6. Cable Dressing 

 

6a. Install cable management tray to panel. 

 

6b. Press cables neatly on cable 

management tray and secure with cable 
ties or Velcro strips ensuring 29 mm 
bend radius is maintained. 

 

6c. Individually earth each panel to cabinet 

earth position. 

 

 

7. Attach MIIM I/O cable to I/O port 

 

Secure to cable management tray if desired. 

 

 

 
 
 
 
 
 
 
 

Fig.6 

 

8.  RemovalInstructions 

To remove rear housing, open clamp and 
pull up on latch on top of the housing. 
 

Note

: Use flat screwdriver to 

Lift latch of housing. 

 

 

Fig.8 

 
 

 
 

Fig.7 

 
 
 
 
 
 
 

9.  Adding MIIM panels to the MIIM System 

 

Connect a patch cord between the RJ45 port 
on the back of the panel to a port on a MIIM 
scanner. 
 
Refer to the scanner and panel firmware 
update section in the MIIM Installation Guide 
to insure the panel firmware and scanner 
application are matched correctly. 
 
Access the scanner to confirm scanner 
application and panel firmware versions. 
 
If necessary, perform a panel firmware 
update on the panel. 
 

MPN NO.

 

SAP NO.

 

215-390

 

187000372

 

Summary of Contents for PID-00231

Page 1: ...DOC INSTALLATION INSTRUCTIONS PID 00231 PANEL PARTS LIST Panel with Integrated Cable Manager Hardware Kit Rear Housing Assembly Stuffer Caps Labels Instruction Sheet GENERAL REQUIREMENTS The following tools are required for installation of the panel 110 termination tool set on low impact Flush cut pliers Cable stripping tool Phillips screwdriver ASSEMBLY INSTRUCTIONS 1 Panel Preparation 1a Remove ...

Page 2: ...a minimum of 40mm Fig 1 2 Remove foil from three pairs and untwist pairs Fig 2 3 Use clippers to cut off foil Fig 3 4 Pull the foil shield back from the forth pair over the jacket Ensure the cable foil s conductive surface is facing out Wrap the drain wire around the foil shield Fig 4 2b F UTP 1 Strip the cable a minimum of 40mm Fig 1 2 Untwist pairs and remove cable separator with wire clippers F...

Page 3: ...Huber TEMPLATE FILENAME APPLICATION_SPEC SIZE_A V 1 DOC 3 Cable Termination 3a Untwist wires and position for terminating 3b Position cable to align each pair with corresponding color code Ensure cable sheath is maintained up to the jack 3c Punch down with110 tool 4 Stuffer Cap Install stuffer cap 3 c Fig 4 Fig 3a Fig 3b Fig 3c 5 Fitting Rear Housing Attach housing and close cable clamp Clamp must...

Page 4: ...h each panel to cabinet earth position 7 Attach MIIM I O cable to I O port Secure to cable management tray if desired Fig 6 8 RemovalInstructions To remove rear housing open clamp and pull up on latch on top of the housing Note Use flat screwdriver to Lift latch of housing Fig 8 Fig 7 9 Adding MIIM panels to the MIIM System Connect a patch cord between the RJ45 port on the back of the panel to a p...

Reviews: