background image

14 

 

 To connect an extension cable to the QA6ADP, remove a sticker on the 

IN side connector. 

Sticker

QA6ADP

Extension base unit

Base cover

IN side

 

 To connect an extension cable to the OUT side connector of the 

QA6ADP, remove the portion (lid) under the characters "OUT" by tools 
such as a flathead screwdriver (5.5 75, 6 100). 

QA6ADP

Extension base unit

Cutting one 

thin-walled part

Flathead screwdriver

Base cover

OUT side

 

 

Summary of Contents for QA6ADP

Page 1: ...itsubishi general purpose programmable logic controller MELSEC Q Series Prior to use please read both this manual and detailed manual thoroughly and familiarize yourself with the product MODEL QA6ADP U JE MODEL CODE 13JY50 IB NA 0800402 B 0803 MEE 2007 MITSUBISHI ELECTRIC CORPORATION ...

Page 2: ...Partial correction Section 2 2 6 1 This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual 2007 MITSUBISHI ELECTRIC CORPORATION ...

Page 3: ...oltage Drop of Extension Cable 17 7 EXTERNAL DIMENSIONS 18 GENERIC TERMS AND ABBREVIATIONS Unless otherwise specified this manual uses the following generic terms and abbreviations to explain the QA conversion adapter module Generic term Abbreviation Description A5 B Generic term for A52B A55B and A58B extension base units on which A series I O module and special function module can be mounted wit...

Page 4: ...3 B QA6 B A6 B Replace CPU with QCPU Mount the QA6ADP on the extension base unit A6 B Replace the main base unit A3 B with the extension base unit QA6 B QA6ADP POINT The QA6ADP is CE compliant To meet the EMC directive the extension base unit and module to be used in combination with the QA6ADP should be CE compliant When using a control line or communication cable keep it away from the main circu...

Page 5: ...r the first to seventh stages to extension stages from the one nearest to the main base unit 5 An extension cable connectable to the QA6ADP is the Q series extension cable only 6 Set the same stage number to both the stage number setting connector of the extension base unit and that of the QA6ADP 7 The QA6ADP A5 B A6 B cannot be used as the MELSECNET H remote I O station 8 The bus connection with ...

Page 6: ...n base unit where the QA6ADP is mounted Product name Model Remarks Power supply module A61P A61PN A62P A63P A61PEU A62PEU Power supply module I O slot mounting type A68P AC input module AX10 AX11 AX11EU AX20 AX21 AX21EU 6 AC DC input module AX31 AX31 S1 DC input module AX40 AX41 AX41 S1 AX42 AX42 S1 AX50 S1 AX60 S1 AX70 AX71 AX80 AX80E AX81 AX81 S1 AX81 S2 AX81 S3 AX81B AX82 Contact output module ...

Page 7: ...iction on the number of mountable modules Product name Model No of mountable modules Intelligent communication module AD51 AD51 S3 AD51H AD51H S3 6 Interrupt module AI61 AI61 S1 1 5 3 Using the A A1S module conversion adapter enables to use modules equivalent to the AnS module by the module shown in the table For the mountable modules refer to A A1S Module Conversion Adapter User s Manual IB 08003...

Page 8: ...ion location Control panel Overvoltage category 1 II max Pollution degree 2 2 max Equipment category Class I 1 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within premises Category II applies to equipment for which electrical power is supplied from fixed facilities The sur...

Page 9: ...nternal current consumption 110 mA External dimensions 1 130 mm 5 11 inch H 73 5 mm 2 89 inch W 74 2 91 inch mm D Weight 0 2 kg Adapter mounting screw M3 torque 0 36 to 0 48 N m Board fixing screw torque 0 61 to 0 82 N m 1 The external dimensions show values in a status where the QA6ADP is mounted on the extension base unit ...

Page 10: ...base unit Utilize screws used in the extension base unit Included parts 5 Mounting bracket fixing screw Screw for mounting an adapter module mounting bracket on the extension base unit Included parts 6 Base side stage number setting connector window Window is transparent so that a stage number setting connecter of the extension base unit side can be seen 7 Extension base unit mounting connector Co...

Page 11: ... made to the number of stages incorrect input or incorrect output will occur 1 Extension stage number setting of the QA6ADP The following describes how to set the number of extension stages of the QA6ADP Extension stage number setting 1st stage 2nd stage 3rd stage 4th stage 5th stage 6th stage 7th stage Stage number setting connector setting 2 Extension stage number setting of the extension base u...

Page 12: ...series extension cable to the QA6ADP and the upper lower base unit Disconnect the A series extension cable from the extension base unit Remove a base cover from the extension base unit Set the stage number setting connector of the extension base unit In case of the A5 B disconnect a lead of the FG terminal right side Among screws fixing a board of the extension base unit remove two at the left Scr...

Page 13: ...and bottom Remove the QA6ADP main body from the extension base unit Remove a board fixing screw and an adapter module mounting bracket of the QA6ADP Mount a screw fixing the board of the extension base unit at two parts on the left Completed QA6ADP Board fixing screw Adapter module mounting bracket Mounting guide Adapter module mounting screw Adapter module mounting screw Extension base unit IN si...

Page 14: ...Connector Ferrite core Holding a ferrite core may cause cable break inside the connector Also if the ferrite core is shifted the characteristic will change When handling the cable take care not to change position of the ferrite core 2 Connection of extension cable The following shows extension cables connectable to the QA6ADP Model Remarks QC05B 0 45m cable QC06B 0 6m cable QC12B 1 2m cable QC30B ...

Page 15: ...Extension base unit Base cover IN side To connect an extension cable to the OUT side connector of the QA6ADP remove the portion lid under the characters OUT by tools such as a flathead screwdriver 5 5 75 6 100 QA6ADP Extension base unit Cutting one thin walled part Flathead screwdriver Base cover OUT side ...

Page 16: ...ten fixing screws of the extension cable connector after connecting the extension cable Tightening torque 0 20 N m QA6ADP Extension base unit Flathead screwdriver Fixing screw 3 Disconnection of extension cable When disconnecting an extension cable hold and pull the connector part of the extension cable after making sure that fixing screws have been completely removed ...

Page 17: ...pply module mounted on the main base unit I3 I2 I0 I1 I4 IA IA IA Main base unit First extension stage Second extension stage Third extension stage Fourth extension stage Extension base unit QA6 B Extension base unit A5 B Extension base unit A5 B Extension base unit A6 B Power supply module Power supply module Power supply module Symbol Description I Rated current of power supply module on the mai...

Page 18: ...cription V Sum of voltage drop V1 Voltage drop due to an extension cable between the main base unit and the QA6 B Vn Voltage drop due to an extension cable between the extension base unit n 1th extension stage and the extension base unit nth extension stage R1 Resistance value of a cable between the main base unit and the extension base unit QA6 B Rn Resistance value of an extension cable between ...

Page 19: ... 2 91 I O POWER I O I O I O I O QA6ADP QA conversion adapter module 2 6 M4 screw for mounting module Handle 4 6mounting hole M5 mounting screw A series extension base unit that you have already had 9 0 35 Power supply module Extension cable 121 4 76 250 9 84 172 6 77 Power supply module Extension cable Unit mm inch ...

Page 20: ...es Barcelona Spain Tel 34 93 565 3131 France Mitsubishi Electric Europe B V French Branch 25 Boulevard des Bouvets F 92741 Nanterre Cedex France TEL 33 1 5568 5568 South Africa Circuit Breaker Industries Ltd Private Bag 2016 ZA 1600 Isando South Africa Tel 27 11 928 2000 Hong Kong Mitsubishi Electric Automation Hong Kong Ltd 10th Floor Manulife Tower 169 Electric Road North Point Hong Kong Tel 852...

Reviews: