ML Accessories SHE1BEM Installation & Maintenance Manual Download Page 2

These instructions should be read carefully and retained after installation by the end user for 
future reference and maintenance.
These instructions should be used to aid installation of the following products:
SHE1BEM / SHE1GEM / SHE2BEM / SHE2GEM

GENERAL INSTRUCTIONS

• This product must be installed in accordance with the latest edition of the IEE Wiring Regulations (BS7671) 

and current Building Regulations. If in any doubt, consult a qualified electrician

• Please isolate mains prior to installation or maintenance
• Check the total load on the circuit (including when this luminaire is fitted) does not exceed the rating of the 

circuit cable, fuse, or circuit breaker

• Please note the IP (Ingress Protection) rating of this product when deciding the location for installation
• This product is Class I and must be earthed
• This product is IP65 rated

SAFETY

INSTALLATION

Note - If this luminaire is being used in conjunction with an external PIR or sensor, please confirm with the
manufacturer of the sensors that they are compatible with LED luminaires.
• Provide power to the required point of installation (refer to BS7671 for correct cabling methods). Suitable IP 

rated junction boxes should be used where required

• Remove the diffuser by unscrewing the four hex screws at the front of the diffuser
• Using the baseplate as a template, mark the location for, and drill the fixing holes ensuring not to infringe with 

any gas/water pipes or electrical cables 

• Feed the mains cable through the rubber grommet to retain IP rating, and secure the baseplate to the surface
• Ensuring correct polarity is observed, carefully wire as shown (Fig. 1) for non-maintained operation, maintained 

operation (Fig. 2) or switched-maintained operation (Fig. 3)

Summary of Contents for SHE1BEM

Page 1: ...INSTALLATION MAINTENANCE MANUAL SHE1BEM SHE1GEM SHE2BEM SHE2GEM ...

Page 2: ...nstallation This product is Class I and must be earthed This product is IP65 rated SAFETY INSTALLATION Note If this luminaire is being used in conjunction with an external PIR or sensor please confirm with the manufacturer of the sensors that they are compatible with LED luminaires Provide power to the required point of installation refer to BS7671 for correct cabling methods Suitable IP rated jun...

Page 3: ...Fig 3 Fig 2 Fig 1 ...

Page 4: ...end on commissioning the installation a minimum charge period of 24 hours before carrying out an emergency duration test h lead on the LED plate is secured correctly to the earth lead on the body of the fitting to the body uired colour temperature by means of the three position switch see Fig 2 WARNING This product must be disconnected from the circuit if subjected to any high voltage or insulatio...

Page 5: ...use aggressive cleaning products or solvents which may damage the product This product is non dimmable This product should be dismantled for disposal when it reaches the end of its life Please see website for dismantling instructions This product should be recycled in the correct manner when it reaches the end of its life Check local authorities for where facilities exist The batteries in this lum...

Page 6: ...fected ML Accessories reserve the right to alter product specification without prior notice Recommended routine test procedure in accordance with BS5266 Daily check check LED charge indicator is illuminated Monthly functional test simulate a mains supply failure for approx 30 seconds by operation of key switch or switching off circuit breaker Ensure normal supply is restored after test and ensure ...

Page 7: ...sheet ...

Page 8: ...AVOCT21_V2 ML Accessories Limited LU5 4LT www mlaccessories co uk 134 INTERNATIONAL CONTACT DETAILS INTERNAT CONTACT D 20 C 50 C TA ...

Reviews: