                                                                                                                                                                                                                                                                                                                   SHEET No. 

2

 of 

2

 

  

             

  

Fig. 2     

 

 

 

 

Fig. 3 

Install E-module in patch panel: 

Install E-module in the slot below the contacts on the bezel (see Fig. 2). Rotate locking bar up  
and insert E-module until contacts on the E-module are no longer visible (see Fig.3). Rotate  
locking bar down to secure E-module. The locking bar should be in contact with the panel.    
The E-module (or MIIM Continuity Boards) is required to maintain continuity on the permanent  
link.  FAILURE TO INSTALL THE E-MODULE WILL RESULT IN OPEN PAIRS. 

 

   

 

                           

 

 

   

   

 

 

Fig. 4   

 

 

 

 

Fig. 5 

   

  Connect panel to scanner:

 

 

Connect MIIM panel to MIIM Scanner with a Category 5e or better patch cord (see Fig. 4).  The  
panel is powered by the scanner and will automatically turn on. Power is indicated by the Stat B  
LED on the front of the panel. 

 

 

 

 

 

 

 

Remove E-Module: 

 

1.  Lift locking bar up and rotate locking bar toward the front of the panel to disengage the E-module 

from the panel (see Fig. 5). 

2.  Remove E-module. 
3.  Install replacement E-module or MIIM continuity boards. 

LOCKING BAR 

CONNECT 

PATCH CORD 
TO SCANNER 