5  Walk test appointed to coverage area

1. Set detector to test mode for walking test. According to surrounding, pulse counts 1,
    2 or 3 for option. 

2.  

3 .Testing in different direction to confirm the two boundaries of the coverage,  ensure
    the detector is  appointed  to the central desired  area.

4.T

5.

Horizontal movement which triggers detector alarming at the remote of the detection

     coverage  at the  speed of 0.75m/s ,  the LED  indicator will  light  several seconds. 

he centre of detection area should not be towards vertical incline. If can  not obtain 

    an ideal detection area , please adjust  the vertical angle to ensure direction for detector 
    neither high nor low. 

Attention: Once detection angle is adjusted,  walking test must be performed again.

6. Please set detector to normal mode after finishing walking test.

 

2

4.2   Introduce DIP function:

Three work modes to be set:

Test mode: Detector alarms once being triggered, no
time interval between two alarm emissions. This mode
is used  for walking test.

Normal mode: Detector probes one time each interval
2.5min, sends supervision signal which reports status
of the detector and battery each interval 65min.

Enroll mode:  Sends identity  code  to  receiver  after 
pressing tamper key over 3 seconds.

Refer to follow form to set each mode:
     

DIP3

DIP4

MODE

ON        

OFF     

TEST  MODE

OFF       

ON              NORMAL  MODE  

OFF       

OFF            ENROLL  MODE     

Three types of pulse for option:

One pulse: Detect or alarms once detecting one pulse.
Two pulses: Detector alarms once detecting two pulses.
Three pulses: Detector alarms once detecting three
pulses.(Default)
The more pulse counts, the lower performance for 
sensitivity of capture. But more pulse counts can reduce
false alarms. 

DIP1

DIP2

MODE

ON         OFF      ONE PULSE 

OFF         ON

TWO PULSES 

OFF

OFF

 THREE PULSES 

Press the tamper switch
for study the ID code
 

Set detector to enroll mode and then insert one lithium battery
into detector. LED will start up for lighting for several seconds.
Detector will send the identity signal to receiver after pressing
tamper key over 3 seconds. If panel receives this identity 
signal, it will have corresponding sound for hinting enrollment
is successful. Please refer to manual of panel to know how 
to make panel to ready for studying detector.

 

4.3 Enrollment of the detector to the system

4.4 Replace lithium battery

It means low battery of detector under the condition that LED
light flashes when detector emits signal each time. Meantime,
It also will send signal of low battery to receiver.
Refer to follow pictures to change one new battery:  

Insert one new battery

3

2

1

4

DIP

ON