- 13 -
2.3
Display Module MB6001F-110
The display module MB6001F-110 has to be mounted in such a way,
that it is clearly visible and easily accessible. Its function is to indicate:
•
operational messages and fault signals;
•
Load current and the generated voltage.
The power generating system is being turned on and off from here.
Display and operation elements
H1
I/O
status message
- LED (green)
lights up, when the device is ready for
operation
H2
U >
fault alarm
LED (red)
lights up if overvoltage is > 150V
blinks if undervoltage is < 90V
H3
I >
fault alarm
LED (red)
lights up if overvoltage is > 90 A
H5
Syst
fault alarm
LED (red)
lights up if there is a
fault in the system,
fault in the control electronics,
dead short circuit or overheating
H6
Earth fault
fault alarm
LED (red)
lights up if there is an earth-fault
(see 2.4.1)
H7
%
Load indication
indicates the load current, which is
presently used
H8
V
Voltage indication
indicates the output voltage
S1
a/b
ON
OFF
On/off switch
starts the system
S2
TEST
Test button
button to test the insulation
monitoring function
H1
H2
H3
H5
H6
H7
H8
S1a
S1b
S2