Non-combustible Material 

CLEARANCES 

AND

 

HEIGHT REQUIREMENTS

4.

   Mantel clearances: 

The canopy supplied with the unit must be installed. If a combustible mantel is installed, it must 

meet the clearance requirements as shown in 

Figure 5

. However, if lower mantel height is desired, 

see page 15 

for 

canopy options.

5.   Floor clearance: 

This inner chamber fi rebox fl oor must be installed at least 1

33

/

8

" above any combustible fl ooring mate-

rial, such as carpeting or asphalt tile, which is closer than 14" to the base of the fi rebox. 

See Figure 6. 

Or

    The inner chamber fi rebox fl oor may be installed nearer to the fl oor if a minimum of 14" of noncombustible material 

such as slate or marble is installed between the base of the fi rebox and the combustible fl ooring.

 See Figure 7. 

Figure 5 - Mantel Clearances

Figure 6 - Minimum Clearance above 

Combustible Flooring 

Figure 7 - Minimum Clearance above Combustible 

Flooring with Non-Combustible Material Installed at 

Base of Fireplace 

Combustible 

Material 

1

3

/

8

" Minimum

14" Minimum

Can Be Less 

than 1

3

/

8

Non-Combustible 

Material 

Summary of Contents for LO-RIDER LCUF36

Page 1: ...NGS If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Imm...

Page 2: ...l Installation Information 6 Firebox External Dimensions 6 Minimum Hearth Dimensions 7 Location of Fireplace 7 Clearances and Height Requirements 8 Fireplace Framing 10 Gas Line Installation 12 Canopy Installation 13 Other Optional Equipment 14 Illustrated Parts Breakdown 14 Warranty Back Cover ...

Page 3: ...ead these instructions carefully before installing or trying to operate a vent free gas heater in this firebox IMPORTANT SAFETY INFORMATION 1 Due to high temperatures the appliance should be located out of traffic and away from furniture and draperies 2 Children and adults should be alerted to the hazard of high surface temperature and should stay away to avoid burns or clothing ignition 3 Young chi...

Page 4: ...d be reduced 4 percent for each 1 000 feet above sea level Refer to the National Fuel Gas Code 21 The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1 2 psig 3 5 kPa 22 The appliance must be isolated from the gas supply piping system by closing its equipment shutoff valve du...

Page 5: ...structions 2 Canopy 4 Five 5 sheet metal screws for canopy WHAT YOU WILL NEED FOR INSTALLATION TOOLS BUILDING SUPPLIES Phillips screwdriver Square Framing materials Hammer Piping complying with local codes Wall finishing materials Saw and or sabersaw Tee joint Caulking material noncombustible Level Pipe wrench Fireplace surround materials noncombustible Measuring tape Pliers Electric drill and bits...

Page 6: ...is unique however and might require a different sequence 1 Position firebox prior to framing or into prepared framing 2 Plumb gas line Gas connections should only be performed by an experienced licensed certified tradesman 3 Install vent free gas log heater per the instructions provided with the vent free gas log heater 4 Complete finish wall material surround and optional hearth extension to your in...

Page 7: ...isters for forced air furnaces air conditioners windows or doors Installation must provide adequate ventilation and combustion air DO NOT INSTALLTHIS FIREBOX IN A BED ROOM OR BATHROOM Location should be out of high traffic or windy or drafty areas DO NOT INSTALLWHERE CURTAINS FURNITURE CLOTHING OR OTHER FLAMMABLE OBJECTS ARE LESS THAN 42 FROM FRONT OF HEATER Never obstruct the front opening of the ...

Page 8: ... to follow these requirements may create a fire hazard 1 Sidewall clearances The clearance from the inside of the appliance to any combustible wall should not be less than 9 See Figure 4 2 Ceiling clearance The ceiling must be at least 42 from the top of the firebox opening See Figure 4 3 Back wall clearnace The appliance may be placed against a combustible back wall Figure 4 Clearance and Height Re...

Page 9: ... combustible flooring mate rial such as carpeting or asphalt tile which is closer than 14 to the base of the firebox See Figure 6 Or The inner chamber firebox floor may be installed nearer to the floor if a minimum of 14 of noncombustible material such as slate or marble is installed between the base of the firebox and the combustible flooring See Figure 7 Figure 5 Mantel Clearances Figure 6 Minimum Clea...

Page 10: ...ht When the firebox is installed directly on carpeting tile or other combustible material other than wood flooring the firebox shall be installed on a metal or wood panel extending the full width and depth of the enclosure LCUF36 A 41 A 411 4 B 44 B 441 2 C 30 C 301 2 D 15 D 151 4 E 71 E 711 2 F 35 F 353 4 G 21 G 21 H 50 H 501 2 A 41 B 44 C 30 D 15 E 71 F 35 G 21 H 50 Figure 8 Corner Installation Fig...

Page 11: ...odate the fireplace with trim installed is as follows Figure 12 Custom Cabinet Figure 13 Location of Nailing Flanges Nail Sides Through Nailing Flanges LCUF36 with trim K 417 8 8 J 357 8 8 LCUF36 with trim 41 35 The fireplace must be installed giving full consideration to the clearance and height requirements identified in this manual WARNING This appliance is approved for the installation of drywall...

Page 12: ...opane L P G heaters in addition to the regulator fitted to the heater to reduce the supply tank pressure to 13 w c maximum Any copper tubing used to supply propane L P G from the tank must be internally tinned Note When connecting propane L P G vent free room heaters you must use pipe sealant resistant to propane L P G Important Hold heater regulator with a wrench to prevent movement when connectin...

Page 13: ...the side frames See Figure 14 2 Align the canopy with the holes in the top frame 3 Replace the screws previously removed 4 Tighten side screws Make sure the canopy is level and secure The firebox canopy must not be modified or replaced with a canopy that may be provided with the unvented decorative room heater WARNING Close fireplace screen panel before operating a decorative type unvented room heat...

Page 14: ...Canopy 1 BRCU36 1 Standard Brass Canopy 1 BRCU36 1 Standard Brass Canopy 1 BRCU36 1 Wide Brass Canopy 1 BRC36 1 Wide Brass Canopy 1 BRC36 1 Wide Brass Canopy 1 BRC36 1 Wide Brass Canopy 1 BRC36 4 Brass Trim Curved Design 1 BRTKM36 4 Brass Trim Curved Design 1 BRTKM36 4 Brass Trim Curved Design 1 BRTKM36 4 Brass Trim Curved Design 1 BRTKM36 4 Pewter Trim Curved Design 1 PWTKM36 4 Pewter Trim Curved...

Page 15: ...26D4721 15 NOTES ...

Page 16: ... in accordance with the installation instructions The Limited Lifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assembly damage by accident neglect misuse abuse alteration negligence of others including the installation thereof by unqualified installers 2 the ...

Reviews: