FIG 1
F. WATER PRESSURE TEST
• It is IMPORTANT that a pressure check is carried out.
• Low and high pressure can result in either damage to, or failure of the unit.
• If daytime static water pressure* exceeds 3.5 bar (50psi) a 5 bar pressure limiter
should be fitted. *50psi daytime pressure can reach nearly 100psi at night!
• Minimum dynamic pressure must exceed 1.5 bar.
• If in any doubt please call us on
01986 784 759
4
H. INLET & OUTLET CONNECTIONS – See Fig 1
Under no circumstances use washing machine hoses or plumb the unit in solid
copper pipe. Ensure nipples (when used) have been tightened to seal.
G. INSTALL BYPASS VALVES & CHECK VALVE
Form an installation as per Fig 1 Below.
Checklist
✔
Water pressure 1.5 – 5 bar (20 – 70psi)
✔
Access for maintenance