Monessen Hearth IRVF2T Installation, Operation And Maintanance Manual Download Page 11

C

OMBUSTION

 

AND

  V

ENTILATION

  A

IR

  R

EQUIREMENTS

Warning:  If the area in which
this appliance may be operated
is smaller than that defined as
an unconfined space or if the
building is of unusually tight
construction, provide adequate
combustion and ventilation air
by one of the methods described
in the National Fuel Gas Code,
ANSI Z223.1/NFPA 54, Latest
Edition, Section 5.3 or
applicable local codes.   This
appliance shall not be installed
in a confined space or unusually
tight construction unless
provisions are provided for
adequate combustion and
ventilation air.

Caution:    Because water is a
product of fuel gas combustion,
all gas-fired appliances will
produce some water vapor
(humidity) when fired.  The water
vapor may collect on windows
and walls, especially in
buildings constructed unusually
tight.  Providing additional fresh
air will reduce the amount of
water vapor which collects on
the windows and walls.

9

This heater requires fresh air (oxygen) for proper combustion and
ventilation.  In some cases, but not all, normal air infiltration into a building
will supply a sufficient amount of fresh air for proper combustion and
ventilation.  The number of gas-fired appliances involved, the type of
space being utilized, and the construction tightness of the building
involved must all be considered when determining whether normal air
infiltration is sufficient or if additional fresh air will be needed for proper
combustion and ventilation of the gas-fired appliances installed in a
particular space.

Unconfined space and confined space are the terms used to describe
the space in which gas-fired appliances may be installed.  The National
Fuel Gas Code , ANSI Z223.1/NFPA 54 defines a 

confined space as a

space whose volume is less than 50 cubic feet per 1,000 Btu per hour
(4.8m

 per kW) of the aggregate input rating of all gas-fired appliances

installed in that space, and an 

unconfined space as a space whose

volume is not less than 50 cubic feet per 1,000  Btu per hour (4.8m

 per

kW) of the aggregate input rating of all gas-fired appliances installed in
that space.  Rooms communicating directly with the space in which the
appliances are installed, through openings not furnished with doors,
are considered a part of the to-be-defined space.  For example, three
rooms in a house are adjoining with interconnecting passageways but
no doors; each room has an 8 foot ceiling.  One room is 16 x 12 feet,
one is 12 x 12 feet, and one is 10 x 14 feet.  The total volume of the
three rooms is 3,808 cubic feet; (8 x 16 x 12) plus (8 x 12 x 12) plus (8
x 10 x 14) equals 3,808 cubic feet.  To be considered an unconfined
space in this example, the total maximum aggregate input rating of all
gas-fired appliances installed in the 3,808 cubic feet space must not
exceed 76,160 Btu per hour; (3,808 divided by 50) x 1,000 equals 76,160
Btu per hour.

Normal air infiltration into an unconfined space will be adequate to supply
the necessary fresh air for proper combustion and ventilation if the building
is not constructed unusually tight.  However, if the building is of unusually
tight construction, additional fresh air from outside will be required for
proper combustion and ventilation of the gas-fired appliances installed
in the unconfined space.  Unusually tight construction is defined as
construction where:

a.) Walls and ceiling exposed to the outside atmosphere have a

continuous water vapor retarder with a rating of 1 perm (6 x 10

-11

kg per pa-sec-m˝) or less with openings gasketed or sealed,
and

b.) Weather stripping has been added on openable windows and

doors, and

c.) Caulking or sealants are applied to areas such as joints around

window and door frames, between sole plates and floors, between
wall-ceiling joints, between wall panels, at penetrations for
plumbing, electrical, and gas lines, and at other openings.

53D9012. Rev 1 03/03

Summary of Contents for IRVF2T

Page 1: ...LY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR S PHONE FOLLOW THE GAS SUPPLIER S INSTRUCTIONS IF YOU CANNOT REACH YOUR GAS SUPPLIER CALL THE FIRE DEPARTMENT WARNING IF THE INFORMATION IN THIS MANUAL IS NOT...

Page 2: ...ILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM WITH THE HEATER DO NOT PLACE CLOTHING OR OTHER FLAMMABLE MATERIAL ON OR NEAR THE HEATER ANY SAFETY SCREEN OR GUARD REMOVED FOR SERV...

Page 3: ...s are detected report this to the dealer from whom you purchased the heater and get the deficiency corrected before installing and using the heater Do not install or use a damaged or incomplete heater...

Page 4: ...5 PARTS DIAGRAM 2 8 11 IN WC 555 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 FRONT FRONT RIGHT RIGHT SIDE SIDE LEFT LEFT SIDE SIDE TOP TOP 53D9012 Rev 1 03 03...

Page 5: ...Hearth Plate Assembly Reflector Left Side Pntd Brace Reflector Piezo Cable Cabinet Side Left W Labels Piezo Ignitor Cabinet Top w Caution Label Pilot NAT Gas Pilot LP Gas Venturi Shield Burner Tube A...

Page 6: ...ions of this manual The control system on this heater serves several functions It regulates the incoming gas to the correct pressure for the combustion rate required It will not regulate LP gas direct...

Page 7: ...inches Sides 12 inches on one side of the heater 18 inches on the opposite side of the heater Top 36 inches Front 48 inches 36 MIN 36 MIN SEE NOTE 2 SEE NOTE 2 18 MIN 18 MIN SEE NOTES SEE NOTES 1 2 1...

Page 8: ...the only model that may be installed in a bedroom If an infrared heater is installed in a bedroom it must be wall mounted Floor stand mounted heaters are prohibited in bedrooms FLOOR PROTECTION Some F...

Page 9: ...aded joints of gas piping must be resistant to the action of liquefied petroleum gas Gas piping must be of sufficient size to provide a minimum natural gas pressure at the appliance of 7 inches water...

Page 10: ...AS SUPPLY IN BOTTOM OF HEATER SUPPLY IN BOTTOM OF HEATER FIGURE 3 UNION SHUTOFF VALVE JOIST SEDIMENT TRAP TEE GAS SUPPLY LINE FLOOR NOTE A PLUGGED 1 8 NPT TAP MUST BE LOCATED SOMEWHERE BETWEEN THE SHU...

Page 11: ...put rating of all gas fired appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1 000 Btu per hour 4 8m per kW of the aggregate input...

Page 12: ...ve off carbon monoxide an odorless poisonous gas If this heater shuts off during operation do not relight it until you provide additional fresh air If permanent provisions for providing additional fre...

Page 13: ...e not designed for use with optional blowers These blowers are the only blowers acceptable for use on these heaters The use of any other blower could adversely and dangerously affect the operation of...

Page 14: ...into the wall as shown by Figure 5 USE HAMMER TO DRIVE ANCHOR INTO WALL USE HAMMER TO DRIVE ANCHOR INTO WALL NOTE ANCHORS ARE FOR USE IN HOLLOW NOTE ANCHORS ARE FOR USE IN HOLLOW WALLS WALL AREA BETW...

Page 15: ...of the heater Insert two screws from the bag of fasteners through the holes in the standoffs Tighten the screws into the wall until the heater is firmly secured to the wall See Figure 6 Proceed to St...

Page 16: ...n wall do the following Turn the gas off at the shutoff valve Loosen the four screws which secure the control s mounting bracket Item No 23 of PARTS DIAGRAM found in the upper righthand corner of the...

Page 17: ...CE 21 After all checks are satisfactorily completed as described above turn the heater s control knob to Pilot and reinstall the heater s front panel See Figure 6 22 The heater may now be operated for...

Page 18: ...ntrol knob cl ll not stay lit after several tries turn the gas control knob clockwise to OFF and call your service lier gas supplier ng steadily slowly turn the control knob coun and burning steadily...

Page 19: ...minute a 3 After the pilot is lit continue to hold the control knob down for a minute and then release it The control knob nd then release it The control knob should pop back up fully and the pilot sh...

Page 20: ...stible materials gasoline and other flammable liquids 9 Do take the necessary precautions during any pressure testing of the heater s gas supply piping system 10 Do keep children and mentally impaired...

Page 21: ...CE The pilot gas flow is not adjustable on this heater Proper operation of the ODS Oxygen Depletion Sensitive Pilot Safety System is dependent upon the pilot gas flow rate and any attempt to adjust th...

Page 22: ...their probable cause and solution Any adjustments and or replacements must be performed by a qualified person Do not replace any component with a different type Only use components supplied by the man...

Page 23: ...nsequential damages so the above limitation or exclusion may not apply to you 4 This warranty applies only to the original purchaser and may not be transferred 5 This warranty applies only to a gas he...

Page 24: ...ATTENTION APPLIANCE INSTALLER PLEASE RETURN THESE OPERATING AND INSTALLATION INSTRUCTIONS TO THE APPLIANCE FOR CONSUMER USE 53D9012 REV 1 03 03...

Reviews: