5 Walk test appointed to coverage area
1. Set detector to test mode for walking test. According to surrounding, pulse counts 1,
2 or 3 for option.
2.
3 .Testing in different direction to confirm the two boundaries of the coverage, ensure
the detector is appointed to the central desired area.
4.T
5.
Horizontal movement which triggers detector alarming at the remote of the detection
coverage at the speed of 0.75m/s , the LED indicator will light several seconds.
he centre of detection area should not be towards vertical incline. If can not obtain
an ideal detection area , please adjust the vertical angle to ensure direction for detector
neither high nor low.
Attention: Once detection angle is adjusted, walking test must be performed again.
6. Please set detector to normal mode after finishing walking test.
2
4.2 Introduce DIP function:
Three work modes to be set:
Test mode: Detector alarms once being triggered, no
time interval between two alarm emissions. This mode
is used for walking test.
Normal mode: Detector probes one time each interval
2.5min, sends supervision signal which reports status
of the detector and battery each interval 65min.
Enroll mode: Sends identity code to receiver after
pressing tamper key over 3 seconds.
Refer to follow form to set each mode:
DIP3
DIP4
MODE
ON
OFF
TEST MODE
OFF
ON NORMAL MODE
OFF
OFF ENROLL MODE
Three types of pulse for option:
One pulse: Detect or alarms once detecting one pulse.
Two pulses: Detector alarms once detecting two pulses.
Three pulses: Detector alarms once detecting three
pulses.(Default)
The more pulse counts, the lower performance for
sensitivity of capture. But more pulse counts can reduce
false alarms.
DIP1
DIP2
MODE
ON OFF ONE PULSE
OFF ON
TWO PULSES
OFF
OFF
THREE PULSES
Press the tamper switch
for study the ID code
Set detector to enroll mode and then insert one lithium battery
into detector. LED will start up for lighting for several seconds.
Detector will send the identity signal to receiver after pressing
tamper key over 3 seconds. If panel receives this identity
signal, it will have corresponding sound for hinting enrollment
is successful. Please refer to manual of panel to know how
to make panel to ready for studying detector.
4.3 Enrollment of the detector to the system
4.4 Replace lithium battery
It means low battery of detector under the condition that LED
light flashes when detector emits signal each time. Meantime,
It also will send signal of low battery to receiver.
Refer to follow pictures to change one new battery:
Insert one new battery
3
2
1
4
DIP
ON