6
4. EXTENDED OPTIONS
To program the Mobeye PowerGuard, the GSM module must have network connection. The
configuration is programmed by SMS messages.
All settings are stored and will be kept in the unit, even in case the power supplies are removed.
4.1 PROGRAM MODE
As long as the Mobeye PowerGuard has external power supply, it has GSM network connection.
The module is ready to receive SMS commands. In case the Mobeye PowerGuard has no
external power supply but is fed by batteries, the module enters the program mode directly after
placing the batteries. During the time the module searches GSM network connection the LED
flashes 2 sec. on/1 sec. off. Within 10-30 seconds the connection is established and the status
LED starts flashing 1 sec. on/1 sec. on
(or ‘off’ in case the first telephone number has not been
configured).
The Mobeye PowerGuard (just fed by batteries) returns to the program mode by pressing the
on/off button during 5 seconds, until the LED starts flashing (or turns to ‘on’).
4.2 THE SECURITY CODE
For configuration activities the security code of the Mobeye PowerGuard must be used. The initial
security code is
‘1111’.
In this manual this code is referred to as <CODE>.
4.3 PROGRAMMING THE SETTINGS BY SMS
The settings are programmed by SMS text messages.
- Be sure the PowerGuard is in program mode (please refer to 4.1).
- Send an SMS message with following content:
<CODE> <command>
- Do not forget the space character between <PIN code> and <command>.
- The commands are case sensitive.
- Several commands may be combined in one SMS message (with a maximum of 160
characters) by placing a # between the commands.
<CODE> <command1>#<command2> ...... #<commandN>
The green LED blinks 3 times to indicate the successful configuration. In case of an incorrect
command, the LED flashes 5 times.
In 4.6 the complete scheme with SMS commands is listed
4.4 POSSIBLE GENERAL SETTINGS
This paragraph describes the general settings for the PowerGuard.
4.4.1 Phone numbers
The Mobeye PowerGuard is able to send alarm messages up to 5 phone numbers. The first
telephone number (TEL1) belongs to the administrator. Only this number receives all system
messages. The other phone numbers (including the administrator) only get the alarm messages.
To set or change telephone numbers:
SMS command 1
st
telephone number:
<CODE> TEL1:<telephone number>
SMS command 2
nd
telephone number:
<CODE> TEL2:<telephone number>
.... similar for TEL3...TEL5