU SQ FT HR F IN Thickness of Listed Material FP533ADD Addendum 6 1 99 djt 8 4 99 changed 2 to 1 one inch to 1 2 inch djt FP533ADD Fig 22 Hearth extension material factors Example of Determining Hearth Extension Equivalents To determine the thickness required for any new mate rial NEW K of new material per inch thickness required X of listed thickness K of listed material per inch mater...

Page 18: ...device and 2 complying with the Standard for Decorative Gas Appliances for Installa tion in Vented Fireplaces ANSI Z21 60 or CSA draft requirements for Gas Fired Log Lighters for Woodburn ing Fireplaces Draft No 4 August 1993 Decorative gas appliance should be installed in accor dance with the National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition CAUTION When using decorative gas appliance flu...

Page 19: ...on M400BFC 1 Top Grille Painted 3126160 2 Bottom Grille Painted 3126160 3 Grate Assembly 7579218 4 Left Door Assembly Complete 30004361 5 Right Door Assembly Complete 30004362 6 Rear Firebrick 2353145 7 Side Firebrick two per fireplace 2353146 8 Hearth Firebrick 2353140 9 Nailing Flange four per fireplace 2422198 10 Fiberglas Rope Gasket Outer Collar 7547137 11 Top Refractory 2353147 12 Front Bric...

Page 20: ...ass Panel two per fireplace 30004352 21 Flat Gasket 3 4 Wide two per fireplace 20013997 22 Knob two per fireplace 1600657 23 Bushing four per fireplace 1201895 24 Pan Hd PH 1 4 20 x 1 Black two per fireplace 1200907 25 Spacer two per fireplace 1600070 26 Spring Clip 30004450 27 8 18 x 1 2 Decorative Screw 7521180 28 Hinge Spacer two per fireplace 30004360 29 BFC Door Assembly 20014006 Ref Descript...

Page 21: ...t ed only with MHSC approved components If you use an unapproved component to make any modifications you may create a possible fire hazard and will void the MHSC warranty In addition such action may void the coverage provided by the owner s insurance Accessories Hearth Extension Insulation Provides hearth extension floor protection EH2416 Grate for BR BC36 42 Holds firewood in firebox RBG M400BFC ...

Page 22: ...hing is not included TT200C Adapter Kit TT8CB is required Chase Top Housing Used with chase terminations to prevent rain entry FL88 8 flue Contemporary Flashing 8 6 12 with 8 flue Required for Contemporary Round Top 0 to 6 12 pitch termination to prevent rain entry 8 12 12 with 8 flue 6 12 to 12 12 pitch Chimney Sections 8 flue 81 1 long Used to build chimney systems 818 1 long 83 3 long 84 4 long...

Page 23: ...or pressure dif ferentials produced by wind Broken glass components Cracks in ceramic and castable parts that do not affect safe operation We do not warrant this fireplace to be in compliance with your local building code Building codes vary greatly throughout the country and you should determine whether your local building code contains restrictions on the use of this fireplace before you purchas...

Page 24: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com ...

Reviews: