PICTURE 1
Terminal Connections
INSTALLATION DATA SHEET
LED201/200 Series
Carefully twist lens firmly one turn clockwise to remove from base. Remove 3 x No:4 screws
from LED mounting plate that fix plate to internal lugs in the base. Fix base to the required
surface, utilising rubber gasket, with 2 x M4 screws (not supplied). Insert power cable through
aperture in base & connect to the 4 way terminal on the PCB. ‘see picture 1’. Position the base of the
LED array over the internal base lugs & fix in place with 3 x No:4 screws.
LED401/400 Series
Connection to this type of unit is either into the three way barrier strip situated in the base of the
unit (standard connection) or via the M20 side conduit entry. If M20 is preferred method then two
wires in the barrier strip in the base need to be unscrewed and freed from the barrier strip. Un-screw
3 x No:4 screws that retain the base plate & carefully remove, threading the wires through the aperture.
Un-screw the same two wires from the internal terminal block. Carefully drill out the M20 entry &
using the appropriate cable gland, insert power cable into unit connecting to the internal terminal block.
Screw base plate back into position. Fix base to the required surface using the supplied gasket with
3 x M6 Hex set screws (not supplied).
Alarm Stages (Modes of Operation)
These are selected by a two way dip switch on the lens side of the PCB at installation.
The operational mode is factory pre-set to FLASH.
Replace lens onto base ensuring that the base spigot ‘O’ ring is in place. Twist lens one turn
anti-clockwise to lock & check that the ‘O’ ring is positioned correctly & not caught or snagged.
General Installation Notes
• Installation must be carried out in accordance with the latest codes of practice by
a qualified electrician.
• Ensure power is disconnected prior to installation or maintenance to avoid electrical shock.
• Environmental exposure conditions during installation should be dry, not moist or wet.
• The lens of the unit is polycarbonate plastic. Do not clean with petroleum based cleaners.
• To maintain the IP65 weatherproof rating the beacon must be mounted with
the lens above the base.
• Avoid mounting the beacon where it will be subject to excessive vibration.
LED201/200 Series
LED401/400 Series
ON
1 2
STEADY
1 BAR ROTATING
FLASH
2 BAR ROTATING
SWITCH
POSITION
ON
ON
ON
1 2
1 2
1 2
+V (L) Power In Ov (N)