Mitsubishi SAF Series User Manual Download Page 11

Item 

Model No.

SAF150E7

Power Source

220-240V~  50Hz

Ventilation Mode

Heat Exchange Ventilation

Normal Ventilation

Notch

(Extra high)

High 

Low

(Extra high)

High 

Low

Input (W)

97-114

92-107

69-77

97-114

92-107

69-77

Air Volume (m

3

/h)

150

150

120

150

150

120

External Static Pressure 
(Pa)

80

70

25

80

70

25

Noise (dB)

28.5-29.0

28.0-29.0

19.5-21.5

28.5-29.0

28.0-29.0

19.5-21.5

Temperature Exchange 

Effiency(%)

75

75

77

Dimensions(mm)

Width 970 × Depth 467 × Height 270

Weight (kg)

25

Item 

Model No.

SAF250E7

Power Source

220-240V~  50Hz

Ventilation Mode

Heat Exchange Ventilation

Normal Ventilation

Notch

(Extra high)

High 

Low

(Extra high)

High 

Low

Input (W)

112-128

108-123

87-96

112-128

108-123

87-96

Air Volume (m

3

/h)

250

250

190

250

250

190

External Static Pressure 
(Pa)

105

95

45

105

95

45

Noise (dB)

30.0-31.5

29.5-30.5

23.5-26.5

30.0-31.5

29.5-30.5

23.5-26.5

Temperature Exchange 

Effiency(%)

75

75

77

Dimensions(mm)

Width 882 × Depth 599 × Height 270

Weight (kg)

29

Item 

Model No.

SAF350E7

Power Source

220-240V~  50Hz

Ventilation Mode

Heat Exchange Ventilation

Normal Ventilation

Notch

(Extra high)

High 

Low

(Extra high)

High 

Low

Input (W)

182-190

178-185

175-168

182-190

178-185

175-168

Air Volume (m

3

/h)

350

350

240

350

350

240

External Static Pressure 
(Pa)

140

60

45

140

60

45

Noise (dB)

32.5-33.0

30.5-31.0

22.5-25.5

32.5-33.0

30.5-31.0

22.5-25.5

Temperature Exchange 

Effiency(%)

75

75

78

Dimensions(mm)

Width 1050 × Depth 804 × Height 317

Weight (kg)

49

Specifications

9

PCH012A010.indb   9

2017/09/26   21:15:56

Summary of Contents for SAF Series

Page 1: ...gilt f r Bereiche mit einer Netzstromversorgung von 50 Hz Questo condizionatore d aria conforme alla seguente direttiva Macchinario 2006 42 CE Bassa tensione 2014 35 UE EMC 2014 30 UE RoHS 2011 65 UE...

Page 2: ...PCH012A010 indb 2 2017 09 26 21 15 53...

Page 3: ...PCH012A010 indb 1 2017 09 26 21 15 54...

Page 4: ...physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards...

Page 5: ...PCH012A010 indb 3 2017 09 26 21 15 54...

Page 6: ...PCH012A010 indb 4 2017 09 26 21 15 54...

Page 7: ...SAF150E7 Model No SAF350E7 SAF500E7 SAF800E7 SAF1000E7 970 A 1050 1090 1322 1322 467 B 804 904 884 1134 270 SAF250E7 882 599 270 C 317 317 388 388 Energy Recovery Ventilator Remocon Energy Recovery Ve...

Page 8: ...tor Remocon with certainty In particular suddenly turning the switch on and off will not only cause improper operation of the unit but will also affect the relay inside the switch and may damage it PC...

Page 9: ...For detail please refer to the Energy Recovery Ventilator Remocon manual PCH012A010 indb 7 2017 09 26 21 15 55...

Page 10: ...PCH012A010 indb 8 2017 09 26 21 15 55...

Page 11: ...112 128 108 123 87 96 112 128 108 123 87 96 Air Volume m3 h 250 250 190 250 250 190 External Static Pressure Pa 105 95 45 105 95 45 Noise dB 30 0 31 5 29 5 30 5 23 5 26 5 30 0 31 5 29 5 30 5 23 5 26...

Page 12: ...140 110 55 Noise dB 37 0 37 5 36 5 37 0 33 5 34 5 37 0 37 5 36 5 37 0 33 5 34 5 Temperature Exchange Effiency 75 75 76 Dimensions mm Width 1322 Depth 884 Height 388 Weight kg 71 Item Model No SAF1000E...

Page 13: ...Description of apparatus Heat Exchanger Unit Model name SAF Series Relevant EU Directives Machinery Directive 2006 42 EC Applied Standards EN 60335 1 Authorized representative in EU MITSUBISHI HEAVY I...

Page 14: ...Tokyo 108 8215 Japan http www mhi co jp aircon MITSUBISHI HEAVY INDUSTRIES AIR CONDITIONING EUROPE LTD 7 Roundwood Avenue Stockley Park Uxbridge Middlesex UB11 1AX United Kingdom Tel 44 20 7025 2750...

Reviews: