8
5.3 Intelligent Function Module Switch setting
The intelligent function module switches are set using the I/O
assignment settings of GX Developer.
It can be easy to set by inputting using hexadecimal-4 digits.
* Setting any value within the setting range will provide the same operation. When
the setting range is 1
H
to F
H
, set 1
H
for example.
Table 5.1 Switch setting item
Switch No.
Setting item
Switch 1
Analog input range
Input range
setting value
4 to 20mA
(For 2-wire transmitter input)
0
H
4 to 20mA
(For current input)
6
H
Switch 2
0 to 20mA
(For current input)
7
H
4 to 20mA (Expanded mode)
(For 2-wire transmitter input)
A
H
4 to 20mA (Expanded mode)
(For current input)
C
H
User range setting
(For current input)
E
H
User range setting
(For 2-wire transmitter input)
F
H
Switch 3
Empty
Switch 4
Switch 5
0
H
: Fixed
CH4 CH3
Input range setting
(CH1 to CH4)
CH2 CH1
H
H
00
H
: Fixed
0
H
: Normal resolution mode
1
H
to F
H
(value other than 0
H
)
*
: High resolution mode
0
H
: Normal mode (A/D conversion processing)
1
H
to F
H
(value other than 0
H
)
*
: Offset/gain setting mode