ML Accessories OP7N Installation & Maintenance Manual Download Page 4

The backbox has drain hole drilling guides marked (see Fig. 2). Drilling a drain hole is 
advised if the unit is installed in a location subject to temperature fluctuations where  
build-up of condensation may occur. It is not advised if the unit will be subject to spray 
or jets, as drilling a drain hole will reduce the IP rating. A 3-5mm hole can be drilled at 
the bottom back edge of the enclosure where marked. If wiring in conduit to the bottom 
entry, then the drain hole should be drilled at the lowest point of the conduit run not in the 
backbox

Fig. 2

Fig. 2 

(OP7N shown) 

 

Remove one or more of the pre-fitted blank plugs as required by pushing out from the inside and install 

a suitable IP rated gland or adaptor (not supplied). For rear entry, cut or drill a 20/25mm hole where 

marked and install a suitable IP rated grommet (not supplied). Unused cable entries must have the 

blank plugs fitted 

 

Feed the mains cable into the unit and secure the base plate to the surface. The fixing holes are 

slotted to allow some rotational adjustment 

 

Replace the gasket onto the backbox, then wire as shown in Fig. 3 ensuring that correct polarity is 

observed: L - Live (brown), E - Earth (green/yellow), N - Neutral (blue)  

 

 

Fig. 3      OP7N  

          OP9N 

 

An earth connection must be made to the earth terminal of the socket. Use green/yellow sleeving on 

earth conductors that are not insulated. The earth terminal in the backbox is provided for convenience 

and does not need to be connected 

 

Check all electrical connections are secure with no loose strands of cable 

 

Ensuring the gasket does not become damaged or pinched, fit the socket assembly onto the backbox, 

taking care not to compress, damage or trap any cables, and secure with the screws provided - do not 

overtighten 

 

Fit screw covers 

 

Switch on and check for correct operation 

For security, and to prevent unwanted tampering with the product, a lug feature with a 6mm hole is provided to 

accept a padlock or similar locking security device (see Fig. 4). 

Summary of Contents for OP7N

Page 1: ...INSTALLATION MAINTENANCE MANUAL OP7N OP9N...

Page 2: ...BS7671 and current Building Regulations If in any doubt consult a qualified electrician Please isolate mains prior to installation or maintenance Check the total load on the circuit including when thi...

Page 3: ...uct is Class I and must be earthed his product is IP66 rated ATION te the unit should be fixed to a rigid flat surface as unevenness could cause damage to the produ ration Provide power to the require...

Page 4: ...illed at the lowest point of the conduit run not in the backbox Fig 2 Fig 2 OP7N shown Remove one or more of the pre fitted blank plugs as required by pushing out from the inside an a suitable IP rate...

Page 5: ...g on earth conductors that are not insulated The earth terminal in the backbox is provided for convenience and does not need to be connected Check all electrical connections are secure with no loose s...

Page 6: ...ed Check all electrical connections are secure with no loose strands of cable Ensuring the gasket does not become damaged or pinched fit the socket assembly onto the backbox taking care not to compres...

Page 7: ...which may damage the product If it is necessary to clean inside the cover use a soft dry cloth only Do not use any source of high pressure washers to maintain or clean this product WARNING To ensure...

Page 8: ...l of the batch code will invalidate the warranty If this product should fail within its warranty period it should be returned to the place of purchase for a free of charge replacement ML Accessories d...

Reviews: