7
PARAMETER SETTING
7.3 MODBUS(R) Device Assignment Parameter
7.3.4 Specifying the error status read device
7
- 26
1
O
VER
VIE
W
2
SYS
T
E
M
CO
NF
IG
U
R
A
T
IO
N
3
S
P
E
CIFICA
TI
ONS
4
MODB
US
(R)
S
TA
NDA
RD
FUN
C
TIO
N
S
5
FUNC
TI
ON
6
PR
E
-O
PER
A
T
ION
AL
P
R
OCED
URE
S A
ND
SE
TTINGS
7
P
A
RA
MET
E
R S
E
TTI
N
G
8
UTIL
ITY P
A
CK
AGE
(G
X Co
nf
ig
u
rat
o
r-M
B)
7.3.4 Specifying the error status read device
Users can specify the data to be read out as an exception status when the QJ71MB91
(slave) receives Read Exception Status (FC:07) from the master.
(1) To specify the error status read device
Specify a read target device to the addresses shown below.
The 8 points from the specified bit device is regarded as a error status read device.
Figure 7.11 Relations between error status and error status read device
Table7.10 Error status read device specification
Address
Parameter name
Setting range
Default
000A
H
(10)
Error status read device specification
Device code
0000
H
: Device code not assigned
Other than 0000
H
: Device code
F000
H
000B
H
(11)
Head device number
0000
H
to FFFF
H
0000
H
M100
M107
M100 to M107
Device
R
Programmable
controller CPU
No sequence
program required
01
H
QJ71MB91 (Slave function)
Error status read device specification
Device memory
Exception status
Request message
(Sends Read Exception Status (FC:07))
Receives response message (exception
status 01
H
)
MODBUS
Master device
RS-232, RS-422 or RS-485
to
Summary of Contents for QJ71MB91
Page 1: ......
Page 2: ......
Page 366: ...App 14 Appendix 4 External Dimensions APPENDICES Memo ...
Page 371: ......
Page 372: ......