7
PARAMETER SETTING
7.3 MODBUS(R) Device Assignment Parameter
7.3.1 MODBUS(R) device assignment to the programmable controller CPU device memory
7
- 18
1
O
VER
VIE
W
2
SYS
T
E
M
CO
NF
IG
U
R
A
T
IO
N
3
S
P
E
CIFICA
TI
ONS
4
MODB
US
(R)
S
TA
NDA
RD
FUN
C
TIO
N
S
5
FUNC
TI
ON
6
PR
E
-O
PER
A
T
ION
AL
P
R
OCED
URE
S A
ND
SE
TTINGS
7
P
A
RA
MET
E
R S
E
TTI
N
G
8
UTIL
ITY P
A
CK
AGE
(G
X Co
nf
ig
u
rat
o
r-M
B)
2) Head device number
Set the head device number of the programmable controller CPU device
memory or the head address of the QJ71MB91 buffer memory to be assigned
to the MODBUS device.
3) Head MODBUS device number (Head coil number/Head input number/Head
input register number/Head holding register number)
As the head MODBUS device number, set the head number of the
MODBUS device of the assignment target (QJ71MB91).
Use the following expression to find a setting value of the head MODBUS
device number:
Head MODBUS device number = Last 5 digits of relevant MODBUS
device number - 1
Example: Set "5139" for the MODBUS device number, 105140.
The head MODBUS device number must not be duplicated among
Assignment 1 to 16.
Set unique head MODBUS device numbers.
The slave function of the QJ71MB91 does not run if any of the device number
settings are duplicated.
4) Assignment points
Set the device points of the programmable controller CPU device memory or
QJ71MB91 buffer memory to be assigned to the MODBUS device.
POINT
If the master requests the QJ71MB91 to access the area outside the valid
programmable controller CPU device range or the user free area in the
QJ71MB91 buffer memory, the QJ71MB91 will send an exception response to the
master.
Summary of Contents for QJ71MB91
Page 1: ......
Page 2: ......
Page 366: ...App 14 Appendix 4 External Dimensions APPENDICES Memo ...
Page 371: ......
Page 372: ......