background image

16

MK Electric Limited

The Arnold Centre, Paycocke Road,
Basildon, Essex SS14 3EA

Telephone: 01268 563000 (National)

Fax:

01268 563563 (UK Sales)
+44 (0) 1268 563360 (International)

Email:

[email protected]

Web site:

www.mkelectric.co.uk

RCBO

tripped / off

NO

Can

RCBO be

switched on

again?

Switch off or disconnect all loads and/or appliances

protected by the RCBO.  Inspect all items that were

connected to the RCBO circuit and do not

re-connect any items which show obvious signs of

being faulty (unusual visual signs or smell of

overheating or other faults).

Call a qualified Electrician to investigate further.

YES

Can

RCBO be

switched on

again?

Check RCBO

operation with

test button

Transient

Fault

If tripping 

re-occurs seek 

expert attention

Expert attention

is needed to

correct fault

Check RCBO

is correctly

connected

Can

RCBO be

switched on

again?

Check RCBO

operation with

test button

Check RCBO

operation with

test button

Does RCBO

trip?

Fault rectified

by wiring

correction

Can

RCBO be

switched on

again?

Switch on or 

reconnect loads

or appliances

one-by-one

until RCBO

trips off

This load or

appliance is 

faulty.  Expert

attention is 

needed to 

correct fault

Disconnect the

RCBO from the

circuit it is

protecting

(Load side only)

There is a 

fault within the

load circuit.

Expert attention

needed to

correct fault

Switch off.

Do not use.

Contact MK

Technical Sales

Services

Switch off

RCBO. 

Do not use.

Contact MK

Technical Sales

Services

YES

NO

YES

YES

NO

NO

NO

YES

9

10

1. Choose and install a suitable enclosure from the Range of MK

Sentry Consumer Units.

2. Mount the RCBO(s) on to the DIN rail in the enclosure with the

L (Supply) terminal at the bottom (shown in Figure 1).

3. It is important that the RCBO is supplied via a Double Pole

Isolator (Switch Disconnector).

4. Strip the Supply Neutral Cable and the Load Cables to expose

11mm of conductor.

5. Connect the Supply Line to the Line (Supply) Terminal at the

bottom, using the busbar supplied with the Consumer Unit.
Alternatively, a suitable cable can be used, which should be
stripped to expose 12mm of conductor for connection.

6. Connect the Neutral (Blue) flying lead of the RCBO to the

Supply Neutral Terminal Bar.

7. Connect the Earth (Cream) flying lead of the RCBO to the

Supply Earth Terminal Bar.

8. Connect the Load, Line and Neutral connections to the

outgoing terminals at the top of the RCBO, marked L (OUT)
and N (OUT), respectively.

9. Connect the Load Earth conductor to the Earth Terminal Bar.

G. INSTALLATION

11

1. Insulation resistance tests

NOTE: Disconnect the L Load, N Load and Earth before
conducting Insulation resistance testing to avoid
damage to the RCBO unit.

2. After the installation is complete, turn on the supply to the

RCBO and check that the supply voltage to the product is
present at its L (Supply) and N (Supply) connection.

3. Switch on the RCBO by moving its switch dolly upwards to

show ‘ON’ position.  Press the Test Button on the device, the
device should trip.

IMPORTANT:

Upon completion, ensure that all terminal screws

are tightened to the correct torque values (Load, Line and Neutral
Terminal - 1.2 to 1.5 Nm, Supply Line Terminal - 2.0 to 2.5Nm).
10. Test the RCBO as detailed in Section H of this leaflet.
11. AFFIX LABEL SUPPLIED TO THE SENTRY

®

CONSUMER UNIT.

12. Leave this Instruction Leaflet with the end user for future use.

H. TESTING

12

4. Carry out the following tests using a calibrated RCD Tester.

Test Current Result

0.5

n

RCBO must not trip

n

RCBO must trip within 300 ms

2

n

RCBO must trip within 200 ms

5

n

RCBO must trip within 40 ms

If the device fails to trip as required in steps 3. and 4.
above, do not use the product.

Failure to trip according to 3. and 4. above, after it is
confirmed that the supply is present to the product, indicates
to a faulty product.  Consult a qualified electrician or contact,
MK Electric Technical Sales and Service Department.

Telephone: 01268 563720 (National)

+44 (0) 1268 563758 (International)

Maintenance

It is recommended that the RCBO is checked regularly, at least
quarterly.  Refer to Item 4 in Section E, Safety Instructions, of
this leaflet.

14

If the black portion of the switch is in the ‘OFF’
position, this is an indication that a fault has caused 
the RCBO to trip.

Consult the Fault Identification Chart (Figure 2) to
establish the cause.

Any repairs to appliances or alterations to the
installation, to correct the fault, should be carried 
out by a competent person.

I. TRIPPING IN SERVICE

15

The Company undertakes to replace or repair, at its discretion,
this product should it become defective within a period of 
10 years after delivery, solely as a result of faulty materials
and/or workmanship.  Understandably, if the product has not
been installed or maintained in accordance with the
Company’s instructions, has not been used appropriately, 
or if any attempt has been made to rectify, dismantle or alter
the product in any way, the guarantee will be invalidated.
This Guarantee states the Company’s entire liability.  It does
not extend to cover consequential loss or damage or
installation costs arising from the defective product.  This
Guarantee does not restrict or infringe the normal statutory
or other rights of the consumer.

MK Electric Limited wishes to make it clear that it will take 
all necessary legal action in any part of the world against
any party found to be manufacturing, distributing, selling or
otherwise dealing with any article which infringes the
company’s design rights, copyrights or patents in its
products, or any other rights of the company therein.
Design Right MK Electric Ltd.

J. GUARANTEE

Figure 2
Fault Identification
Chart (Section I.)

Reviews: