Motor starter RA-MO
(from Version 3.0)
01/08 AWB2190-1430GB
80
Table 12: Function of jumper settings
Setting current values (pins 1 to 4)
The current values can be set with pins 1 to 4 of the DIP switch:
Table 13: Setting of the current with DIP switch
Configuration overview (pins 5 to 8)
Jumper left
Jumper bottom
Jumper right
Monitoring of motor plug
(= thermistor monitoring)
1)
Supply voltage, contactors
Starter type
open (default)
closed
left
right
left
right
Part of group error message
Part of Ready message
24 V DC
400 V AC
Reversing
starters
DOL Starters
1)
section “Set plug monitoring as part of Ready message” on page 79.
h
Caution!
Do not change the Jumper bottom and Jumper right
settings.
1
1
1
1
No function (factory setting)
1)
1
0
1
1
0.3 A
0
1
1
1
0.4 A
1
0
0
0
0.6 A
0
1
0
0
0.8 A
1
1
0
0
1.0 A
0
0
1
0
1.2 A
1
0
1
0
1.5 A
0
1
1
0
1.7 A
1
1
1
0
1.9 A
0
0
0
1
2.1 A
1
0
0
1
2.6 A
0
1
0
1
3.6 A
1
1
0
1
5.0 A
0
0
1
1
6.6 A
0
0
0
0
No function
1)
1) RA-MO can not be operated. The red LED in the motor symbol
is lit. A group error is active.
1
ON
DIP
2
3
4
5
6
7
8
1
0
Figure 86: Configuring the RA-MO…W…
Figure 87: Configuring the RA-MO…D…
I3, I4
0
I3, I4
1
I3, I4
⇒
ASi
0
0
I3, I4
⇒
ASi, AUTO: I3
⇒
FWD + REV
1
0
I3, I4
⇒
ASi,
AUTO: I3
⇒
FWD, I4
⇒
REV
0
1
I3, I4
⇒
ASi,
AUTO & HAND: I3
⇒
FWD, I4
⇒
REV
1
1
L1
⇒
T1, L3
⇒
T3
0
L1
⇒
T3, L3
⇒
T1
1
1
ON
DIP
2
3
4
5
6
7
8
1
0
I3, I4
0
I3, I4
1
I3, I4
⇒
ASi
0
0
I3, I4
⇒
ASi,
AUTO & HAND: I3 + I4
⇒
FWD
1
0
I3, I4
⇒
ASi, AUTO: I3
⇒
FWD
0
1
I3, I4
⇒
ASi,
AUTO & HAND: I3
⇒
FWD
1
1
Factory setting
0
nvalid setting
1
1
ON
DIP
2
3
4
5
6
7
8
1
0
Summary of Contents for Rapid Link
Page 10: ...01 08 AWB2190 1430GB 6 ...
Page 40: ...01 08 AWB2190 1430GB 36 ...
Page 48: ...01 08 AWB2190 1430GB 44 ...
Page 70: ...01 08 AWB2190 1430GB 66 ...
Page 146: ...01 08 AWB2190 1430GB 142 ...
Page 162: ...01 08 AWB2190 1430GB 158 ...