Mobeye PowerGuard CM2100 User Manual Download Page 8

 

4. EXTENDED OPTIONS 

To program the Mobeye PowerGuard, the GSM module must have network connection. The 
configuration is programmed by SMS messages. 
All settings are stored and will be kept in the unit, even in case the power supplies are removed.  

4.1 PROGRAM MODE 

As long as the Mobeye PowerGuard has external power supply, it has GSM network connection. 
The module is ready to receive SMS commands. In case the Mobeye PowerGuard has no 
external power supply but is fed by batteries, the module enters the program mode directly after 
placing the batteries. During the time the module searches GSM network connection the LED 
flashes 2 sec. on/1 sec. off. Within 10-30 seconds the connection is established and the status 
LED starts flashing 1 sec. on/1 sec. on 

(or ‘off’ in case the first telephone number has not been 

configured). 
The Mobeye PowerGuard (just fed by batteries) returns to the program mode by pressing the 
on/off button during 5 seconds, until the LED starts flashing (or turns to ‘on’).  

4.2 THE SECURITY CODE 

For configuration activities the security code of the Mobeye PowerGuard must be used. The initial 
security code is 

‘1111’. 

 
In this manual this code is referred to as <CODE>. 

4.3 PROGRAMMING THE SETTINGS BY SMS 

The settings are programmed by SMS text messages.  
-  Be sure the PowerGuard is in program mode (please refer to 4.1). 
-  Send an SMS message with following content: 
 

<CODE> <command>

 

 
-  Do not forget the space character between <PIN code> and <command>. 
-  The commands are case sensitive. 
-  Several commands may be combined in one SMS message (with a maximum of 160 

characters) by placing a # between the commands. 

 
<CODE> <command1>#<command2> ...... #<commandN>

 

 
The green LED blinks 3 times to indicate the successful configuration. In case of an incorrect 
command, the LED flashes 5 times.  
 

In 4.6 the complete scheme with SMS commands is listed 

4.4 POSSIBLE GENERAL SETTINGS 

This paragraph describes the general settings for the PowerGuard.  

4.4.1 Phone numbers 

The Mobeye PowerGuard is able to send alarm messages up to 5 phone numbers. The first 
telephone number (TEL1) belongs to the administrator. Only this number receives all system 
messages. The other phone numbers (including the administrator) only get the alarm messages.  
 
To set or change telephone numbers: 
SMS command 1

st

  telephone number: 

<CODE> TEL1:<telephone number> 

SMS command 2

nd

  telephone number:

<CODE> TEL2:<telephone number> 

.... similar for TEL3...TEL5 
 

Summary of Contents for PowerGuard CM2100

Page 1: ...USER MANUAL Mobeye PowerGuard CM2100 SW version 1 n...

Page 2: ...from moisture heat and water splashing The guidelines for the battery usage must be regarded Do not expose the device to strong vibrations Do not let it fall from height Do not use in an environment w...

Page 3: ...ossible General settings 6 4 4 1 Phone numbers 6 4 4 2 Identification text 7 4 4 3 Alarm text 7 4 4 4 Alarm notification type SMS or SMS call 7 4 4 5 Power failure delay time 7 4 4 6 Input type 7 4 4...

Page 4: ...rammed The SMS message contains the text Mobeye Power failure In case the power is restored the Mobeye PowerGuard sends a power restored SMS text message to the phone numbers as programmed In case one...

Page 5: ...hould be programmed 2 3 CONNECT THE UNIT TO THE EXTERNAL POWER SUPPLY Connect the external power adapter or any other regulated 12VDC power supply to the power input of the connector V black lead with...

Page 6: ...o switch off disarm the Mobeye PowerGuard Press the on off button at the upper side for 1 second The green LED switches off to indicate the armed status In order to switch on arm the Mobeye PowerGuard...

Page 7: ...nput 1 It does not matter which wire is connected to which connector If necessary the wires can be extended up to 5 meters using appropriate wire material When using a second input connect this to inp...

Page 8: ...be used The initial security code is 1111 In this manual this code is referred to as CODE 4 3 PROGRAMMING THE SETTINGS BY SMS The settings are programmed by SMS text messages Be sure the PowerGuard i...

Page 9: ...ult behaviour after a power failure or an activated input the Mobeye PowerGuard notifies by SMS text message followed by a telephone call beep signal The combination of SMS text and the call increases...

Page 10: ...size the urgency of the alarm messages all alarms can be repeated As long as the alarm status has not returned to the inactive status the SMS alarm will be repeated after the alarm repeat time The tim...

Page 11: ...NO Input type input 2 TYPEIN2 type NO NC NO Delay on input 1 DELAY1 sec 0 999 sec 1 Delay on input 2 DELAY2 sec 0 999 sec 1 Inactive time input 1 INACTIVEIN1 min 0 60 min 0 Inactive time input 2 INAC...

Page 12: ...The status message includes the ARMED NOT CONFIGURED status the status of the inputs and the status of the power and batteries 5 2 OVERVIEW GENERAL SETTINGS The general settings of the Mobeye PowerGu...

Page 13: ...removed Status feedback Status LED pattern Required action Module not configured Blinking 1 second on 1 second off Configure at least one telephone number Module is switched on powered by batteries 1...

Page 14: ...x ca 500 mA Dimensions 80 x 60 x 40 mm Ambient temperature 10 C until 50 C This manual is published by Mobeye All rights the translation included are reserved Any reproduction either photocopy microfi...