07/04 AWB2700-1428GB
37
4 Functions of the Operator Module
This chapter describes the use of the operator module to operate
the controller. The start-up example is used to explain the
individual functions.
The texts in the display (German) are presented without umlaut
symbols, e.g. ü
r
UE.
Initial PLC startup
When the power supply is switched on, the UPS device closes the
Power Fail circuit. The PLC operating system is started and the
STARTING CONTROLLER message appears on the display of the
operating module. The STOP, RUN and SF (SF = Central error) LEDs
of the operator module are not lit up. The STOP LED lights up and
the SF LED light up after a few seconds.
If there is no program in the PLC, and the operating mode selector
switch (OMS) is set to STOP, the display will show the following
information after a few seconds:
The STOP and SF LEDs are lit. When the SF LED is lit, this indicates
that the PLC did not find a bootable program during startup. The
! in the display indicates that the PLC is in STOP status.
First of all, clear the messages:
X
Choose menu item MAIN MENU
r
DIAGNOSTICS
r
CLEAR.
This will display the CLEAR menu.
X
Instead of No, select Yes by turning the MSS.
X
Press the MSS.
X
Press the MSS once more after ENTER is displayed.
The SF LED will go out and the exclamation mark will be cleared.
X
Return to the basic menu.
You can now load a program into the PLC using XSoft or select the
main menu using the menu selector switch.
X
Press the MSS when the cursor flashes in front of the MAIN
MENU menu item.
Your are now in the main menu and can select the individual menu
items.
Loading the program into the PLC
You can transfer a compiled program such as the program
TESTPRO from the PC to the PLC.
Requirement: The OMS must be set to STOP or RUN-P.
X
Choose Online
r
Login in the XSoft programming software.
If there is no program in the PLC, the following window will
appear:
X
Click on Yes.
This will confirm the storing of a bootable version of the program
in the working memory. The display will change:
If there is already a program in the working memory, it will be
overwritten after the confirmation.
X
Click on Yes. The program name will change in the display.
h
The basic operating principles of the PLC are described in
the Chapter “Menu overview of the operator module” on
page 45.
Time, event message, OMS position
PLC status (irrespective of OMS)
Program content (no program in PLC)
Menu entry
! = indicates an event
S = STOP (event)
17:10:37 !S
STOP
PROG: ???
>MAIN MENU
Abbildung 65:Loading a new program
Abbildung 66:Loading new program when the old one was present
17:29:23
!S
STOP
TESTPRO.PRO
>MAIN MENU