04/03 AWB2725-1452GB
Digital input/output modules
41
Digital input/output modules
Configuration and programming of the digital inputs/
outputs
The module has 16 connections. The first 12 connections (0 to 11)
can be used as inputs and outputs, the connections 12 to 15 can
only be used as inputs,
The configuration of the module is performed in the "PLC Confi-
guration" register. An "Empty slot" is inserted with
"Set element". The following appears, for example:
h
Important!
The operating voltages for the inputs and outputs must
come from the same source as those for the module.
Type
XIOC-16DX
Inputs
Input type
DC input
Number of input channels
16 (0 to 15)
Input voltage
24 V DC
Range
20.4 to 28.8 V DC
Input resistance
5.6 k
O
Input current
Typ. 4 mA
Voltage level
ON
f
15V
OFF
F
5V
Input signal delay
OFF
l
ON
typ. 100
m
s
ON
l
OFF
typ. 1 ms
Electrical isolation
Between inputs and the I/O bus
Through optocouplers
Input indication
By LED (green)
Outputs
Output type
Transistor (source type)
Number of output channels
12 (0 to 11)
Output voltage
24 V DC
Residual current for a “0” signal
approx. 140 µA
Rated current
for “1” signal
0.5 A DC at 24 V DC
Lamp load
4 W, without series resistor
Simultaneity factor g
1
Relative ON time (duty cycle)
100 %
Limiting of switch-off voltage
For inductive loads
yes, –21 V (for U
N
= 24 V DC)
Switching repetition rate (actions
per hour)
For time constant t
≤
72 ms
3600 (G = 1)
Parallel wiring capability of
outputs
in groups 0 – 3, 4 – 7, 8 – 11.
Actuation of the outputs within a
group only in the same program
cycle.
Number of outputs
max. 3
Maximum total current
2A per group
Minimum total current
250 mA
Output signal delay
typ. 100 µs
Overvoltage protection
Diode
Electrical isolation
Between outputs and the I/O
bus
Through optocouplers
Short-circuit-protection
yes
Short-circuit-detection threshold
max. 1.2 A for 3 ms per output
Output indication
By LED (green)
General
External connection
Plug-in terminal block
Internal current consumption
(5 V DC)
Typ. 50 mA
External supply voltage
1)
24 V DC,
Weight
0.16 kg
1) Important! With UL-conform applications the supply cables must
have a cross-section of AWG16 (1.3 mm
2
).
Figure 49:
Terminal assignments for module XIOC-16DX
Type
XIOC-16DX
24 V
H
0 V
H
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
---XIOC-16DX[SLOT
---AT%IW6:WORD;(*Inputs/Outputs*) [CHANNEL (I)]
---AT%QW2:WORD;(*Outputs/Inputs*) [CHANNEL (I)]
For Immediate Delivery call KMParts.com at (866) 595-9616
Summary of Contents for XIOC
Page 4: ...II For Immediate Delivery call KMParts com at 866 595 9616...
Page 8: ...04 03 AWB2725 1452GB 4 For Immediate Delivery call KMParts com at 866 595 9616...
Page 24: ...04 03 AWB2725 1452GB 20 For Immediate Delivery call KMParts com at 866 595 9616...
Page 52: ...04 03 AWB2725 1452GB 48 For Immediate Delivery call KMParts com at 866 595 9616...